Sprinklers » Residential » Residential Sprinklers
A-10 One Inch Adjustable Flat Plate Concealed Pendent 4.9K Model GL4906
"The Inch" Residential Automatic Sprinklers Model GL4906 One Inch Adjustable Flat Plate Concealed Pendent
Description and Operation
The Globe Model GL4906 Residential One Inch Adjustable Concealed Pendent Sprinkler has a flat plate profile that utilizes a 3mm frangible glass ampule as the thermosensitive element. It features economy, aesthetics and the lowest allowable water flow with a nominal 1" of adjustment for easier installation. The combination of the 3mm frangible glass ampule and specially designed deflector make the Model GL4906 the ultimate in life safety and fire control. It has met the strict requirements of Underwriters Laboratories Inc. as described in UL Standard, 1626, for Residential Sprinklers for Fire Protection Service, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction.
All that is seen at the ceiling is the 3 5/16" diameter flat ceiling plate color finished to match the specifier's exact requirements. The ceiling plate is soldered to the sprinkler's special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the residential pendent spray sprinkler. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass bulb to shatter. This results in water discharge which is distributed in an approved pattern.
Technical data
- Temperature Rating - 155°F (68°C)
- Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating - -67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
Specifications and Approvals
| Sin Model | K Factor | Thread Size | Length | Finishes | 155°F 68°C | cULus |
|---|---|---|---|---|---|---|
| GL4906 | 4.9 (68 metric) |
1/2" NPT | 3" (7.6 cm) |
Bright Chrome |
• | • |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order. for painted plates other than white, contact Globe for ordering specifications.
Cross Section

Click image above for a detailed view of this product.
Installation Data for Flat and Sloped Ceilings**
| Model | Maximum Area of Coverage | Minimum Water Discharge & Pressures Needed Per Sprinkler* |
|---|---|---|
| GL4906 | 12' x 12' | 13 G.P.M. - 7 P.S.I. |
| 14' x 14' | 13 G.P.M. - 7 P.S.I. | |
| 16' x 16' | 13 G.P.M. - 7 P.S.I. | |
| 18' x 18' | 17 G.P.M. - 12 P.S.I. | |
| 20' x 20' | 20 G.P.M. - 16.7 P.S.I. |
*When these sprinklers are used in NFPA 13 systems, A 0.1 design density minimum shall be utilized.
**Refer to page 2 of the Globe Residential Sprinkler Installation Guide for NFPA 13D and 13R requirements.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 332765
- Quantity - Protective Caps - P/N 332868
| Cover Plate Size | White 135°F Part # | Chrome 135°F Part # |
|---|---|---|
| 3 5/16" | 332892 | 332891 |
Product Related Documents
Download this page as a pdfSprinklers » Sprinkler Accessories
B-3 Clean Room Cover Plates
Cover Plate with a Gasket Seal for Clean Room Application
Cover Plates
The Seal is intended for areas where it is desirable to stop air travel through the cover plate from the area above the ceiling.
For "The Inch" Standard Response GL5653, For Full Description See Pages: A-69-CR
- Chrome: 332739
- White: 332737
- Chrome: 332740
- White: 332741
155°F (68°C) with plate 135°F (57°C); 155°F (68°C) with plate (68°C);
175°F (79°C) with plate 155°F (68°C); 200°F (93°C) with plate 155°F
(68°C)
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-3 Concealed Cover Plates
Concealed Cover Plates to Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D, & E
Concealed Cover Plates
For "The Inch" Quick Response GL5606 & Standard Response GL5653
- Chrome: 332821
- White: 332822
- Chrome: 332827
- White: 332828
- cULus Approved: GL5653 -135°F (57°C) with plate 135°F
(57°C);155°F (68°C) with plate 135°F (57°C); 155°F (68°C)
with plate (68°C); 175°F (79°C) with plate 155°F (68°C); 200°F
(93°C) with plate 155°F (68°C)
For full descriptions see pages: A-38-EQ, & A-69-EQ
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-3 Recessed Escutcheons
Recessed Escutcheons to Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D, & E
Recessed Escutcheons
2 Pc. Recessed
1/2" Adjustable
- Chrome: 326201
- White: 326203-W
- Chrome: 326208
- White: 326210-W
3/4" Adjustable
- Chrome: 326170
- White: 326172-W
- Chrome: 326177
- White: 326179-W
1/2" Adjustable Recessed Model Numbers
- cULus Approved: 2810,4110,4210,4230,4231,
4234,4710,5628,5630,5631,8101,8107,8128,8129,
8151 & 8174 - cULUs & FM Approved: 5601,8106, 8156 & 5635
3/4" Adjustable Recessed Model Numbers Seismic
- cULus Approved:2801,2826,2851,2870,4201,4226,
4231,4251,4270,5601,5602,5626,5628,5635,5636,5641,
5642,5652,5670,5680,5685,5686,8101,8102,8152,8106,
8107,8109,8127,8128,8129,8135,8141,8157,8159,8171,
8174,8179,8185 - cULus & FM Approved: 5651, 8156, 8151 & 5679
For full descriptions see pages:: A-24-EQ, A-41-EQ, A-55-EQ, A-67-EQ, A-76-EQ & A-90-EQ
Download this page as a pdf
Dry Sprinklers » Dry Type Pendent
A-90EQ Automatic Sprinklers GL Series Dry Type Recessed Pendent
Automatic Sprinklers GL Series Dry Type Recessed Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe GL Series Dry Type Pendent Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm
- Orifice insert - brass
- 3/4" or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable |
Bright Chrome White Polyester |
| 8.1 | (116 metric) | 1" NPT | FM Variable to 36" |
|
Note:
- Metric conversions are approximate.
- cULus listed corrosion resistant: Polyester must be specified on order.
- 1Finishes available on special order.
- 2 Wax Coating cULus listed up to 200°F
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | *FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Recessed Pendent |
GL5679 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5680 | 5.6 | ¾" NPT | • | • | • | • | • | • | – | • | |
| GL8179 | 8.1 | 1" NPT | • | • | • | • | • | • | – | • |
Note:
- Listed for all hazards
- FM Approved 155°F and 200°F only.
Cross Section
Click image above for a detailed view of this product
Installation Data
Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Download this page as a pdf
Sprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Pendent
A-76EQ Extended Coverage Light Hazard Automatic Sprinklers Model GL8159 Pendent
Extended Coverage Light Hazard Automatic Sprinklers Model GL8159 Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe Model GL8159-EQ Extended Coverage Pendent Sprinkler for Light Hazard occupancies is a low profile yet durable design which utilizes a 5mm frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it serves to protect various light hazard area coverages and should be installed in accordance with NFPA 13. This sprinkler series is available in four temperature ratings and several finishes to meet many varying design requirements.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler, and escutcheon are not factory assembled. Assembly is done at the time of installation.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (74°C)
200°F (93°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 8.1 | (116 metric) | 3/4" NPT | 3" (7.6 cm) | Factory Bronze *Satin Chrome Bright Chrome White Polyester+ Black Polyester+ *Lead Coated+ |
Note:
- Metric conversions are approximate.
- *Finishes available on special order.
- +Available as UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | cULus |
|---|---|---|---|---|---|---|---|
| Pendent | GL8159 | 8.1 | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards Only
| Style | TEMP | Area of Coverage | MIN. PRESSURE P.S.I. | FLOW G.P.M. |
|---|---|---|---|---|
| Recessed Pendent | 135°F / 57°C 155°F / 68°C 175°F / 79°C 200°F / 93°C |
16' x 16' | 10.3 | 26 |
| 18' x 18' | 16.6 | 33 | ||
| 20' x 20' | 24.4 | 40 |
Note: Due to the high spray pattern created by the spinkler, there must be a minmum spacing of 8'-0" between sprinklers to eliminate the risk of cold soldering.
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
Download this page as a pdf
Dry Sprinklers » Dry Type Pendent
A-55EQ Quick Response Automatic Sprinklers GL Series Dry Type Recessed Pendent
Quick Response Automatic Sprinklers GL Series Dry Type Recessed Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe Quick Response GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe Quick Response GL Series Dry Type Pendent Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable |
Bright Chrome White Polyester |
| 8.1 | (116 metric) | 1" NPT | FM Variable to 36" |
|
Note:
- Metric conversions are approximate.
- cULus listed corrosion resistant: Polyester must be specified on order.
- 1Finishes available on special order.
- 2Lead coated is cULus approved only.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | *FM | cULus |
|---|---|---|---|---|---|---|---|---|---|---|
| Recessed Pendent |
GL5635 | 5.6 | 1" NPT | • | • | • | • | • | • | • |
| GL5636 | 5.6 | ¾" NPT | • | • | • | • | • | – | • | |
| GL8135 | 8.1 | 1" NPT | • | • | • | • | • | – | • |
Note:
- Listed for all hazards
- FM Approved 155°F and 200°F only.
Cross Section
Click image above for a detailed view of this product
Installation Data
Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
For further important installation data, please refer to our Dry Sprinkler Caution Sheet.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Pendent
A-41EQ Extended Coverage Light Hazard Automatic Sprinklers Model GL8109
Extended Coverage Light Hazard Automatic Sprinklers Model GL8109 Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe Quick Response Model GL8109-EQ Extended Coverage Pendent Sprinkler for Light Hazard occupancies is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermo sensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While this Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard light hazard extended coverage pendent sprinklers are specified; but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction, in accordance with their listings and in accordance with NFPA 13.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
Technical Data
- Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C) - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 8.1 | (116 metric) | 3/4" NPT | 3" (7.6 cm) | Bright Chrome White Polyester+ |
NOTE:
- Metric conversions are approximate.
- +Available as cULus listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | cULus |
|---|---|---|---|---|---|---|---|
| Pendent |
GL8109 | 8.1 | • | • | • | • | • |
| Sin Model | Style | Temp. | Area of Coverage | Min. Pressure P.S.I. | Flow in G.P.M. |
|---|---|---|---|---|---|
| GL8109 |
Recessed | 135°F/57°C 155°F/68°C 175°F/79°C 200°F/93°C |
16' x 16' |
10.3 | 26 |
| 18' x 18' | 16.6 | 33 | |||
| 135°F/57°C | 20' x 20' | 24.4 | 40 |
NOTE:
- Due to high spray pattern created by this sprinkler, there must be a minimum spacing of 8'-0" between sprinklers to eliminate the risk of cold soldering.
Cross Sections

Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Download this page as a pdf
Sprinklers » Standard Spray Sprinklers » Standard Response - Standard Spray Sprinkler
A-67EQ Automatic Sprinklers GL Series Dry Type Recessed Pendent
Automatic Sprinklers GL Series Recessed Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E

The GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements.
The heart of Globe’s GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass, causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C),
200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze Satin Chrome2 Bright Chrome White Polyester3 Black Polyester3 Lead Coated2 |
| 4.2 | (59 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 7.8 | (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- 2 Finishes available on special order.
- 3 Available as cULus listed corrosion resistant when specified on order.
| Style | Sin Model | K Factor | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | **286°F 141° C | †cULus | FM | LPC | CE | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Pendent Recessed |
GL2851 | 2.8 | • | • | • | • | • | • | — | — | — | • |
| GL4251 | 4.2 | • | • | • | • | • | • | — | — | — | • | |
| GL5651 | 5.6 | • | • | • | • | • | • | • | • | • | • | |
| GL8151* | 7.8* | • | • | • | • | • | • | • | — | — | • | |
| GL8156 | 8.1 | • | • | • | • | • | • | •$ | • | • | • |
Note:
- † 5.6K Orifice, 7.8K Orifice and 8.1K Orifice listed for all hazards.
- *7.8" X 1/2" NPT
- ** 286°F cULus listed only.
$ Brass finish only

Click image above for a detailed view of this product.
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325391, Rev. F (1/2"); P/N 325401, Rev. D (L.O.)
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Sprinklers » Standard Spray Sprinklers » Quick Response - Standard Spray Sprinkler
A-24EQ Automatic Sprinklers GL Series Recessed Pendent
Automatic Sprinklers GL Series Recessed Pendent To Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe Quick Response GL Series Sprinkler is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While the Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe’s GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
The use of the 4 1/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
Technical Data
- Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/4" (5.7 cm) |
Chrome White Polyester1 |
| 4.2 | (59 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 7.8 | (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
NOTE:
- Metric conversions are approximate.
- 1cULus listed corrosion ressistant - Polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | **286°F 141°C | cULus | FM†† | LPC | CE | NYC-DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Pendent Recessed |
GL2801 | 2.8 | • | • | • | • | • | • | — | — | — | • |
| GL4201 | 4.2 | • | • | • | • | • | • | — | — | — | • | |
| GL5601 | 5.6† | • | • | • | • | • | • | • | • | • | • | |
| GL8101 | 7.8† | • | • | • | • | • | • | • | — | — | • | |
| GL8106 | 8.1† | • | • | • | • | • | • | • | • | • | • |
NOTE:
- † 5.6K orifice, 7.8K orifice and 8.1K orifice listed for all hazards.
**286°F cULus listed only.
Upright vertical sidewall cULus listed for 9' min. spacing.
††1/2" Recessed escutcheons are required for FM approved sprinklers.
Cross Sections

Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325391 (1/2"); P/N 325401, Rev. F (L.O.)
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Download this page as a pdf
Sprinklers » Residential » Residential Sprinklers
A-3 Automatic Sprinklers Model GL3010
Automatic Spinklers Model GL3010 Pendent Recessed Pendent
Description and Operation
The Globe Model GL3010 Residential Sprinkler has a low profile yet durable design, which utilizes a 3mm frangible glass ampule as the thermosensitive element. It features economy, aesthetics and low flow.
The combination of the 3mm frangible glass ampule and specially designed deflector makes the Model GL3010 Residential Sprinkler the ultimate in life safety and fire control. This Globe Pendent and Recessed Pendent Residential Sprinkler has met the strict requirements of Underwriters Laboratories Inc. as described in the UL Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction.
The heart of Globe's Model GL3010 sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Rating - 155°F (68°C)
- Water Working Pressure Rating - 175 psi (12 Bars).
- Factory tested hydrostatically to 500 psi (34 Bars).
- Maximum low temperature glass bulb rating is
-67°F (-55°C). - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size.
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
Specifications and Approvals
| Sin Model | K Factor | Thread Size | Length | Finishes | 155°F 68°C | NYC-DOB MEA 101-92-E |
|---|---|---|---|---|---|---|
| GL3010 | 3.0 (42 metric) |
1/2" NPT | 2 1/2" (6.4 cm) | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
• | • |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2C-U.L. Listed Corrosion Resistant - Polyester must be specified on order.
Cross Section
Click image above for a detailed view of this product.
Installation Data for Flat and Sloped Ceilings**
Pendent and Recessed Pendent
| Maximum Area of Coverage | Minimum Water Discharge & Pressures Needed Per Sprinkler* |
|---|---|
| 12' x 12' | 8 G.P.M. - 7.1 P.S.I. |
| 14' x 14' | 10 G.P.M. - 11.1 P.S.I. |
*When these sprinklers are used in NFPA 13 systems, a 0.1 design density minimum shall be utilized.
**Refer to page 2 of the Globe Residential Sprinkler Installation Guide for NFPA 13D and 13R requirements.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390
- Quantity - Recessed Wrenches - P/N 325391
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ¾” NPT Recessed Wrench 325401
¾" NPT RECESSED WRENCH
P/N 325401
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 Residential Sidewall Recessed Wrench (327102)
RESIDENTIAL SIDEWALL RECESSED WRENCH
P/N 327102
Download this page as a pdf
Sprinklers » Sprinkler Accessories » Dry Sprinklers » Dry Type Accessories
B-4 Dry Sprinkler Recessed Wrench (337014)
DRY SPRINKLER RECESSED WRENCH
P/N 337014
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ¾” NPT EXTRA LARGE ORIFICE WRENCH (333010)
¾" NPT EXTRA LARGE ORIFICE WRENCH
P/N 333010
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 1/2” NPT 1” Adjustable Concealed Wrench (332765)
1/2" NPT 1" ADJUSTABLE CONCEALED WRENCHP/N 332765
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ½” NPT MILLENNIUM WRENCH (332334)
½" NPT MILLENNIUM WRENCH
P/N 332334
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ½” NPT Recessed / Concealed Wrench (325391)
½" NPT RECESSED / CONCEALED WRENCH
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ¾” NPT Standard Wrench (312366)
¾" NPT STANDARD WRENCH
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-4 ½” NPT Standard Wrench (325390)
½" NPT STANDARD WRENCH
Download this page as a pdf
Sprinklers » Standard Spray Sprinklers » Quick Response - Standard Spray Sprinkler
A-26 Automatic Sprinklers GL Series 10MM Upright • Pendent • Recessed Pendent
Quick Response Automatic Sprinklers GL Series 10MM
Upright • Pendent • Recessed Pendent
Description and Operation
The Globe Quick Response GL Series 10mm Sprinklers are a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While the Quick Response 10mm Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified when allowed by the applicable standards. It offers the additional feature of greatly increased safety to life and is available in various styles, temperature ratings and finishes to meet many varying design requirements. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler-proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands, increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass, causing the glass to shatter. This results in water discharge which is distributed in an approved pattern, depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. Assembly is done in the field.
Technical Data
- Temperature Ratings - 57°C (135°F), 68°C (155°F), 79°C (175°F), 93°C (200°F), 141°C (286°F)
- Water Working Pressure Rating - 12 Bars
- Factory tested hydrostatically to 34 Bars
- Maximum low temperature glass bulb rating is
-55°C (-65°F ).
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 57°C/68°C | 135°F/155°F | Orange/Red | 38°C | 100°F |
| Intermediate | 79°C/93°C | 175°F/200°F | Yellow/Green | 66°C | 150°F |
| High | 141°C | 286°F | Blue | 107°C | 225°F |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 57 METRIC | 10mm (ISO 7/1-R3/8) |
5.7 cm | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as c-UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 57°C (135°F) | 68°C (155°F) | 79°C (175°F) | 93°C (200°F) | 141°C (286°F) | cULus |
|---|---|---|---|---|---|---|---|---|
| Upright | GL4221 | 57 Metric | • | • | • | • | • | • |
| Pendent Recessed Pendent |
GL4202 | 57 Metric | • | • | • | • | • | • |
Cross Sections
Ordering Information
When ordering, please specify the following:
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390
Download this page as a pdf
Sprinklers » Standard Spray Sprinklers » Standard Response - Standard Spray Sprinkler
A-64 Automatic Sprinklers GL Series 10MM Upright • Pendent • Recessed Pendent
Automatic Sprinklers GL Series 10MM
Upright • Pendent • Recessed Pendent
Description and Operation
The Globe GL Series10mm Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the10mm sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified. This sprinkler series is available in various styles, temperature ratings and finishes to meet varying design requirements.
The heart of Globe's GL Series sprinkler-proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands, increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass, causing the glass to shatter. This results in water discharge which is distributed in an approved pattern, depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. Assembly is done in the field.
Technical Data
- Temperature Ratings - 57°C (135°F), 68°C (155°F), 79°C (175°F), 93°C (200°F), 141°C (286°F), 182°C (360°F)
- Water Working Pressure Rating - 12 Bars
- Factory tested hydrostatically to 34 Bars
- Maximum low temperature glass bulb rating is
-55°C (-65°F ).
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 57°C/68°C | 135°F/155°F | Orange/Red | 38°C | 100°F |
| Intermediate | 79°C/93°C | 175°F/200°F | Yellow/Green | 66°C | 150°F |
| High | 141°C | 286°F | Blue | 107°C | 225°F |
| Extra High | 182°C | 360°F | Mauve | 149°C | 300°F |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 57 METRIC | 10mm (ISO 7/1-R3/8) |
5.7 cm | Factory Bronze Satin Chrome1 Bright Chrome3 White Polyester3 Black Polyester3 Wax Coated2,3 Lead Coated1,3 Wax Over Lead2,3 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2 Wax Coating UL listed up to 200°F only.
- 3cUL listed corrosion resistant polyester must be specified on order.
Approvals
Note:
| Style | Sin Model | K Factor | 57°C 135°F | 68°C 155°F | 79°C 175°F | 93°C 200°F | 141°C 286°F | 182°C 360°F | cULus |
|---|---|---|---|---|---|---|---|---|---|
| Upright | GL4262 | 57 Metric | • | • | • | • | • | • | • |
| Pendent Recessed Pendent |
GL4252 | 57 Metric | • | • | • | • | • | • | • |
Cross Sections
Ordering Information
When ordering, please specify the following:
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390
Sprinklers, Nozzles & Accessories
![]()
![]()
Download this page as a pdf
Sprinklers » Standard Spray Sprinklers » Concealed Pendent » "The Inch" for Seismic Applications
A-69EQ “The Inch” Adjustable Concealed Pendent Sprinkler Seismic Application - GL5653
Automatic Sprinklers
"The Inch"
Model GL5653 One Inch
Adjustable Concealed Pendent
with Cover Plate to meet IBC-ASCE/SEI 7 Codes for Seismic Areas C,D, & E.
Description and Operation
The Globe GL5653 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. The 4 1/2" diameter cover plate allows for 1" clearance around the sprinkler body and meets the IBC-ASCE/SEI 7 requirements for the use in seismic design categories C, D, & E. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 5mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 5mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin based solution, 5mm size
- Drop Pin - stainless steel
- Cover Plate - brass
- Upper Escutcheon Assembly - plated steel
- Note: Globe's wrench P/N 332765 must be used to install this sprinkler.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|---|
| Adjustable Concealed Pendent |
GL5653 | 5.6 | • | • | • | • | • | • |
Cross Section
|
CEILING PLATES | White 135°F Part # | White 155°F Part # | Chrome 135°F Part # | Chrome 155°F Part # |
|---|---|---|---|---|
| 332822 | 332828 | 332821 | 332827 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Adjustable Concealed Wrenches - P/N 332765
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » "The Inch" for Clean Rooms
A-69CR “The Inch for Clean Rooms” One Inch Adjustable Concealed Pendent Model GL5653
Automatic Sprinklers
"The Inch for Clean Rooms"
Automatic Sprinklers
One Inch Adjustable
Concealed Pendent Model GL5653
Description and Operation
The Globe GL5653 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. All that is seen at the ceiling is a 3 3/8" diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling.
The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed with a nominal 1" inch of adjustment.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern.
Features
- Cover Plate with a gasket seal assembly for dust free environment, such as "Clean Rooms".
- Nominal 1" of Adjustment.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin based solution, 5mm size
- Drop Pin - stainless steel
- Cover Plate - brass
- Upper Escutcheon Assembly - plated steel
- Gasket Seal - Santoprene
- Note: Globe's wrench P/N 332765 must be used to install this sprinkler.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted Other Painted Finishes1 (Gasket color White only) |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|---|
| Adjustable Concealed Pendent |
GL5653 | 5.6 | • | • | • | • | • | • |
Cross Section
| White 135°F Part # | White 155°F Part # | Chrome 135°F Part # | Chrome 155°F Part # | Min. Ceiling Hole Dia. |
|---|---|---|---|---|
| 332737 | 332741 | 332739 | 332740 | 2 1/4" |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Adjustable Concealed Wrenches - P/N 332765
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » "The Inch" for Seismic Applications
A-38EQ “The Inch” Automatic Sprinkler Seismic Application - Model GL5606
Quick Response
"The Inch" Automatic Sprinklers Model GL5606, One Inch Adjustable Concealed Pendent
w/Cover Plate to Meet IBC-ASCE/SEI 7 Codes for Seismic Areas C, D & E
Description and Operation
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. The 4 1/2" diameter cover plate allows for 1" clearance around the sprinkler body and meets the IBC-ASCE/SEI 7 requirements for the use in seismic design categories C, D, & E. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Drop Pin - stainless steel
- Cover Plate - brass
- Upper Escutcheon Assembly - plated steel
- NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes* |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted |
Note:
- Metric conversions are approximate.
- *Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|---|
| Adjustable Concealed Pendent |
GL5606 | 5.6 | • | • | • | • | • | • |
Cross Section
| White 135°F Part # | White 155°F Part # | Chrome 135°F Part # | Chrome 155°F Part # |
|
|---|---|---|---|---|
| Ceiling Plates | 332822 | 332828 | 332821 | 332827 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Adjustable Concealed Wrenches - P/N 332765
Product Related Documents
Download this page as a pdfSprinklers » Caution Sheets
The Inch Caution Sheet
"The Inch" Automatic Sprinklers Model GL5653 & GL5606 One Inch Adjustable Concealed Pendent
Installation Instructions - Read Carefully
Position
Commercial or Residential Pendent Spray Sprinkler. Install in pendent position only.
Warning
Sprinklers contained in this carton have been manufactured and tested in accordance with the applicable standards or where applicable under the inspection of Underwriters Laboratories Inc., and FM Approvals.
Any alteration to the sprinkler after it leaves the factory including, but not limited to painting, plating, coating or other alteration, may render the sprinkler inoperative and will nullify the Listing of Underwriters Laboratories Inc., and FM Approvals.
Glass bulbs are very fragile. Handle with extreme care. Sprinklers should be kept in the carton provided with dividers at all times prior to installation. Sprinklers should never come in direct contact with one another or any other foreign object prior to installation. Do not place sprinklers in a bucket. Globe Fire Sprinkler Corporation is not responsible for glass bulb damage due to improper handling.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Important Precautions to Follow
- Globe Sprinklers are to be installed in accordance with the latest published standards of the National Fire Protection Association, Globe Sprinkler data sheets, Government agencies and/or other similar organizations and to meet local codes and ordinances.
- The protective cover provided is to be installed after sprinkler installation for integrity as long as work is being done by any contractor in the area. This prevents accidental sprinkler damage. Protective caps are to be removed when cover plates are installed.
- Care should be taken not to bend deflector drop pins at installation. Deflector is to fall freely after installation.
- Never install a sprinkler after it has dropped to the floor or been injured in any way. These sprinklers should be discarded.
- Never install sprinklers in the fittings until the piping is in place on the ceiling as sprinklers are liable to be injured if screwed into the fittings when the lines are made up at the bench.
- Never paint or whitewash sprinklers as this is liable to prevent their operation in a fire.
- Never install sprinklers in pendent position on a dry system unless of a type designed for this purpose and as permitted by NFPA 13 and the authority having jurisdiction.
- Never attach wiring, ropes or fixtures to sprinkler or sprinkler piping.
- Globe's wrench P/N 332765 must be used to install this sprinkler.
- Sprinklers must remain separated from each other at all times. Allowing metal parts to come in contact with the glass bulb can cause damage, causing premature operation.
- Store sprinklers in cool, dry place and preferably in their shipping carton.
- Sprinklers of proper rating must be carefully selected to meet the temperature conditions where they are located (see table on reverse side for available temperatures). 175°F (79°C) or lower sprinklers should not be installed in locations less than 30" above or 12" to one side of steam pipes, heating coils or radiators. 200°F (93°C) sprinkler should be used under skylights where exposed to direct sun rays. Consult the local authority having jurisdiction to determine the proper temperature ratings in special locations such as:
- Areas near unit heaters.
- Areas where low pressure blow-off discharges into a large room.
- Areas in an unventilated concealed space under uninsulated wood or tin roofs.
- Areas in an unventilated attic.
- Areas in a shed with an unventilated peak roof or thin boards or metal.
- Areas where show windows have high powered electric illumination processes.
- Areas where a locomotive enters a building.
- Areas in other locations where special consideration is necessary.
- Inspect sprinklers regularly for mechanical damage, corrosion, paint and dust buildup as outlined in NFPA publications.
- All automatic sprinklers should be replaced in accordance with the latest NFPA 25 requirements, or as conditions warrant.
- When replacing sprinklers in any system, make sure those replacements are of the same style, size, and temperature rating as those removed.
- Should a change in building structure, occupancy or temperature conditions indicate a probable change in sprinkler requirements, notify the insurance carrier or other qualified inspection agency immediately. Do not make any changes without the authorization of one of these agencies.
- Maintain an extra stock of sprinklers and wrenches in a cabinet as required by NFPA 13.
- Concealed sprinklers and recessed sprinklers should not be used if the space above the ceiling is used for delivery (positive pressure) in an HVAC system.
- Globe Fire Sprinkler Corporation sprinklers have been tested, listed or approved by the agencies noted on the individual sprinkler data sheet. Acceptance by other agencies or authorities is not the responsibility of Globe Fire Sprinkler Corporation. Globe Fire Sprinkler Corporation is not liable for any costs arising as a result of any changes to listings or approvals after shipment. The Seller makes no warranties express or implied including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose except as expressly stated in seller's sales contract or sales acknowledgment form.
Download this page as a pdf
Sprinklers » Caution Sheets
Millennium Caution Sheet
Automatic Sprinklers Millennium GL Series Caution
Installation Instructions - Read Carefully
Position
Commercial or Residential Pendent Spray Sprinkler. Install in pendent position only.
Warning
Sprinklers contained in this carton have been manufactured and tested in accordance with the applicable standards and under the inspection of Underwriters Laboratories Inc.
Any alteration to the sprinkler after it leaves the factory, including, but not limited to, painting, plating, coating or other alteration, may render the sprinkler inoperative and will nullify the Listing of Underwriters Laboratories Inc. Glass bulbs are very fragile. Handle with extreme care. Sprinklers should be kept in the carton provided with dividers at all times prior to installation. Sprinklers should never come in direct contact with one another or any other foreign object prior to installation. Do not place sprinklers in a bucket. Globe Fire Sprinkler Corporation is not responsible for glass bulb damage due to improper handling.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color |
N.F.P.A. Maximum |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Important Precautions to Follow
- Globe Sprinklers are to be installed in accordance with the latest published standards of the National Fire Protection Association, Globe Sprinkler data sheets, Government agencies and/or other similar organizations and to meet local codes and ordinances.
- Never install an Upright Spray Sprinkler in a pendent position or a Pendent Spray Sprinkler in an upright position.
- Use only a special sprinkler wrench to install sprinklers. Any other wrench is liable to injure the sprinkler.
- The protective cover should be left on as long as work is being done by any contractor in the area to prevent accidental damage.
- Never install a sprinkler after it has dropped to the floor or been injured in any way. These sprinklers should be discarded.
- Never install sprinklers in the fittings until the piping is in place on the ceiling as sprinklers are liable to be injured if screwed into the fittings when the lines are made up at the bench.
- Never paint or whitewash sprinklers as this is liable to prevent their operation in a fire.
- Never install sprinklers in pendent position on a dry system unless of a type designed for this purpose and as permitted by NFPA 13 and the authority having jurisdiction.
- Never attach wiring, ropes or fixtures to sprinkler or sprinkler piping.
- Sprinklers must remain separated from each other at all times. Allowing metal parts to come in contact with the glass bulb can cause damage, causing premature operation.
- Wax Coated, Lead Plated or Wax over Lead sprinklers should be used in all locations subject to corrosion from acid fumes, chemicals, processes, etc. Extreme care must be exercised when installing to avoid damage to coating.
- Use sprinkler guards on all sprinklers subject to injury by moving objects.
- Store sprinklers in cool, dry place and preferably in their shipping carton.
- Sprinklers of proper rating must be carefully selected to meet the temperature conditions where they are located (see table below for available temperatures). 175°F (79°C) or lower sprinklers should not be installed in locations less than 30" above or 12" to one side of steam pipes, heating coils or radiators. 200°F (93°C) sprinkler should be used under skylights where exposed to direct sun rays. Consult the local authority having jurisdiction to determine the proper temperature ratings in special locations such as:
- Areas near unit heaters.
- Areas where low pressure blow-off discharges into a large room.
- Areas in an unventilated concealed space under uninsulated wood or tin roofs.
- Areas in an unventilated attic.
- Areas in a shed with an unventilated peak roof or thin boards or metal.
- Areas where show windows have high powered electric illumination processes.
- Areas where a locomotive enters a building.
- Areas in other locations where special consideration is necessary.
- Inspect sprinklers regularly for mechanical damage, corrosion, paint and dust buildup as outlined in NFPA publications.
- All automatic sprinklers should be replaced in accordance with the latest NFPA 25 requirements, or as conditions warrant.
- When replacing sprinklers in any system, make sure those replacements are of the same style, size, and temperature rating as those removed.
- Should a change in building structure, occupancy or temperature conditions indicate a probable change in sprinkler requirements, notify the insurance carrier or other qualified inspection agency immediately. Do not make any changes without the authorization of one of these agencies.
- Maintain an extra stock of sprinklers and wrenches in a cabinet as required by NFPA 13.
- Concealed sprinklers and recessed sprinklers should not be used if the space above the ceiling is used for delivery (positive pressure) in an HVAC system.
- Globe Fire Sprinkler Corporation sprinklers have been tested, listed or approved by the agencies noted on the individual sprinkler data sheet. Acceptance by other agencies or authorities is not the responsibility of Globe Fire Sprinkler Corporation. Globe Fire Sprinkler Corporation is not liable for any costs arising as a result of any changes to listings or approvals after shipment. The Seller makes no warranties express or implied including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose except as expressly stated in seller's sales contract or sales acknowledgment form.
Download this page as a pdf
Sprinklers » Caution Sheets » Dry Sprinklers » Dry Type Caution Sheets
GL Series Dry Type Caution Sheet
Automatic Sprinklers GL Series Dry Type Cautions
Installation Instructions - Read Carefully
Standard and Large Orifice Upright Sprinkler. Install in upright position only. Identified by "SSU" on deflector. Standard and Large Orifice Pendent Sprinkler. Install in pendent position only. Identified by "SSP" on deflector. Standard and Large Orifice Horizontal Sidewall Sprinkler. Install in horizontal position only. Identified by "TOP" on deflector. Standard and Large Orifice Vertical Sidewall Sprinkler. Install in the upright or pendent positions. Identified by "FLOW" on deflector.
Warning
Sprinklers contained in this carton have been manufactured and tested in accordance with the applicable standards or where applicable under the inspection of Underwriters Laboratories Inc., and FM Approvals. See individual data sheets for specific approvals.
Any alteration to the sprinkler after it leaves the factory including, but not limited to painting, plating, coating or other alteration, may render the sprinkler inoperative and will nullify the listings and approvals.
Glass bulbs are very fragile. Handle with extreme care. Sprinklers should be kept in the carton provided with dividers at all times prior to installation. Sprinklers should never come in direct contact with one another or any other foreign object prior to installation. Do not place sprinklers in a bucket. Globe Fire Sprinkler Corporation is not responsible for glass bulb damage due to improper handling.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color |
N.F.P.A. Maximum |
||
|---|---|---|---|---|---|
| ORDINARY | 135°F/155°F | 57°C/68°C | ORANGE/RED | 100°F | 38°C |
| INTERMEDIATE | 175°F/200°F | 79°C/93°C | GREEN/YELLOW | 150°F | 66°C |
| HIGH | 286°F | 141°C | BLUE | 225°F | 107°C |
Important Precautions to Follow
- Globe Sprinklers are to be installed in accordance with the latest published standards of the National Fire Protection Association, Loss Prevention Council, Globe Sprinkler data sheets, Government agencies and/or other similar organizations and to meet local codes and ordinances.
- Never replace a Large Orifice Sprinkler with a standard sprinkler or vice versa.
- Never install an Upright Spray Sprinkler in a pendent position or a Pendent Spray Sprinkler in an upright position.
- Install using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
- Minimum operating pressure for dry upright is 12 psi.
- Install Globe GL Series Dry Type Sprinklers in 1"NPT or ¾"NPT tees only - ANSI B16.3 Class 155 or ANSI B16.4 Class 125. Tyco Blazemaster® CPVC Fittings have been evaluated and found acceptable for use. Other plastic fittings may be acceptable but we have not received samples for evaluation.
- Never install a sprinkler after it has dropped to the floor or been injured in any way. These sprinklers should be returned to the factory for examination.
- Never install sprinklers in the fittings until the piping is in place on the ceiling as sprinklers are liable to be injured if screwed into the fittings when the lines are made up at the bench.
- Never paint or whitewash sprinklers as this is liable to prevent their operation in a fire.
- Never attach wiring, ropes or fixtures to sprinkler or sprinkler piping.
- Lead Plated sprinklers should be used in all locations subject to corrosion from acid fumes, chemicals, processes, etc. Extreme care must be exercised when installing to avoid damage to coating.
- Use sprinkler guards on all sprinklers subject to injury by moving objects.
- Some Globe Fire Sprinkler Corporation sprinkler models are shipped with a factory applied sealant on the threads. Globe recommends that no additional tape or pipe dope be used on these sprinklers. If pipe compound is used on sprinklers without factory applied sealant, apply to sprinkler threads only. Wipe all excess compound off sprinkler.
- Store sprinklers in cool, dry place and preferably in their shipping carton.
- Sprinklers of proper rating must be carefully selected to meet the temperature conditions where they are located (see table on reverse side for available temperatures). 175°F (79°C) or lower sprinklers should not be installed in locations less than 30" above or 12" to one side of steam pipes, heating coils or radiators. 200°F (93°C) sprinkler should be used under skylights where exposed to direct sun rays. Consult the local authority having jurisdiction to determine the proper temperature ratings in special locations such as:
- Areas near unit heaters.
- Areas where low pressure blow-off discharges into a large room.
- Areas in an unventilated concealed
space under uninsulated wood or tin roofs. - Areas in an unventilated attic.
- Areas in a shed with an unventilated peak roof or thin boards or metal.
- Areas where show windows have high powered electric illumination processes.
- Areas where a locomotive enters a building.
- Areas in other locations where special consideration is necessary.
- Inspect sprinklers regularly for mechanical damage, corrosion, paint and dust buildup as outlined in NFPA publications.
- Dry type sprinklers should be replaced after 10 years of service or as conditions warrant.
- High temperature sprinklers (360°F and higher) should be replaced after 5 years of service or as conditions warrant.
- When replacing sprinklers in any system, make sure those replacements are of the same style, size, and temperature rating as those removed.
- Should a change in building structure, occupancy or temperature conditions indicate a probable change in sprinkler requirements, notify the insurance carrier or other qualified inspection agency immediately. Do not make any changes without the authorization of one of these agencies.
- Maintain an extra stock of sprinklers and wrenches in a cabinet as required by NFPA 13.
- Concealed sprinklers and recessed sprinklers should not be used if the space above the ceiling is used for delivery (positive pressure) in an HVAC system.
- Globe Fire Sprinkler Corporation sprinklers have been tested, listed or approved by the agencies noted on the individual sprinkler data sheet. Acceptance by other agencies or authorities is not the responsibility of Globe Fire Sprinkler Corporation. Globe Fire Sprinkler Corporation is not liable for any costs arising as a result of any changes to listings or approvals after shipment. The Seller makes no warranties express or implied including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose except as expressly stated in seller's sales contract or sales acknowledgment form.
Cross Sections
| Ambient Temperature of Protected Area at the Discharge End of the Sprinkler |
Exposed Barrel Ambient Temperature |
||
| 40°F/4°C | 50°F/10°C | 60°F/16°C | |
| Exposed Minimum Barrel Length (Face of Tee to Top of Ceiling or Inside Wall) |
|||
| 40°F (4°C) | 0 | 0 | 0 |
| 30°F (-1°C) | 0 | 0 | 0 |
| 20°F (-7°C) | 4 (101) | 0 | 0 |
| 10°F (-12°C) | 8 (203) | 1 (25.1) | 0 |
| -0°F (-18°C) | 12 (305) | 3 (75) | 0 |
| -10°F (-23°C) | 14 (356) | 4 (101) | 1 (25.1) |
| -20°F (-29°C) | 14 (356) | 6 (152) | 3 (75) |
| -30°F (-34°C) | 16 (406) | 8 (203) | 4 (101) |
| -40°F (-40°C) | 18 (457) | 8 (203) | 4 (101) |
| -50°F (-46°C) | 20 (508) | 10 (254) | 6 (152) |
| -60°F (-51°C) | 20 (508) | 10 (254) | 6 (152) |
Sprinklers » Caution Sheets
GL Series Bulb Spray Caution Sheet
Automatic Sprinklers GL Series Bulb Spray Caution Sheet
Installation Instructions - Read Carefully

Position
Standard Orifice Upright Spray Sprinkler. Install in upright position only. Identified by "SSU" on deflector.
Standard Orifice Pendent Spray Sprinkler. Install in pendent position only. Identified by "SSP" on deflector.
Standard Orifice Conventional Spray Sprinkler. Install in upright or pendent position. Identified by "CU/P" on deflector.
Standard Orifice Horizontal Sidewall Spray Sprinkler. Install in horizontal position only. Identified by "TOP" on deflector.
Standard Orifice Vertical Sidewall Spray Sprinkler. Install in upright or pendent position. Identified by "SIDEWALL" on deflector.
Warning
Sprinklers contained in this carton have been manufactured and tested in accordance with the applicable standards or where applicable under the inspection of Underwriters Laboratories Inc., FM Approvals, and The Loss Prevention Certification Board.
Any alteration to the sprinkler after it leaves the factory including, but not limited to painting, plating, coating or other alteration, may render the sprinkler inoperative and will nullify the Listing of Underwriters Laboratories Inc., the Approval of FM Approvals, and the Approval of The Loss Prevention Certification Board.
Glass bulbs are very fragile. Handle with extreme care. Sprinklers should be kept in the carton provided with dividers at all times prior to installation. Sprinklers should never come in direct contact with one another or any other foreign object prior to installation. Do not place sprinklers in a bucket. Globe Fire Sprinkler Corporation is not responsible for glass bulb damage due to improper handling.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color |
N.F.P.A. Maximum |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Green/Yellow | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
| Extra High | 360°F | 182°C | Mauve | 300°F | 149°C |
Important Precautions to Follow
- Globe Sprinklers are to be installed in accordance with the latest published standards of the National Fire Protection Association, Factory Mutual, Loss Prevention Council, Globe Sprinkler data sheets, Government agencies and/or other similar organizations and to meet local codes and ordinances.
- Never replace a Large Orifice Sprinkler with a standard sprinkler or vice versa.
- Never replace a Spray Sprinkler with an old style sprinkler or a used sprinkler.
- Never install an Upright Spray Sprinkler in a pendent position or a Pendent Spray Sprinkler in an upright position.
- Use only a special sprinkler wrench to install sprinklers. Any other wrench is liable to injure the sprinkler.
- Never install a sprinkler after it has dropped to the floor or been injured in any way. These sprinklers should be returned to the
factory for examination. - Never install sprinklers in the fittings until the piping is in place on the ceiling as sprinklers are liable to be injured if screwed into
the fittings when the lines are made up at the bench. - Never paint or whitewash sprinklers as this is liable to prevent their operation in a fire.
- Never install sprinklers in pendent position on a dry system unless of a type designed for this purpose and as permitted by NFPA
13 and the authority having jurisdiction. - Never attach wiring, ropes or fixtures to sprinkler or sprinkler piping.
- Wax Coated, Lead Plated or Wax over Lead sprinklers should be used in all locations subject to corrosion from acid fumes,
chemicals, processes, etc. Extreme care must be exercised when installing to avoid damage to coating. - Use sprinkler guards on all sprinklers subject to injury by moving objects.
- Some Globe Fire Sprinkler Corporation sprinkler models are shipped with a factory applied sealant on the threads. Globe
recommends that no additional tape or pipe dope be used on these sprinklers. If pipe compound is used on sprinklers without
factory applied sealant, apply to sprinkler threads only. Wipe all excess compound off sprinkler. - Store sprinklers in cool, dry place and preferably in their shipping carton.
- Sprinklers of proper rating must be carefully selected to meet the temperature conditions where they are located (see table above for available temperatures). 175°F (79°C) or lower sprinklers should not be installed in locations less than 30" above or 12" to one side of steam pipes, heating coils or radiators. 200°F (93°C) sprinkler should be used under skylights where exposed to direct sun rays. Consult the local authority having jurisdiction to determine the proper temperature ratings in special locations such as:
- Areas near unit heaters.
- Areas where low pressure blow-off discharges into a large room.
- Areas in an unventilated concealed space under uninsulated wood or tin roofs.
- Areas in an unventilated attic.
- Areas in a shed with an unventilated peak roof or thin boards or metal.
- Areas where show windows have high powered electric illumination processes.
- Areas where a locomotive enters a building.
- Areas in other locations where special consideration is necessary.
- Inspect sprinklers regularly for mechanical damage, corrosion, paint and dust buildup as outlined in NFPA publications.
- Standard sprinklers should be replace after 50 years of service or as conditions warrant.
- Quick response sprinklers should be replaced after 20 years of service or as conditions warrant.
- High temperature sprinklers (360°F and higher) should be replaced after 5 years of service or as conditions warrant.
- When replacing sprinklers in any system, make sure those replacements are of the same style, size, and temperature rating as those removed.
- Should a change in building structure, occupancy or temperature conditions indicate a probable change in sprinkler requirements, notify the insurance carrier or other qualified inspection agency immediately. Do not make any changes without the authorization of one of these agencies.
- Maintain an extra stock of sprinklers and wrenches in a cabinet as required by NFPA 13.
- Concealed sprinklers and recessed sprinklers should not be used if the space above the ceiling is used for delivery (positive pressure) in an HVAC system.
- Globe Fire Sprinkler Corporation sprinklers have been tested, listed or approved by the agencies noted on the individual sprinkler data sheet. Acceptance by other agencies or authorities is not the responsibility of Globe Fire Sprinkler Corporation. Globe Fire Sprinkler Corporation is not liable for any costs arising as a result of any changes to listings or approvals after shipment. The seller makes no warranties express or implied including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose except as expressly stated in seller's sales contract or sales acknowledgment form.
Download this page as a pdf
Valves & Accessories » Misc. Valves & Valve Accessories
B-20 Sight Drains
Sight Drains for Automatic Sprinkler Systems
| P/N | Description | Image | Cross Section |
|---|---|---|---|
| 323310 | 1" NPT Sight Drains / 175 PSI Maximum WWP | ![]() |
![]() |
| 323320 | 2" NPT Sight Drains / 175 PSI Maximum WWP | ![]() |
![]() |
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-5 Sprinkler Cabinets
Sprinkler Cabinets for Replacement Automatic Sprinklers
| P/N | Description | Image |
|---|---|---|
| 312390 | Six Sprinkler Cabinets for ½" OR ¾" | ![]() |
| 312392 | Twelve Sprinkler Cabinets for ½" OR ¾" | ![]() |
When storing concealed sprinklers, Twelve Sprinkler Cabinet holds six units and Six Sprinkler Cabinet holds three units.
Download this page as a pdfSprinklers » Residential » Residential Sprinklers
A-2 5.6K Pendent Sprinkler - GL5610
Automatic Sprinklers Model GL5610 Pendent Recessed Pendent
Description and Operation
The Globe Model GL5610 Residential Sprinkler has a low profile yet durable design, which utilizes a 3mm frangible glass ampule as the thermosensitive element. It features economy, aesthetics and low flow.
The combination of the 3mm frangible glass ampule and specially designed deflector makes the Model GL5610 Residential Sprinkler the ultimate in life safety and fire control. This Globe Pendent and Recessed Pendent Residential Sprinkler has met the strict requirements of Underwriters Laboratories Inc. as described in the UL Standard for Residential Sprinklers for Fire Protection Service, UL 1626, and should be used accordingly. This sprinkler should also be installed in accordance with the appropriate NFPA Standard 13, 13D or 13R and under the direction of the approving authorities having jurisdiction.
The heart of Globe's Model GL5610 sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature, the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Rating - 155°F (68°C).
- Water Working Pressure Rating - 175 psi (12 Bars).
- Factory tested hydrostatically to 500 psi (34 Bars).
- Maximum low temperature glass bulb rating is
-67°F (-55°C). - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size.
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
Specifications and Approvals
|
Sin | 'K' Factor | Thread Size | Length | Finishes | 155°F 68°C | cULus | |
|---|---|---|---|---|---|---|---|
| GL5610 | 1/2" NPT | 2 1/2" (6.4 cm) |
Factory Bronze |
• | • | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2C-U.L. listed corrosion resistant polyester must be specified on order.
Cross Sections
Installation Data for Flat and Sloped Ceilings**
Pendent and Recessed Pendent
| Maximum Area of Coverage | Minimum Water Discharge & Pressures Needed* | |
|---|---|---|
| 12' x 12' | 15 G.P.M. - 7.2 P.S.I. |
— |
| 14' x 14' | 19 G.P.M. - 11.5 P.S.I. | — |
| 16' x 16' | 19 G.P.M. - 11.5 P.S.I. | — |
| 18' x 18' | 21 G.P.M. - 14.1 P.S.I. | — |
| 20' x 20' | 24 G.P.M. - 18.4 P.S.I. | — |
*When these sprinklers are used in NFPA 13 systems, a 0.1 design density minimum shall be utilized.
**Refer to page 2 of the Globe Residential Sprinkler Installation Guide for NFPA 13D and 13R requirements.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390
- Quantity - Recessed Wrenches - P/N 325391
- Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Sprinkler Accessories
Sprinkler Wrenches
Wrenches For Globe Automatic Sprinklers
| P/N | Description | Image |
|---|---|---|
| 325390 | ½" NPT STANDARD WRENCH | ![]() |
| 312366 | ¾" NPT STANDARD WRENCH | ![]() |
| 333010 | ¾" NPT EXTRA LARGE ORIFICE WRENCH | ![]() |
| 337014 | DRY SPRINKLER RECESSED WRENCH | ![]() |
| 325401 | ¾ "NPT RECESSED WRENCH | ![]() |
| 325391 | ½" NPT RECESSED / CONCEALED WRENCH | ![]() |
| 327102 | RESIDENTIAL SIDEWALL RECESSED WRENCH | ![]() |
| 332765 | ½” NPT 1” ADJUSTABLE CONCEALED WRENCH | ![]() |
| 332334 | ½" NPT MILLENNIUM WRENCH | ![]() |
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-2 Recessed Escutcheons
Globe Recessed Escutcheons
Recessed Escutcheons 1/2” NPT or 3/4” NPT
2 Pc. Recessed
(3/4” Adj. x 2 7/8” Diameter)
- Chrome: 325422
- Brass: 325424
- *Poly: 325426
- Chrome: 325423
- Brass: 325420
- *Poly: 325427
2 Pc. Recessed
(1/2” Adj. x 2 7/8” Diameter)
Finish/Part No. 1/2”NPT:
- Chrome: 332071
- Brass: 332072
- *Poly: 332073
2 Pc. Screw Adjustable Recessed
(3/4” Adj. x 2 7/8” Diameter)
- Chrome: 329306
- *Poly: 329308
- Chrome: 325423
- Brass: 325420
- *Poly: 325427
2 Pc. Screw Adjustable Recessed
(1/2” Adj. x 2 7/8” Diameter)
- Chrome: 329301
- *Poly: 329303
- Chrome: 329311
- *Poly: 329313
1/2” Adjustable Recessed Model Numbers
- cULus Approved: 2810, 4110, 4210, 4230, 4231, 4234, 4710, 5628, 5630, 5631, 8101, 8107, 8128, 8129, 8151 & 8174
- cULus & FM Approved: 5601, 8106 & 8156
3/4” Adjustable Recessed Model Numbers
- cULus Approved: 2801, 2826, 2851, 2870, 4201, 4226, 4231, 4251, 4270, 5601, 5602, 5626, 5628, 5635, 5636, 5641, 5642, 5652, 5670, 5679, 5680, 5685, 5686, 8101, 8102, 8151, 8152 , 8106, 8107, 8109, 8127, 8128, 8129, 8135, 8141, 8157, 8159, 8171, 8174, 8179, 8185
- cULus & FM Approved: 5651 & 8156
*When ordering specify color after part number: -W= white, -B= black.
Download this page as a pdf
Valves & Accessories » System Sensor
Alarm Pressure Switches - EPS10-1 & EPS10-2
EPS10-1 and EPS10-2 Alarm Pressure Switches
Product Overview
- Sensitivity adjustment wheel, no tools required
- Reinforced diaphram resists pressure spikes
- Two conduit entrances provided
- NEMA 4 rated
System Sensor EPS10 Series switches are designed for use in wet, dry, deluge, and preaction automatic sprinkler systems to indicate a discharge from a sprinkler. The EPS10-1 has a single SPDT switch while the EPS10-2 model contains two SPDT switches..
The EPS10 Series features field adjustable pressure sensitivity to provide an alarm response between 4 and 20 psi. It is factory set to respond at 4 – 8 psi on rising pressure. The pressure adjustment wheel requires no special tools and does not affect switch synchronization on the EPS10-2.
Specifications
|
Standard Specifications
|
|
|---|---|
| Maximum Operating Pressure |
250 psi
|
| Differential |
Approximately 3 psi throughout range
|
| Maximum Adjustment Pressure Range |
4 to 20 psi
|
| Factory Setting |
Operates at rising pressure 4 to 8 psi
|
| Pressure Connection |
1/2" NPT male glass reinforced nylon
|
| Switch Contact Ratings |
EPS10-1: One set SPDT (Form C)
EPS10-2: Two sets SPDT (Form C) 10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC |
| Dimensions |
5.12" H x 3.325" W x 4.250" L
(13.0 cm x 8.4 cm x 10.8 cm) |
| Operating Temperature Range: |
Indoor or outdoor use
–40°F to 160 °F ( –40°C to 71°C) |
| Cover Tamper Switch |
UL Models: Optional P/N 546-8000
ULC Models: Factory Installed |
| Enclosure |
Rated UL 4x, NEMA 4 for indoor or outdoor use
|
| Shipping Weight |
1.2 lbs. (.54 Kg)
|
| Service Use |
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA 72 |
| Warranty |
3 years
|
Engineering Specifications
Model shall be an EPS10-1 or EPS10-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type.
Switches shall have a maximum service pressure rating of 250 psi and shall be factory adjusted to operate at a pressure of 4 – 8 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC.
The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a 1⁄2" NPT male pressure connection to be connected to the alarm check valve of a “wet” sprinkler system, into the intermediate chamber of a “dry” system, or to a pre-action or deluge valve. They shall be activated by any flow of water equal to or in excess of the discharge from one sprinkler head. Switches shall provide 1 knockout type and 1 open hole for 1⁄2" conduit fitting attachment and a ground screw provision for electrical grounding.
The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover shall incorporate tamper-resistant screws.
The unit shall be listed by Underwriters Laboratories, Inc. and approved by Factory Mutual.
Cross Section



Ordering Information
| Model Number | Description |
|---|---|
| EPS10-1 |
Alarm Water flow Pressure Switch, One SPDT, 4 –20 PSI
|
| EPS10-2 |
Alarm Water flow Pressure Switch, Two SPDT, 4 –20 PSI
|
| EPSA10-1 |
ULC/Canadian Version
|
| EPSA10-2 |
ULC/Canadian Version
|
| Replacement Parts | Description |
|---|---|
| S07-66-02 |
Replacement Tamper Screws for Cover of EPS
|
| WFDW |
Replacement Tamper Proof Wrench for Cover of EPS
|
| 546-8000 |
Cover Tamper Switch for EPS Series
|
Download this page as a pdf
Valves & Accessories » System Sensor
Supervisory Special Purpose Switch - PSP1
PSPI Plug-in Special Purpose Supervisory Switch
Product Overview
- Monitors non-rising stem gate and ball and angle valves
- NEMA 3 rated enclosures
- 360° mounting design provides greater installation flexibility
- Adjustable length supervisory cord
- Lockout feature ensures alarm signal integrity
- Cover tamper switch factory installed
- Tamper-resistant cover screws
System Sensor’s PSP1 plug-in switch is a special application supervisory switch designed for applications where no other type of listed valve supervisory switch can be used..
Application Flexibility. The PSP1 is to be used on non-rising stem gate valves and ball and angle valves. The unit is approved for Class A and Class B circuits.
Robust Construction. The PSP1 consists of a rugged rain tight metal housing. With its NEMA 3 rated housing and water-resistant cord, the PSP1 may be used in either indoor or outdoor applications.
Simplified Operation. The PSP1 features a 360° versatile mounting design and an adjustable length cord which allow more freedom to install the unit at the most desirable alignment angle.
Reliable Performance. The PSP1 employs a supervisory cord which, when pulled out, closes a set of normally open contacts. A lockout feature prevents reinsertion of the cord until the cover is removed, and the unit is reset. Removal of the cover or cutting of the cord results in an open circuit.
Specifications
|
Standard Specifications
|
|
|---|---|
| Operating Voltage |
6/12/24V AC/DC
|
| Maximum Operating Current |
250 mA
|
| Dimensions |
43/4"L x 3"W x 21/2"D
(12cm x 7.5cm x 5.6cm) |
| Dimensions with bracket |
81/2"L (21.5cm)
|
| Operating Temperature Range |
-4°F to 149 °F (-20 °C to 65°C)
|
| Enclosure Rating |
NEMA 3 UL Indoor/Outdoor Rated
|
| Cover Tamper Switch |
Standard
|
| Cable |
2 wire, 16 gauge waterproof, 8 feet long (2.4m)
|
| Shipping Weight |
1.7 lbs. (0.8 kg)
|
| Warranty |
3 years
|
Engineering Specifications
Model shall be a model number PSP1 special purpose supervisory switch as manufactured by System Sensor. The unit is not intended or designed for ordinary usage. It is a special application device to be used for unusual conditions where no other approved or listed method of protection is available or practical, such as non-rising stem gate valves. When installed on a non-rising stem gate valve, turning the valve wheel will pull the plug out of the jack and close a set of normally open contacts. A lockout will prevent reinsertion and will require removal of the cover. Tamper-proof screws are provided for the cover. Removal of the cover, cutting of the cord, or ground faults will cause an open circuit. The device should be wired to the trouble circuit of a fire alarm control panel. The PSP1 shall be capable of operating on Class A or Class B circuits. The PSP1 shall be NEMA 3 rated for indoor/outdoor use and shall have an operating temperature range of - 4°F to 149°F (- 20°C to 65°C). The PSP1 shall be listed by Underwriters Laboratories and Underwriters Laboratories of Canada, Inc. and shall be Factory Mutual approved.
Cross Sections

Ordering Information
| Model Number | Description |
|---|---|
| PSP1 |
Plug-In Special Purpose Supervisory Switch
|
| PSP1A |
Plug-In Special Purpose Supervisory Switch (ULC model)
|
Valves & Accessories » System Sensor
Supervisory Pressure Switches - EPS40-1 & EPS40-2
EPS40-1 and EPS40-2 Supervisory Pressure Switches
Product Overview
- Sensitivity adjustment wheel, no special tools required
- Reinforced diaphram resists pressure spikes
- Two conduit entrances provided
- NEMA 4 rated
System Sensor EPS40 Series switches are designed for use in dry pipe systems or pressure tanks and water pressure supplies of automatic water control valves. The EPS40-1 has a single SPDT switch while the EPS40-2 model contains two SPDT switches.
The EPS40 Series features field adjustable pressure sensitivity to provide an alarm response between 10 and 100 psi. All models are factory set for use in a nominal 40 psi system. The EPS40-1 is factory set to respond at 30 psi at decreasing pressure while the EPS40-2 is factory set to respond at 50 psi on rising pressure and 30 psi at decreasing pressure. The pressure adjustment wheel requires no special tools and does not affect switch synchronization on the EPS40-2..
Specifications
|
Standard Specifications
|
|
|---|---|
| Maximum Operating Pressure |
250 psi
|
| Differential |
Approximately 3 psi @ 10 psi, 6 psi @ 100 psi
|
| Maximum Adjustment Pressure Range |
10 to 100 psi
|
| Factory Setting |
EPS40-1 operates at decreasing pressure at 30 psi
EPS40-2 operates at increasing pressure at 50 psi and decreasing pressure at 30 psi |
| Pressure Connection |
1/2" NPT male
|
| Switch Contact Ratings |
EPS40-1: One set SPDT (Form C)
EPS40-2: Two sets SPDT (Form C) 10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC |
| Dimensions |
5.12" H x 3.325" W x 4.250" L
(13.0 cm x 8.4 cm x 10.8 cm) |
| Operating Temperature Range: |
Indoor or outdoor use
–40°F to 160 °F ( –40°C to 71°C) |
| Cover Tamper Switch |
UL Models: Optional P/N 546-8000
ULC Models: Factory Installed |
| Enclosure |
Rated UL 4x, NEMA 4 for indoor or outdoor use
|
| Shipping Weight |
1.2 lbs. (.54 Kg)
|
| Service Use |
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA 72 |
| Warranty |
3 years
|
Engineering Specifications
Model shall be an EPS40-1 or EPS40-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type.
Switches shall have a maximum service pressure rating of 250 psi and shall be adjustable from 10 - 100 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC.
The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a 1⁄2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off valve. Switches shall provide 1 knockout type and 1 open hole for 1⁄2" conduit fitting attachment and a ground screw provision for electrical grounding.
The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover shall incorporate tamper-resistant screws.
The unit shall be listed by Underwriters Laboratories, Inc., the California State Fire Marshal, MEA, and approved by Factory Mutual.
Cross Section



Ordering Information
| Model Number | Description |
|---|---|
| EPS40-1 |
Low Pressure Supervisory Switch, One SPDT, 10-100 PSI
|
| EPS40-2 |
High/Low Pressure Supervisory Switch, Two SPDT, 10-100 PSI
|
| EPSA40-1 |
ULC/Canadian Version
|
| EPSA40-2 |
ULC/Canadian Version
|
| Replacement Parts | Description |
|---|---|
| S07-66-XX |
Replacement Tamper Screws for Cover of EPS
|
| WFDW |
Replacement Tamper Proof Wrench for Cover of EPS
|
| 546-8000 |
Cover Tamper Switch for EPS Series
|
Download this page as a pdf
Valves & Accessories » System Sensor
Supervisory Switch - PIBV2
PIBV2 Supervisory Switch
Product Overview
- NEMA 3R rated enclosure
- Bi-directional actuator accommodates rising or falling flags
- Single side conduit entry does not require right angle fittings
- Adjustable length actuator eliminates the need for cutting the shaft
- Accommodates up to 12 AWG wire
- Two SPDT contacts are enclosed in a durable terminal block for added strength
- 100% synchronization activates both alarm panel and local bell simultaneously
System Sensor’s PIBV2 supervisory switch monitors the open position of post indicator and butterfly control valves.
Robust Construction. The PIBV2 consists of a rugged housing, intended for indoor and outdoor use. When installed with the actuator in the vertical position, the PIBV2 is NEMA 3R rated per UL.
Application Flexibility. The PIBV2 features a flexible design that accommodates post indicator, butterfly, and many other types of wall post, recessed wall post and pressure reducing valves. The PIBV2’s unique bi-directional actuator allows the unit to be installed in either rising or falling flag installations.
Simplified Operation. Installation is made easier with the PIBV2’s single side conduit entrance. By providing a direct conduit pathway to the electrical source, right angle fittings are not required. Installation is further simplified by the PIBV2’s adjustable length actuator, which eliminates the need for cutting the shaft.
Reliable Performance. The PIBV2 is equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to assure reliable performance.
Specifications
|
Standard Specifications
|
|
|---|---|
| Contact Ratings |
Two sets of SPDT (Form C)
10.0 A @ 125/250V AC 2.5 @ 6/12/24V DC |
| Overall Switch Dimensions |
41/4″H x 31/2″W x 31/4″D
(10.8cm x 8.9cm x 8.2cm) |
| Maximum Stem Extension |
21/8″ (5.4 cm)
|
| Mounting |
1/2″ NPT nipple
|
| Conduit Entrances |
One single side open for 1/2″ conduit
|
| Operating Temperature Range |
32°F to 120°F (0°C to 49°C)
Note: The PIBV2 will operate from –40°F to 120°F (–40°C to 49°C); however UL does not test control valve supervisory switches below 32°F (0°C). |
| Enclosure Rating |
UL indoor/outdoor
NEMA 3R when mounted with the actuator vertical |
| Cover Tamper Switch |
Standard with ULC model
Optional for UL model, part no. 546-7000 |
| Shipping Weight |
2 lbs. (0.9 kg)
|
| Service Use |
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 stories: NFPA 13R National Fire Alarm code: NFPA 72 |
| Warranty |
3 years
|
| U.S. Patent No. |
5,213,205
|
Engineering Specifications
Model shall be model number PIBV2 Post Indicator Butterfly Valve supervisory switch as manufactured by System Sensor. PIBV2 shall be installed on each valve as designated on the drawings and/or as specified herein. Switches shall be mounted so as not to interfere with the normal operation of the valve and shall be adjusted to operate within two revolutions of the valve control or when the valve flag has moved no more than one-fifth of the distance from its normal position. The mechanism shall be contained in a weatherproof die cast metal housing, which shall provide a side entrance for 1/2″ conduit and incorporate a 1/2″ NPT nipple for attachment to the valve body. A grounding provision is provided. The switch assembly shall include two switches each with a rated capacity of 10 Amp @ 125/250V AC and 2.5 Amp @ 24V DC. The cover shall contain tamper-resistant screws for which a security wrench will be provided with each switch. PIBV2 shall be Underwriters Laboratories listed for indoor or outdoor use. The PIBV2 shall be Factory Mutual, CSFM, and MEA approved.
Cross Section

Ordering Information
| Model Number | Description |
|---|---|
| PIBV2 |
Post Indicator/Butterfly valve supervisory switch
|
| PIBV2A |
Post Indicator/Butterfly valve supervisory switch (ULC model)
|
| Part Number | Description |
| A3010-00 |
Replacement hardware kit (wrenches, screw pack)
|
| 546-7000 |
Cover tamper switch kit
|
| S07-66-XX |
Tamper screws for cover
|
| WFDW |
Replacement tamper proof wrench for cover
|
| HEXW |
Replacement hex wrench
|
|
Models Available
|
Replacement Parts
|
|||
|---|---|---|---|---|
| PIBV2 |
Post Indicator/Butterfly
Valve Supervisory Switch |
A3010-00 |
Replacement Hardware Kit
|
|
| PIBV2A |
Post Indicator/Butterfly
Valve Supervisory Switch (ULC/Canadian) |
546-7000 |
Cover Tamper Switch Kit
|
|
| S07-66-XX |
Cover Tamper Switch Kit
|
|||
| WFDW |
Cover Wrench
|
|||
| HEXW |
Replacement Hex Wrench
|
|||
Download this page as a pdf
Valves & Accessories » System Sensor
Supervisory Switch - OSY2
OSY2 Supervisory Switch
Product Overview
- NEMA 3R rated enclosure
- User-friendly mounting bracket fits newer valve yokes
- Single side conduit entry does not require right angle fittings
- Adjustable length actuator eliminates the need for cutting the shaft
- Accommodates up to 12 AWG wire
- Three position switch monitors vandal and valve close signals
- Two SPDT contacts are enclosed in a durable terminal block for added strength
- 100% synchronization activates both alarm panel and local bell simultaneously
System Sensor’s OSY2 is used to monitor the open position of an Outside Screw and Yoke (OS&Y) type gate valve.
Robust Construction. The OSY2 consists of a rugged housing, intended for indoor and outdoor use. When installed with the actuator in the vertical position, the OSY2 is NEMA 3R rated per UL.
Application Flexibility. The OSY2 features a user-friendly mounting bracket and adjustable shaft to permit mounting to most OS&Y valves, ranging is size from 1″ to 12″. Its right angle design and wide bracket span provides maximum clearance for valve components, to accommodate troublesome valves. Removing the OSY2’s gate valve bracket allows the unit to monitor sidebracket style pressure reducing valves.
Simplified Operation. Installation is made easier with the OSY2’s single side conduit entrance. By providing a direct conduit pathway to the electrical source, right angle fittings are not required. Installation is further simplified by the OSY2’s adjustable length actuator, which eliminates the need for cutting the shaft.
Reliable Performance. The OSY2 is equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal black to assure reliable performance.
Specifications
|
Standard Specifications
|
|
|---|---|
| Contact Ratings |
Two sets of SPDT (Form C)
10.0 A @ 125/250V AC 2.5 @ 6/12/24V DC |
| Overall Switch Dimensions |
5¾″H x 3½″W x 3¼″D
(14.6cm x 8.9cm x 8.2cm) |
| Bracket Span |
2¼″H x 6¾″W x 1″D
(5.7cm x 17.1cm x 2.5cm) |
| Maximum Stem Extension |
25/8″ (6.7 cm)
|
| Shipping Weight |
2.8 lbs. (1.3 kg)
|
| Conduit Entrances |
One single side open for ½″ conduit
|
| Operating Temperature Range |
32°F to 120°F (0°C to 49°C)
Note: The OSY2 will operate from –40°F to 120°F (–40°C to 49°C); however UL does not test control valve supervisory switches below 32°F (0°C). |
| Enclosure Rating |
UL indoor/outdoor
NEMA 3R when mounted with the actuator vertical |
| Cover Tamper Switch |
Standard with ULC model
Optional for UL model, part no. 546-7000 |
| Service Use |
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 stories: NFPA 13R National Fire Alarm code: NFPA 72 |
| Warranty |
3 years
|
| U.S. Patent Numbers |
5,478,038; 5,213,205
|
Engineering Specifications
Model shall be model number OSY2 supervisory switch as manufactured by System Sensor. OSY2 shall be installed on each valve as designated on the drawings and/or as specified herein. Switches shall be mounted so as not to interfere with the normal operation of the valve and shall be adjusted to operate within two revolutions of the valve control or when the stem has moved no more than one-fifth of the distance from its normal position. The mechanism shall be contained in a weatherproof die cast metal housing, which shall provide a side entrance for 1/2″ conduit and incorporate the necessary facilities for attachment to the valve. A grounding provision is provided. The switch assembly shall include two switches each with a rated capacity of 10 Amp @ 125/250VAC and 2.5 Amp @ 24VDC. The cover shall contain tamper-resistant screws for which a security wrench will be provided with each switch. The OSY2 shall be Underwriters Laboratories listed for indoor or outdoor use. The OSY2 shall be Factory Mutual, CSFM, and MEA approved.
Cross Sections

Ordering Information
| Model Number | Description |
|---|---|
| OSY2 |
Outside Screw and Yoke valve supervisory switch
|
| OSY2A |
Outside Screw and Yoke valve supervisory switch (ULC model
|
| Part Number | Description |
| OSYRK |
Replacement hardware kit (wrenches, screw pack and J-hooks)
|
| 546-7000 |
Cover tamper switch kit
|
| S07-66-XX |
Tamper screws for cover
|
| WFDW |
Replacement tamper proof wrench for cover
|
| HEXW |
Replacement hex wrench
|
|
Models Available
|
Replacement Parts
|
|||
|---|---|---|---|---|
| OSY2 | OS&Y Supervisory Switch | OSYRK | Replacement Hardware Kit | |
| OSY2A | OS&Y Supervisory Switch (ULC/Canadian) |
546-7000 | Cover Tamper Switch Kit | |
| S07-66-XX | Tamper Screws for Cover | |||
| WFDW | Cover Wrench | |||
| HEXW | Replacement Hex Wrench | |||
Download this page as a pdf
Valves & Accessories » System Sensor
Alarm Bells - SSM/SSV
SSM/SSV Series Alarm Bells
Product Overview
Approved for indoor and outdoor use
Low current draw
High dB output
Three sizes available 6", 8", 10"
AC and DC models
DC models are polarized for use with supervision circuitry
Mount directly to standard 4" square electrical box
System Sensor’s SSM and SSV series bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications.
Reliable Performance. The SSM and SSV series provide loud resonant tones. The SSM series operate on 24VDC and are motor driven, while the SSV series operate on 120VAC utilizing a vibrating mechanism.
Simplified Installation. For indoor use, the SSM and SSV series mount to a standard 4 inch square electrical box. For outdoor applications, weatherproof back box, model number WBB, is used.
The SSM and SSV series come pre-wired, to reduce installation time. The SSM series incorporate a polarized electrical design for use with supervision circuitry.
Specifications
|
Standard Specifications
|
|
|---|---|
|
Operating Temperature Range
|
-31°F to 140 °F
|
|
Operating Voltage
|
SSM series 24VDC
SSV series 120VAC |
|
Termination
|
Provided with 2 sets of leads for
in/out writing |
|
Service Use
|
Fire Alarm, General Signaling, Burglar Alarm
|
|
Warranty
|
3 years
|
| Model | Gong Diameter (inches) | Nominal Voltage | Operating Voltage Range | Average Current Draw | Sound Output (dB) |
|---|---|---|---|---|---|
| SSM24-6 | 6 | 24VDC | 19.2 to 26.4VDC | 0.03A | 85 |
| SSM24-8 | 8 | 85 | |||
| SSM24-10 | 10 | 85 | |||
| SSV120-6 | 6 | 120VAC | 96 to 132VAC | 0.047A | 82 |
| SSV120-8 | 8 | 85 | |||
| SSV120-10 | 10 | 82 |
* Sound output measured at Underwriter Laboratories, as specified in UL464
Engineering Specifications
Model shall be a SSM or SSV Series alarm bell. Bells shall have underdome strikers and operating mechanisms. Gongs on said bells shall be no smaller than nominal 6"/8"/10" (specify size) with an operating voltage of 24VDC or 120VAC (specify by part number). Bells shall be suitable for surface or semi-flush mounting. Outdoor surface mounted installations shall be weatherproof (using optional WBB weatherproof electrical box). Otherwise bells shall mount to a standard 4" square electrical box having a maximum projection of 21/2". Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction. Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal, and approved by Factory Mutual and MEA.
Ordering Information
| UL/FM Model Numbers | ULC/Canadian Models | Description |
|---|---|---|
| SSM24-6 | SSM24-6A | Bell, 6", 24VDC, Polarized, 85dba |
| SSM24-8 | SSM24-8A | Bell, 8", 24VDC, Polarized, 85dba |
| SSM24-10 | SSM24-10A | Bell, 10", 24VDC, Polarized, 85dba |
| SSV120-6 | SSV120-6A | Bell, 6", 120VAC, 82dba |
| SSV120-8 | SSV120-8A | Bell, 8", 120VAC, 85dba |
| SSV120-10 | SSV120-10A | Bell, 10", 120VAC, 82dba |
| WBB | Weatherproof Back Box for SSM and SSV series, when installed outdoor |
| UL/FM Models | ULC/Canadian Models | Weatherproof Back Box |
|---|---|---|
| SSM24-6 |
SSM24-6A |
WBB |
| SSM24-8 |
SSM24-8A |
|
| SSM24-10 |
SSM24-10A |
|
| SSV120-6 |
SSV120-6A |
|
| SSV120-8 |
SSV120-8A |
|
| SSV120-10 | SSV120-10A |
Download this page as a pdf
Valves & Accessories » System Sensor
T-Tap Waterflow Detector
T-Tap Waterflow Detector
Product Overview
Sealed retard mechanism (Model WFDT) assures that the retard is not contaminated by dust and dirt when the cover is removed
Visual Switch Activation (Model WFDT) permits installer to accurately set the retard even under extremely noisy conditions
100% Synchronization activates both alarm panel and local bell simultaneously
Accommodates up to 12 AWG wire
System Sensor WFDT Retard and WFDTNR Non-Retard T-Tap Waterflow Detectors are designed for primary signaling in residential systems and branch line signaling in larger systems. Both models fit any tee that has a 1″ NPT branch, including: 1″, 11⁄4″ and 11⁄2″ NPT threaded ferrous and brass tees; 1″, 11⁄4″, 11⁄2″ and 2″ copper sweat tees; Central, Spears®, and Victaulic® brand 1″ CPVC tees; and 11⁄2″ polybutylene tees.
Design. The design of the WFDT and WFDTNR makes them easy to install and simple to maintain. Either can be mounted in the vertical or horizontal position. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism (Model WFDT only) and switch assemblies are fieldreplaceable.
Features. Nine different flexible plastic paddles fit 1″, 11⁄4″, 11⁄2″ and 2″ tees. Sizes are marked clearly on the paddle for ease of installation. Plastic paddles slip over the actuating lever and are securely fastened with one screw. The handy depth gauge insures the proper installation depth and clearance of the detector to the tee.
Construction. The WFDT and WFDTNR include a durable tamper resistant enclosure and rugged switch assembly. The long lasting covers completely enclose the electrical components to keep out dust and dirt. Improved self-guiding security screws and removal tools make detectors resistant to tampering and simplify field maintenance. Dual SPDT switches are enclosed in a durable terminal block for added strength.
Specifications
| General Specifications | |
|---|---|
| Static Pressure Rating |
250 PSI
|
| Triggering Threshold Bandwidth (Flow Rate) |
4 – 10 GPM
|
| Maximum Surge |
18 FPS
|
| Compatible Tee Fittings |
Threaded ferrous and brass tees, copper sweat tees, CPVC tees, and polybutylene tees
|
| Contact Ratings |
Two sets of SPDT (Form C)
10.0 A @ 125/250 VAC 2.5 A @ 24 VDC |
| Overall Dimensions, Installed |
WFDT: 4.5″ H x 3.75″ W x 6.7″ L
(11.4cm H x 9.5cm W x 17cm L) WFDTNR: 3.75″ H x 3.25″ W x 4.25″ L (9.5cm H x 8.2cm x W x 10.8cm L) |
| Conduit Entrances |
2 openings for 1⁄2″ conduit
|
| Operating Temperature Range |
32°F – 120°F (0°C – 49°C)
|
| Enclosure Rating |
UL Indoor/Outdoor Rated
|
| Shipping Weight |
WFDT: 2.6 lbs. (1.2 kg.)
WFDTNR: 1.5 lbs. (0.7 kg.) |
| Service Use |
Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA 72 |
| Warranty |
3 years
|
| U.S. Patent Numbers |
3,845,259; 4,782,333; 5,213,205
|
Engineering Specifications
Model shall be a WFDT or WFDTNR as manufactured by System Sensor. T-tap water flow detectors shall be installed on a tee that has a 1″ NPT branch including: 1″, 11⁄4″ , or 11⁄2″ threaded ferrous or brass tee; 1–2″ copper sweat tees; Central, Spears®, and Victaulic® brand 1″ CPVC tees; or 11⁄2″ polybutylene tee as designated on the drawings and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate size, either a ver tical or horizontal run at least 6″ from any fittings or valves which may change water direction, flow rate, or pipe diameter or no closer than 24″ from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 250 psi. The retard t-tap detector shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through the tee fitting and connected by a mechanical linkage to the delay mechanism. The non-retard t-tap detector shall respond with no time delay to waterflow in the specified direction and range. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances (one of which is a knockout type) for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. All detectors shall be listed by Underwriters Laboratories for indoor or outdoor use.
Cross Section
Electrical Connections for WFDT
Common and B connections will close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector.| Contact Ratings | |
|---|---|
| 125/250 VAC | 10 AMPS |
| 24 VDC | 2.5 AMPS |



Break wire as shown for supervision of connection. Do not allow stripped wire leads to extend beyond switch housing. Do Not loop wires.

Click image above for a detailed view of this product
Ordering Information
| Part Number | Description |
|---|---|
| WFDT |
Waterflow Detector, Fits 1″, 11⁄4″, 11⁄2″ ferrous and brass threaded tees;
1″, 11⁄4″, 11⁄2″, 2″ copper sweat tees; 1″ CPVC tees;and 11⁄2″ polybutylene tees |
| WFDTNR |
Waterflow Detector, non-retard, fits same tees as Model WFDT
|
| A77-01-02 |
Replacement Terminal Block for WFDT
|
| A77-01-08 |
Replacement Terminal Block for WFDTNR
|
| A3008-00 |
Replacement Retard Mechanism
|
| PRK9 |
Replacement Paddle Kit — 11 paddles for WFDT and WFDTNR (see WFDT for sizes)
|
| 546-7000 |
Cover Tamper Switch Kit for WFDT
|
| S07-66-02 |
Replacement Tamper Screws for Covers of WFDT, WFDTNR
|
| WFDW |
Replacement Tamper Proof Wrench for Cover of WFDT, WFDTNR
|
| WFDN4 |
NEMA-4 Gasket Kit
|
| C58-164-01 |
Replacement Metal Cover
|
|
Models Available
|
Replacement Parts
|
|||
|---|---|---|---|---|
| WFDT | Waterflow Detector | A77-01-02 | Terminal Block for WFDT | |
| WFDTA | Waterflow Detector (ULC/Canadian) |
A77-01-08 | Terminal Block for WFDTNR | |
| WFDTNR | Waterflow Detector (non-retard) |
A3008-00 | Retard Mechanism | |
| PRK9 | Paddle Kit | |||
| 546-7000 | Cover Tamper Switch Kit | |||
| S07-66-02 | Tamper Screws for Cover | |||
| WFDW | Cover Wrench | |||
| WFDN4 | NEMA-4 Gasket Kit | |||
| C58-164-01 | Metal Cover | |||
Download this page as a pdf
Valves & Accessories » System Sensor
WFD Series Waterflow Detector
WFD Series Waterflow Detector
Product Overview
New WFD30-2 models install in 2” hole sizes.
UL models are NEMA 4 rated
Sealed retard mechanism assures that the retard is not contaminated by dust and dirt when the cover is removed
Visual switch activation permits installer to accurately set retard under noisy conditions
Rugged, dual SPDT switches are enclosed in a durable terminal block
Accommodates up to 12 AWG wire
100% synchronization activates both alarm panel and local bell simultaneously
System Sensor’s WFD series is compatible with schedule 10 through 40 steel pipe, sizes 2” through 8”, and can be mounted in a vertical or horizontal position.
Robust Construction. The WFD series consists of a rugged, NEMA 4 rated enclosure. Designed for both indoor and outdoor use, the WFD series operates across a wide temperature range, from 32°F to 120°F.
Reliable Performance. UL listed models are equipped with tamper resistant cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) synchronized switches are enclosed in a durable terminal block to assure reliable performance.
False Alarm Immunity. The WFD series incorporates a mechanical retard feature, which minimizes the risk of false alarm due to pressure surges or air trapped in the sprinkler system. In addition, the mechanical retard’s unique sealed design is immune to dust and other contaminants.
Simplified Operation. The WFD series is designed to simplify installation. Two conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field-replaceable.
Specifications
Engineering Specifications
Vane-type waterflow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6” from any fittings which may change water direction, flow rate, or pipe diameter or no closer than 24” from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi for 2” - 8” pipes. The detector shall respond to waterflow in the specified direction after a preset time delay which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or outdoor use.
|
Standard Specifications
|
|
|---|---|
| Static Pressure Rating |
450 PSI
|
| Triggering Threshold Bandwidth (Flow Rate) |
4-10 GPM
|
| Maximum Surge |
18 Feet Per Second (FPS)
|
| Compatible Pipe: |
Steel water pipe, schedule 10 through 40
|
| Contact Ratings |
Two sets of SPDT (Form C)
10.0 A, 1/2 HP @ 125/250 VAC 2.5 A @ 6/12/24 VDC |
| Conduit Entrances |
Two openings for 1/2” conduit. One open, one knock-out type
|
| Operating Temperature Range |
32ºF to 120ºF (0ºC to 49ºC)
|
| Enclosure Rating* |
NEMA 4 - suitable for indoor/outdoor use
|
| Cover Tamper Switch |
Standard with ULC models
Optional for UL models, part no. 546-7000 |
| Shipping Weight |
WFD20: 4.2 lbs., WFD25: 4.3 lbs., WFD30: 4.5 lbs., WFD30-2: 4.5 lbs., WFD35: 4.7 lbs., WFD40: 5.2 lbs., WFD50: 6.3 lbs. WFD60: 6.8 lbs., WFD80: 7.5 lbs.
|
| Service Use |
Automatic Sprinkler: NFPA-13
One or Two Family Dwelling: NFPA 13D Residential Occupancies up to 4 Stories: NFPA 13R National Fire Alarm Code: NFPA-72 |
| Warranty |
3 Years
|
| U.S. Patent Numbers |
3,845,259 4,782,333 5,213,205
|
Cross Section
Overall Dimensions Installed:
Click image above for a detailed view of this product
Ordering Information
| Part Number | Description |
|---|---|
| A3008-00 | Retard mechanism |
| A77-01-02 | Terminal block |
| 546-7000 | Tamper proof switch kit |
| 546-7000 | Tamer proof wrench for cover |
| WFDN4 | Gasket kit |
| UL Model Numbers | ULC/Canadian Model Numbers | Pipe Size | Hole Size |
|---|---|---|---|
| WFD20 | WFD20A | 2" | 1¼" |
| WFD25 | WFD25A | 2½" | 1¼" |
| WFD30 | WFD30A | 3" | 1¼" |
| WFD30-2* | WFD30-2A | 3" | 2" |
| WFD35 | WFD35A | 3½" | 1¼" |
| WFD40 | WFD40A | 4" | 2" |
| WFD50 | WFD50A | 5" | 2" |
| WFD60 | WFD60A | 6" | 2" |
| WFD80 | WFD80A | 8" | 2" |
*UL listed only.
|
UL Models
| ULC/Canadian Models |
Replacement Parts
|
||
|---|---|---|---|---|
| WFD20 | WFD20A | A3008-00 | Retard Mechanism | |
| WFD25 | WFD25A |
A77-01-02 | Terminal Block | |
| WFD30 | WFD30A | 546-7000 | Cover Tamper Switch Kit | |
| WFD30-2 | WFD30-2A | WFDW | Cover Wrench | |
| WFD35 | WFD35A | WFDN4 | Replacement gasket kit | |
| WFD40 | WFD40A | |||
| WFD50 | WFD50A | |||
| WFD60 | WFD60A | |||
| WFD80 | WFD80A | |||
Valves & Accessories » Misc. Valves & Valve Accessories
Inspectors Test & Drain Valve
Inspectors Test & Drain Valve
Features
- Positive positioning of handle for off, test, or drain
- Only 2 threaded connections
- Integral Sight Glass
- May be installed in horizontal or vertical position
- Available test orifice sizes 1/2" and 17/32"
- Available in 1” NPT or 1¼" NPT
Approvals
- UL
- FM
Cross Section

| Valve Size | Take Out | A | B | C | Weight | Orifice | P/N |
|---|---|---|---|---|---|---|---|
| 1" | 4" | 2 ½" | 8¼" | 4 ½" | 3.2 lbs. | ½" | 324067 |
| 1¼" | 4" | 2 ½" | 8¼" | 4 ½" | 3.2 lbs. | ½" | 324066 |
Download this page as a pdf
Valves & Accessories » Butterfly Valves
GLR300W Wafer Type Butterfly Valves
GLR300W Wafer Type Butterfly Valves Wafer Type End, Sizes: 2 ½", 3", 4", 6" and 8"
Specifications
- Working Pressure: 300 PSI (21.4 Bars)
- Max. Test Pressure: 600 PSI (42.8 Bars)
- Max. Working Temp: 250°F (120°C)
Factory installed UL Listed Double Tamper Switch For Indoor and Outdoor Use.
| Materials of Primary Components | |
|---|---|
| Body | ASTM A-536 Nylon-11 Coated |
| Disc | ASTM A-536 EPDM Encapsulated |
| Upper and Lower Stems | AISI 420-SS |
| Worm Gear Shaft | AISI 410-SS |
| Housing | ASTM A-536 |
| Hand Wheel | ASTM A-536 |
| Flag Indicator | ASTM A-536 |
| Sheer Pin | ASTM A-510 |
| Segment Gear | ASTM B-148 or B-584 |
| Housing Gasket | EPDM Grade "E" |
| O-Rings (All) | EPDM Grade "E" |
Approvals
- NYC - DOB MEA Approved 155-06-E
- cULus Listed
- FM Approved (except 8")
Cross Section

Click image above for a detailed view of this product.
| Dimension Unit: in(mm) | ||||||
|---|---|---|---|---|---|---|
| Size | A | B | C | D | E | P/N |
| 2 ½" | 6.54 (166) | 5.31 (135) | 5.35 (136) | 3.43 (87) | 1.81 (46) | 311836-G |
| 3" | 6.81 (173) | 5.31 (135) | 5.63(143) | 3.66 (93) | 1.81 (46) | 311839-G |
| 4" | 7.32 (186) | 5.31 (135) | 6.14 (156) | 4.29 (109) | 2.05 (52) | 311846-G |
| 6" | 8.58 (218) | 8.66 (193) | 7.40 (188) | 5.67 (144) | 2.20 (56) | 311861-G |
| 8" | 9.92 (252) | 8.66 (193) | 8.74 (222) | 6.54 (166) | 2.28 (58) | 311871-G |
Product Related Documents
Download this page as a pdfValves & Accessories » Butterfly Valves
GLR300G Grooved Butterfly Valves
GLR300G Grooved Butterfly Valves, Grooved End, Sizes: 2 ½", 65mm, 3", 4", 6",150mm, 8"
Specifications
- Working Pressure: 300 PSI (21.4 Bars)
- Max. Test Pressure: 600 PSI (42.8 Bars)
- Max. Working Temp: 250°F (120°C)
Factory installed UL Listed Double Tamper Switch For Indoor and Outdoor Use.
| Materials of Primary Components | |
|---|---|
| Body | ASTM A-536 Nylon-11 Coated |
| Disc | ASTM A-536 EPDM Encapsulated |
| Upper and Lower Stems | AISI 420-SS |
| Worm Gear Shaft | AISI 410-SS |
| Housing | ASTM A-536 |
| Hand Wheel | ASTM A-536 |
| Flag Indicator | ASTM A-536 |
| Sheer Pin | ASTM A-510 |
| Segment Gear | ASTM B-148 or B-584 |
| Housing Gasket | EPDM Grade "E" |
| O-Rings (All) | EPDM Grade "E" |
Approvals
| Size | Approvals | ||
|---|---|---|---|
| cULus | FM | NYC - DOB MEA Approved 155-06-E |
|
| 2 ½" | • | • | • |
| 65MM | • | • | - |
| 3" | • | • | • |
| 4" | • | • | • |
| 6" | • | • | • |
| 150MM | • | • | - |
| 8" | • | - | • |
Cross Sections

Click image above for a detailed view of this product.
| Dimension Unit: in(mm) | ||||||
|---|---|---|---|---|---|---|
| Size | A | B | C | D | E | P/N |
| 2 ½" | 5.31 (135) | 5.04 (128) | 4.13 (105) | 3.30 (85) | 3.80 (96.4) | 311785-G |
| 65MM (76MM PIPE O.D.) | 5.31 (135) | 5.04 (128) | 4.13 (105) | 3.30 (85) | 3.80 (96.4) | 311785-GD |
| 3" | 5.59 (142) | 5.04 (128) | 4.41 (112) | 3.60 (92) | 3.80 (96.4) | 311790-G |
| 4" | 6.89 (175) | 5.04 (128) | 5.71 (145) | 4.30 (108) | 4.54 (115.4) | 311795-G |
| 6" | 8.23 (209) | 8.66 (220) | 7.05 (179) | 5.71 (145) | 5.21 (132.4) | 311805-G |
| 150MM (165MM PIPE O.D.) | 8.23 (209) | 8.66 (220) | 7.05 (179) | 5.71 (145) | 5.21 (132.4) | 311805-GD |
| 8" | 9.21 (234) | 8.66 (220) | 8.03 (204) | 6.70 (170) | 5.80 (147.4) | 311815-G |
Product Related Documents
Download this page as a pdfValves & Accessories » Butterfly Valves
GL175G Bronze Butterfly Valves Grooved
GL175G Bronze Butterfly Valves Grooved End, Sizes: 2" and 2½"
Specifications
- Working Pressure: 175 PSI (12.5 Bars)
- Max. Test Pressure: 350 PSI (25.0 Bars)
- Max. Working Temp: 250°F (120°C)
Factory installed UL Listed Double Tamper Switch For Indoor and Outdoor Use.
| Materials of Primary Components | |
|---|---|
| Body | ASTM B-505 |
| Disc | ASTM B-584 EPDM Encapsulated |
| Upper Stem | ASTM A-564 Type XM 12 |
| Lower Stem | ASTM A-564 Type XM 12 |
| Gear Housing, Cover | ASTM A-619 |
| Hand Wheel | ASTM A-619 |
| Flag Indicator | ASTM B-16 |
| York Mechanism | ASTM A-283 |
| Stem Bushing | ASTM B-16 |
| Conduit Connector | ASTM A-307 |
| O-Rings (All) | EPDM Grade "E" |
| Cover Gasket | NBR |
Approvals
- NYC - DOB MEA Approved 155-06-E
- UL, ULC Listed
- FM Approved
Cross Sections

Click image above for a detailed view of this product.
| Dimension Unit: in (mm) | ||||
|---|---|---|---|---|
| Size | A | B | C | P/N |
| 2 " | 1.96(49) | 4.56 (114) | 3.62 (90.5) | |
| 2 ½" | 2.18 (54.5) | 4.56 (114) | 3.82 (95.5) | |
Product Related Documents
Download this page as a pdfValves & Accessories » Butterfly Valves
GL175T Bronze Butterfly Valves Threaded End
GL175T Bronze Butterfly Valves Threaded End, Sizes: 1", 1 ¼", 1 ½", 2" and 2½"
Specifications
- Working Pressure: 175 PSI (12.5 Bars)
- Max. Test Pressure: 350 PSI (25.0 Bars)
- Max. Working Temp: 250°F (120°C)
Factory installed UL Listed Double Tamper Switch For Indoor and Outdoor Use.
| Materials of Primary Components | |
|---|---|
| Body | ASTM B-505 |
| Disc | ASTM B-584 EPDM Encapsulated |
| Upper Stem | ASTM A-564 Type XM 12 |
| Lower Stem | ASTM A-564 Type XM 12 |
| Gear Housing, Cover | ASTM A-619 |
| Hand Wheel | ASTM A-619 |
| Flag Indicator | ASTM B-16 |
| York Mechanism | ASTM A-283 |
| Stem Bushing | ASTM B-16 |
| Conduit Connector | ASTM A-307 |
| O-Rings (All) | EPDM Grade "E" |
| Cover Gasket | NBR |
Approvals
- NYC - DOB MEA Approved 155-06-E
- UL, ULC Listed
- FM Approved
Cross Section

Click image above for a detailed view of this product.
| Dimension Unit: in (mm) | ||||
|---|---|---|---|---|
| Size | A | B | C | P/N |
| 1" | 2.16 (54) | 2.08 (52) | 1.48 (52) | 311725-G |
| 1¼" | 2.68 (67) | 2.24 (56) | 1.64 (41) | 311735-G |
| 1½" | 2.92 (73) | 2.36 (59) | 2.45 (61.3) | 311745-G |
| 2" | 3.3 (82.4) | 2.56 (64) | 1.96 (49) | 311755-G |
| 2½" | 4.16 (104) | 2.78 (69.5) | 2.18 (54.5) | 311760-G |
Product Related Documents
Download this page as a pdfValves & Accessories » RCV Check Valves
J-10 Swing Check Valve - Model “RCV” - 2” - 6”
Swing Check Valve Model RCV Standard & "Shotgun" Groove/Groove 2", 2 ½",65mm, 3", 4", 6" & 150mm Sizes
Description and Operation
Globe Model RCV Swing Check Valves feature a swing type clapper designed for use in fire sprinkler or other types of water piping systems that incorporate grooved connecting pipe ends. They are effectively used when it is necessary to permit water flow in one direction only, preventing flow in the reverse direction (non-return). Because the RCV incorpo- rates a spring-loaded clapper assembly, it may be installed in either the vertical or horizontal position. Most commonly, it is used with various configurations of fire department connections for fire sprinkler systems, by-pass connections, gravity pressure tank and, pump discharge in connections from public water supplies to automatic sprinkler systems, etc.
As an alternative to using an alarm check valve with a wet sprinkler system, an RCV Swing Check Valve may be used in a "Shotgun" arrangement whereby the valve is trimmed in a similar manner but utilizes an electric water flow switch and alarm bell instead of a water motor gong for fire notification.
The body of the Globe RCV Swing Check Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling. It meets the ASTM A126 Class B rating. The RCV clapper assembly is made of stainless steel and has an E.P.D.M. rubber facing. The RCV incorporates a special stainless steel spring assembly which allows its use in the downward flow direction. It effectively provides a leak tight seal against back pressures greater than one (1) psi.
Approvals
- cULus Listed
- FM Approved
- NYC - DOB MEA. 305-05-E
Technical Data
- Water Working Pressure Rating - 300 psi (20.7 Bars)
- Factory tested hydrostatically to 600 psi (41.4 Bars)
- Equivalent feet of pipe: 2" Valve = 7.2 feet, 2 1/2" Valve = 7.2 feet, 3" Valve = 7.2 feet, 4" Valve - 9.9 feet, 6" Valve = 16.1 feet
| Size | A | C | E | F | G | H | I | J | K | L | WEIGHT (lbs.) no trim |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 2" | 1" | 4" | 3½" | 4½" | 6½" | ¼" | 1½" | 2 ¼" | 2½" | 4¾" | 4.5 |
| 2½" | 1¼" | 4½" | 4" | 5" | 7 | ¼" | 1½" | 2 ½" | 2¾ | 5½" | 8 |
| 65MM | 1¼" | 4½" | 4" | 5" | 7 | ¼" | 1½" | 2 ½" | 2¾ | 5½" | 8 |
| 3" | 1¼" | 5 | 4½" | 6" | 7¾" | ¼" | 2" | 3" | 3¾ | 6¾ | 12 |
| 4" | 2" | 6¼" | 4" | 6½" | 8½" | ¼" | 2½" | 3 ½" | 4¼" | 7½" | 17.5 |
| 6" | 2" | 8" | 5" | 8" | 10½" | ¼" | 3¼" | 4 ¼" | 5½" | 10" | 40.5 |
| 150MM | 2" | 8" | 5" | 8" | 10½" | ¼" | 3¼" | 4 ¼" | 5½" | 10" | 40.5 |
Cross Section
Click image above for a detailed view of this product
| Item | Description | Mat'l | 2"P/N | 2½"P/N | 3"P/N | 4"P/N | 6"P/N |
|---|---|---|---|---|---|---|---|
| 65MM | 150MM | ||||||
| 1 | Hinge Pin | Stainless Steel | 321521 | 321528 | 321535 | 321541 | 321549 |
| 2 | Torsion Spring |
Stainless Steel | 321523 | 321531 | 321531 | 321545 | 321554 |
| 3 | Machined Body | Cast Iron | 321501 | 321503 | 321505 | 321507 | 321509 |
| (DIN) | (321503-D) | (321509-D) | |||||
| 4 | 1/2" NPT Plug |
Cast Iron | 311003 | 311003 | 311003 | 311003 | 311003 |
| 5 | Seat Ring |
Brass | 321516 | 321530 | 321537 | 321543 | 321551 |
| 6 | Locknut |
Stainless Steel | 321556 | 321556 | 321556 | 321556 | 321556 |
| 7 | Nameplate |
Aluminum | 321558 | 321558 | 321558 | 321558 | 321558 |
| 8 | Clapper |
Stainless Steel | 321515 | 321527 | 321534 | 321540 | 321548 |
| 9 | Clapper Facing Disc |
EPDM | 321516 | 321529 | 321536 | 321542 | 321550 |
| 10 | Sealing Washer |
Hard Fiber | 321518 | 321518 | 321518 | 321518 | 321518 |
| 11 | Disc Retainer |
Stainless Steel | 321517 | 321517 | 321517 | 321544 | 321544 |
| 12 | Hex Head Bolt | Stainless Steel | 321519 | 321519 | 321555 | 321555 | 321559 |
"Shotgun" Trim Arrangement
| Size | A | B | C |
|---|---|---|---|
| 2" | 10" | 8¾" | 2¼" |
| 2½" | 11" | 9¼" | 2¼" |
| 65MM | 11" | 9¼" | 2¼" |
| 3" | 12" | 9½" | 2½" |
| 4" | 13½" | 10" | 3¼" |
| 6" | 14¼" | 10¾" | 4" |
| 150MM | 14¼" | 10¾" | 4" |
Click image above for a detailed view of this product
| Item | Description | 2"(DIN 50) | 2½" | 66mm (76mm groove) | 3"(DIN 80) | 4"(DIN 100) | 6" | 150mm (165mm groove) | Qty. |
|---|---|---|---|---|---|---|---|---|---|
| 1 | RCV |
321526 | 321533 | 321533-D | 321539 | 321547 | 321557 | 321557-D | 1 |
| 2 | Angle Valve |
311614 (1") | 311615 (1¼") | 311615 (1¼") | 311615 (1¼") | 311617 (2") | 311617 (2") | 311617 (2") | 1 |
| 3 | Close Nipple |
310500 (1") | 310600 (1¼") | 310600 (1¼") | 310600 (1¼") | 310800 (2") | 310800 (2") | 310800 (2") | 1 |
| 4 | 1/4" Water Gauge |
300119 | 300119 | 300119 | 300119 | 300119 | 300119 | 300119 | 2 |
| 5 | 1/4" 3 Way Valve |
311683 | 311683 | 311683 | 311683 | 311683 | 311683 | 311683 | 2 |
| 6 | 1/4" Plug |
311001 | 311001 | 311001 | 311001 | 311001 | 311001 | 311001 | 2 |
| 7 | 1/4" Nipple |
311101 (1½") | 311102 (2") | 311102 (2") | 310102 (2") | 310103 (2½") | 310103 (2½") | 310103 (2½") | 1 |
| 8 | 1/4" x 5 1/2" Nipple | 310109 | 310109 | 310109 | 310109 | 310109 | 310109 | 310109 | 1 |
Ordering Information
When ordering, please specify the following.
- Quantity
- Model Number
- Standard or Shotgun Style
Download this page as a pdf
Sprinklers » Nozzles & Window Sprinklers
I-1 Foam Nozzle - Model J
Foam Nozzle Model J Open Style
Description and Operation
Globe's Model JN Foam Nozzles are most typically used with various foam compounds such as A.F.F.F., Fluoroprotein, Protein and Alcohol type foam liquids for the extinguishment and/or control of hydrocarbon based, polar solvents, and other flammable liquid fires.
Globe's Model JN Foam Nozzles are available in both 3/8" and 1/2" nominal orifice sizes and have a 1/2" NPT male thread. Globe's Foam Nozzle is available in the open style for use with deluge systems. The activation of the deluge valve causes the discharge of foam solution onto the floor in a parabolic shaped discharge pattern.
Technical Data
- See reverse side for Specifications
- Water Working Pressure Rating - 175 psi (12 Bars)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Screen mesh - stainless steel
- Mounting plate - stainless steel
- Retaining Ring - stainless steel
- Weight 29 lbs. (131.5 grams)
Approvals
- cULus Listed
Specifications
| Orifice Size | 'K' Factor | Thread Size | Length x Width | Finishes | ||
|---|---|---|---|---|---|---|
| 3/8" | (10 mm) | 2.8 | (39 metric) | 1/2" NPT |
|
Factory Bronze* |
| 1/2" | (15 mm) | 5.6 | (80 metric) | 1/2" NPT | ||
Note:
- Metric conversions are approximate.
- Minimum recommended nozzle pressure is 15 P.S.I.(1.03 Bars)
- *Finishes available upon special request.
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Quantity - Wrenches - P/N 312366
Download this page as a pdf
Sprinklers » Nozzles & Window Sprinklers
I-5 Window Sprinkler - Model “WS”
Window Sprinklers Model WS
Description and Operation
Globe's Model WS Window Sprinklers are specially designed open style nozzles that provide a 180° relatively flat fan-shaped spray pattern. They are generally used to provide a water curtain over a glass window or other opening to prevent fire / heat penetration. They are also used to provide fire exposure protection from one closely located building to another and are also frequently used to protect steel beams and columns to help preserve structural integrity.
The water flow to Globe's Model Window Sprinkler is controlled either by a manually operated control valve or by means of an automatically operated deluge system.
Globe's Model WS Window Sprinklers may be installed in various positions depending on the hazard being protected. The Window Sprinkler installation diagram shown on this page represents a typical installation for the protection of glass windows. However, N.F.P.A. 13 should be consulted for the proper installation and spacing of the Globe Model WS Window Sprinklers.
Technical Data
- Body - brass
- Finish - brass and chrome; other finishes available upon request
- Weights:
1" Hex .25 lbs. (113.40 grams)
1 1/4" Hex .30 lbs. (136.08 grams)
Approvals
- cULus Listed
Specifications
| Orifice Size | Thread Size | 'K' Factor | Height | ||||
|---|---|---|---|---|---|---|---|
| U.S. | Metric | U.S. | Metric | U.S. | Metric | U.S. | Metric |
| 1/4" | 6.35 mm | 1/2" | 15 mm | 1.4 | 20 mm | 1 3/4" | 44.45 mm |
| 5/16" | 7.94 mm | 1/2" | 15 mm | 2.0 | 29 mm | 1 3/4" | 44.45 mm |
| 3/8" | 9.52 mm | 1/2" | 15 mm | 2.8 | 40 mm | 1 3/4" | 44.45 mm |
| 7/16" | 11.11 mm | 1/2" | 15 mm | 4.2 | 59 mm | 1 3/4" | 44.45 mm |
| 1/2" | 12.70 mm | 1/2" | 15 mm | 5.6 | 80 mm | 2 1/16" | 52.39 mm |
| 17/32" | 13.49 mm | 3/4" | 20 mm | 8.1 | 116 mm | 2 1/16" | 52.39 mm |
| 5/8" | 15.88 mm | 3/4" | 20 mm | 11.4 | 163 mm | 2 1/16" | 52.39 mm |
Cross Sections
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Finish
- Orifice
- Thread Size
Download this page as a pdf
Valves & Accessories » Dry Pipe System
G-2 Air Maintenance Device - Model “H-2” & “H-3”
Air Maintenance Device Model H-2, Model H-3
Description and Operation
Globe's Model H-2 and H-3 Air Pressure Maintenance Devices are automatic, field-adjustable devices that control the on-off cycling of an air compressor. They are used to control the supervisory air pressure in a dry pipe sprinkler system, preaction system, or dry pilot line system of a dry pilot sprinkler actuated deluge or preaction valve. The H-2 and H-3 are utilized in applications where it is desirable or necessary to use a small, non-tank mounted compressor that is to be dedicated to the system to be pressurized. The H-2 and H-3 monitor system pressure and automatically cycle the air compressor on and off to maintain system pressure within the preset limits.
The Model H-2 should be specified when the primary air compressor has an unloader as an integral part. After the initial system air pressure has been established, the 1/2" Globe valve is closed. As pressure on the system side of the 1/4" check valve drops, the air pressure switch contacts close, causing the compressor to start. A restricted orifice limits the rate at which air is replaced. When the system air pressure has been re-established, the switch contacts open, stopping the compressor.
Globe's Model H-3 Air Maintenance Device is similar in operation to the Model H-2. The Model H- 3, however, incorporates an unloader valve. This model is selected when the primary air compressor is not equipped with an unloader device. After the compressor has re-established the required air pressure on the system side of the check valve, the air pressure switch contacts open, stopping the compressor and operating a release valve. The release valve vents the compressor head to exhaust the air trapped between the compressor head and the bypass check valve. On the next automatic operating cycle, the compressor will start against atmospheric pressure, thus preventing excessive starting loads.
Approvals
- UL Listed
- FM Approved
- NYC-DOB MEA 335-91-M
Technical Data
- Physical Dimensions
H-2 - 13 1/2" X 7" (343 mm X 178 mm)
H-3 - 13 1/8" X 7 7/8" (334 mm X 200 mm)
Specifications
| U.S. | Metric | ||||
|---|---|---|---|---|---|
| Minimium Close Pressure | 14 PSI | 0.98 kg/cm2 | |||
| Maximum Open Pressure | 60 PSI | 4.22kg/cm2 | |||
| Differential Pressure | 6-16 PSI | 42 - 1.12 kg/cm2 | |||
| Cut In | 30 PSI | 2.11 kg/cm2 | |||
| Cut Out (Adjustable) | 40 PSI | 2.81 kg/cm2 | |||
| 2 HP | 3 HP | 5 HP | 3 HP | 5 HP | 2 HP |
| 120V single phase |
240V single phase |
600V single phase |
120V 3 phase |
240 - 600V 3 phase |
115 - 230V DC |
Note: Metric Conversions are Approximate.
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | P/N | Item | Description | Mat'l | P/N | |
|---|---|---|---|---|---|---|---|---|
| 1 | Name Plate | Aluminum | 320596 | 9 | ¼ Check Valve | Aluminum | 320589 | |
| 2 | ½ x 3 Nipple | Steel | 310304 | 10 | ¼ X 1 ½ Nipple | Steel | 310101 | |
| 3 | ¼ Needle Valve |
Brass | 320586 | 11 | Pressure Sw itch | Purchase | 320597 | |
| 4 | 1/4 Union | Steel | 311401 | 12 | 3/8 X Close Nipple | Steel | 55122 | |
| 5 | ¼ Close Nipple | Steel | 310100 | 13 | ½ x ½ x 3/8 Tee | Steel | 311309 | |
| 6 | ¼ Black Elbow |
Steel | 311201 | 14 | ½ x 2 Nipple | Steel | 310302 | |
| 7 | ¼ Strainer | Brass | 320587 | 15 | ½ Globe Valve | Brass | 311601 | |
| 8 | Metering Orifice | Brass | 320588 | 16 | ½ X ½ X ¼ Tee | Steel | 311314 |
Click image above for a detailed view of this product
| Item | Description | Mat'l | P/N | Item | Description | Mat'l | P/N | |
|---|---|---|---|---|---|---|---|---|
| 1 | Name Plate | Aluminum | 320601 | 10 | ¼ X 1 ½ Nipple | Steel | 310101 | |
| 2 | ½ Globe Valve | Brass | 311601 | 11 | ¼ Strainer | Brass | 320587 | |
| 3 | ½ Close Nipple | Steel | 310300 | 12 | Metering Orifice | Brass | 320588 | |
| 4 | ½ x ½ x ¼ Tee | Steel | 311314 | 13 | ¼ Check Valve | Aluminum | 320589 | |
| 5 | ½ x 2½ Nipple |
Steel | 310303 | 14 | ¼ X ¼ X 3/8 Tee | Steel | 311309 | |
| 6 | ¼ Needle Valve | Brass | 320586 | 15 | 3/8 X Close Nipple | Steel | 55122 | |
| 7 | ¼ Union | Steel | 311401 | 16 | Pressure Sw itch | Purchase | 320602 | |
| 8 | ¼ Close Nipple | Steel | 310100 | 17 | Connector Tubing - 19" | Copper | 320604 | |
| 9 | ¼ Black Elbow | Steel | 311201 | 18 | Tube Fitting | Brass | 320603 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
Download this page as a pdf
Valves & Accessories » Dry Pipe System
G-1 Air Maintenance Device - Model H1
Air Maintenance Device - Model H1
Description and Operation
Globe's Model H-1 Air Pressure Maintenance Device is an automatic, field-adjustable device of the pressure reducing type. It is used to control the supervisory air pressure in a dry pipe sprinkler system, preaction system, or dry pilot line system of a dry pilot sprinkler actuated deluge or preaction valve. The H-1 is utilized in applications where there is a compressed air (or nitrogen) source which is at a higher pressure than the desired system pressure. Pressure sources include plant air supplies having their own automatic compressor controls, or nitrogen supplies having single-stage cylinder mounted pressure regulators.
The 1/2" globe valve is opened to admit air speedily to the dry pipe system. It is closed once the desired system air pressure has been established. As pressure drops on the system side of the 1/4" check valve, the regulator and metering orifice operate automatically to replace small losses of air which periodically occur in the system due to temperature or other system variations. The regulator and metering orifice limit the volume of air introduced to assure that the rate of air replacment is less than that from a discharging sprinkler so that system activation may take place.
Approvals
- UL Listed
- FM Approved
- NYC-DOB MEA 335-91-M
Technical Data
- Physical Dimensions
9 11/16" x 7 3/4"
(246 mm X 197 mm)
Specifications
| U.S. | Metric | |
|---|---|---|
| Pressure Range Output | 15-50 PSI | 1.05-3.51 kg/cm2 |
| Pressure Differential | 2 1/2 PSI | 0.176 kg/cm2 |
|
Connections
|
||
| From Air Supply | 1/2" FEMALE NPT | |
| To System | 1/2" FEMALE NPT | |
Note: Metric Conversions are Approximate.
Cross Sections
| Item | Description | Mat'l | P/N | Item | Description | Mat'l | P/N | |
|---|---|---|---|---|---|---|---|---|
| 1 | Name Plate | Aluminum | 320592 | 8 | 1/4 Black Elbow | Steel | 311201 | |
| 2 | 1/2 Globe Valve | Brass | 311601 | 9 | 1/4 Strainer | Brass | 320587 | |
| 3 | 1/2 X 3 1/2 Nipple | Steel | 310305 | 10 | Metering Orifice | Brass | 320588 | |
| 4 | 1/2 X 1/2 X 1/4 Tee | Steel | 311314 | 11 | Air Regulator | Aluminum | 320590 | |
| 5 | 1/4 Needle Valve | Brass | 320586 | 12 | 1/4 Check Valve | Aluminum | 320589 | |
| 6 | 1/4 Union | Steel | 311401 | 14 | 1/4 X 2 Nipple | Steel | 310102 | |
| 7 | 1/4 Close Nipple | Steel | 310100 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
Download this page as a pdf
Valves & Accessories » Dry Pipe System
F-1 Accelerator & Anti-Flooding Device - Model “C”
Accelerator and Anti-Flooding Device Model C
Description and Operation
Globe's Model C Accelerator is a precision made device used to reduce the time lag normally associated with the opening of a Dry Pipe Valve after one or more system sprinklers have operated. In essence, the Model C Accelerator "accelerates" the opening of the Dry Pipe Valve resulting in faster water discharge from the opened sprinkler(s).
The Model C Accelerator basically monitors the air pressure in a Dry Pipe System. If a rapid loss of system air pressure occurs, as would with the opening of one or more sprinklers, the accelerator senses this loss and immediately sends pressurized air to the intermediate chamber of the Dry Pipe Valve upsetting the pressure differential and causing it to operate instantly.
Globe incorporates the use of its Model C Anti-Flooding Device to help ensure the proper operation of the Model C Accelerator by preventing most water-borne foreign objects from entering the Accelerator. Such objects could cause clogging of the Accelerator and hinder its proper operation. Because of its importance, the Model C Anti-Flooding Device is always included with orders for the Model C Accelerator and should always be properly installed. Accelerators are precision made devices, however, and must be kept clean of foreign matter. A thorough cleaning after use is recommended.
After the Accelerator has operated, the pressurized air in the Accelerator Body and its associated piping is discharged to the Model C Anti-Flooding Device's lower inlet stopping any flow through the piping leading to the Accelerator. This occurs very quickly and always before water reaches the Anti-Flooding Device.
Approvals
- cULus Listed
- FM Approved
- N.Y.C. - D.O.B MEA 353-91-M
Technical Data
- Water Working Pressure Rating - 175 psi (1207 kPa)
Cross Sections
Accelerator
Click image above for a detailed view of this product
| Item | Description | Mat'l | P/N | Item | Description | Mat'l | P/N | |
|---|---|---|---|---|---|---|---|---|
| 1 | Upper Chamber | Bronze | 300401 | 9 | Restricted Orifice Pin | Monel | 300411 | |
| 2 | Lower Chamber and Valve Seat Assembly | Bronze | 300402 | 10 | Valve Disc and Disc Retainer Assembly | Neoprene/Brass | 300412 | |
| 3 | Pressure Plate | Brass | 300405 | 11 | Retaining Screw | Bronze | 300415 | |
| 4 | Diaphragm Plate | Brass | 300406 | 12 | Spring Retainer Disc | Brass | 300416 | |
| 5 | Nut | Bronze | 300407 | 13 | Gasket | E.P.D.M. | 300417 | |
| 6 | Gasket | E.P.D.M. | 300408 | 14 | Spring | Bronze | 300418 | |
| *7 | Clamping Ring | Brass | 300409 | 15 | Plug | Brass | 300419 | |
| *8 | Diaphragm | Neoprene | 300410 |
*323489 Accelerator Clamping Ring Wrench (Item #7) for use when replacing the Diaphram Item #8.
Refer to Globe’s Dry Pipe Valve Installation and Maintenance Guide (Bulletin D.P.V.I.M.) for trim set-up.Anti-Flooding Device 
Click image for a detailed view of this product
| Item | Description | Mat'l | P/N |
|---|---|---|---|
| 1 | Top | Brass | 323334 |
| 2 | Body | Brass | 323333 |
| 3 | Diaphragm | E.P.D.M | 323335 |
| 4 | Spring | Stainless Steel | 323336 |
| 5 | Screw | Steel | 323337 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Size
- Untrimmed or Factory Trimmed and Leak Tested Hydrostatically.
Product Related Documents
Download this page as a pdfValves & Accessories » Dry Pipe System
E-10 Dry Pipe Valve - Model “A” - 3”
Dry Pipe Valve Model A*, Flange/Flange 3" Size
The Globe Model A Dry Pipe Valve is the vital control unit in dry pipe automatic sprinkler systems, where super- visory air under pressure is used to prevent freezing that would certainly occur with ordinary wet pipe systems. The Dry Pipe Valve is the connecting link between the source of water supply and the automatic sprinklers, and must react promptly when it receives a signal from the protected area that a fire condition has developed and water is therefore quickly needed. This signal is generated by the opening of one or more sprinklers which causes a quick drop in system supervisory air pressure resulting in a loss of the differential force ratio.
The single clapper assembly design in the Globe Model A Dry Pipe Valve, provides a differential force ratio of approximately 6:1 between system air pressure and water supply pressure. Once the valve has operated, a special latch holds the clapper open until manually reset by qualified personnel.
The body of the Dry Pipe Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling.
All interior operating parts are machined from highly corrosive-resistant copper alloys, each having high strength and good wear resistance.
Rubber parts are of selective materials which have good abrasive resistance and long life expectancy in terms of resiliency.
NOTE: *Formerly known as Model D
Approvals
- cULus Listed
- FM Approved
Technical Data
- Water Working Pressure Rating - 175 psi (12Bars)
- Factory tested hydrostatically to 350 psi (24Bars)
| PHYSICAL DATA | |
|---|---|
| Size | 3" |
| Overall Length | 14 1/2" |
| Center of Valve to Front | 11" |
| Center of Valve to Back | 9" |
| Center of Valve to Right | 17" |
| Center of Valve to Left | 6" |
| Weight of Value | 106 lbs. |
| Water Pressure P.S.I | Air Pressure Requirements P.S.I |
|
|---|---|---|
| max | min | max |
| 30 | 15 | 20 |
| 50 | 20 | 25 |
| 75 | 25 | 30 |
| 100 | 30 | 35 |
| 125 | 35 | 40 |
| 150 | 40 | 45 |
| 175 | 45 | 50 |
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | P/N | Item | Description | Mat'l | P/N | |
|---|---|---|---|---|---|---|---|---|
| 1 | Cover Plate | Cast Iron | 318501 | 12 | Machine Screw | Bronze | 318512 | |
| 2 | Cover Plate Gasket | Rubber | 318502* | 13 | Pin Air Seat Gasket | Rubber | 318513* | |
| 3 | Cover Plate Stud | Steel | 318503 | 14 | Water Seal Gasket | Rubber | 318514* | |
| 4 | Nut | Steel | 318504 | 15 | Machine Screw | Brass | 318515 | |
| 5 | Latch | Cast Iron | 318505 | 16 | Clapper Hinge Pin | Brass | 318516 | |
| 6 | Clapper Arm Assembly | ------- | 318506 | 17 | Cotter Pin | Brass | 318517 | |
| 7 | Clapper Arm Hinge Pin | Monel | 318507 | 18 | Latch Pin | Brass | 318518 | |
| 8 | Hinge Pin Plug | Brass | 318508 | 19 | Retaining Washer | Brass | 318526 | |
| 9 | Clapper Assembly | ----- | 318509 | 20 | Seat Ring | Bronze | 318522 | |
| 10 | Clapper | Bronze | 318510 | 21 | Air Seat | Bronze | 318523 | |
| 11 | Clapper Ring | Bronze | 318511 |
* Available as a kit only - P/N 318519
Refer to Globe's Dry Pipe Valve Installation and Maintenance Guide (Bulletin D.P.V.I.M.) for trim set-up,
installation instructions, and maintenance.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Size
- Factory Trimmed and Leak Tested Hydrostatically or Loose Trim for Customer Installation.
Product Related Documents
Download this page as a pdfValves & Accessories » Dry Pipe System
E-1 Dry Pipe Valve - Models “F-3” & “G-3” - 4” & 6”
Dry Pipe Valve Model F-3 Flange/Flange, Model G-3 Flange/Groove 4" & 6" Sizes
Description and Operation
The Globe Model F-3 and G-3 Dry Pipe Valves are the vital control unit in dry pipe automatic sprinkler systems, where supervisory air under pressure is used to prevent freezing that would certainly occur with ordinary wet pipe systems. The Dry Pipe Valve is the connecting link between the source of water supply and the automatic sprinklers, and must react promptly when it receives a signal from the protected area that a fire condition has developed and water is therefore quickly needed. This signal is generated by the opening of one or more sprinklers which causes a quick drop in system supervisory air pressure resulting in a loss of the differential ratio.
The single clapper assembly design in the Globe Model F-3 and G-3 Dry Pipe Valves, provides several areas exposed to working pressures which, in combination, create a differential force ratio between system air pressure and water supply pressure. A single-latching lever is provided as a means of holding the clapper in "set" position. Once the valve has operated, a special latch holds the clapper open until manually reset by experienced personnel.
The body of the Dry Pipe Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling.
All interior operating parts are machined from highly corrosive-resistant copper alloys, each having high strength and good wear resistance.
Rubber parts are of selective materials which have good abrasive resistance and long life expectancy in terms of resiliency.
Approvals
- cULus Listed
- FM Approved
- NYC - DOB MEA 324-91-M
Technical Data
- Water Working Pressure Rating - 175 psi (1207 kPa)
- Factory tested hydrostatically to 350 psi (2414 kPa)
| PHYSICAL DATA | Model Size | |||
|---|---|---|---|---|
| F-3 | G-3 | |||
| 4" | 6" | 4" | 6" | |
| Overall Length | 16" | 16 ½" | 16" | 16 ½" |
| Center of Valve to Back | 11" | 12" | 11" | 12" |
| Center of Valve to Right | 12" | 12" | 12" | 12" |
| Center of Valve to Left | 10" | 11" | 10" | 11" |
| Weight of Valve Complete with all Trimmings |
161 lbs 179 lbs. |
231 lbs. 249 lbs. |
151 lbs 169 lbs. |
221 lbs. 239 lbs. |
| Minimum Inside Dimensions of Enclosing Valve House |
45" x 52" | 45" x 52" | 45" x 52" | 45" x 52" |
| Friction Loss in Equivalent Feet |
19' - 6" | 31' - 0" | 19' - 6" | 31' - 0" |
| Water Pressure P.S.I | Air Pressure Requirements P.S.I |
|
|---|---|---|
| max | min | max |
| 30 | 15 | 20 |
| 50 | 20 | 25 |
| 75 | 25 | 30 |
| 100 | 30 | 35 |
| 125 | 35 | 40 |
| 150 | 40 | 45 |
| 175 | 45 | 50 |
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | 4" P/N | 6" P/N | Item | Description | Mat'l | 4" P/N | 6" P/N | |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Bellofram | EPDM | 319794 | 319844 | 20 | Side Cover Plate | Cast Iron | 319767 | 319814 | |
| 2 | Seat Ring | Bronze | 300014 | 300213 | 21 | Pin | Bronze | 300011 | 300210 | |
| 3 | Clapper and Ring Assembly | Bronze | 319779 | 319821 | 22 | Packing Nut | Bronze | 300025 | 300025 | |
| 4 | Lever | Bronze | 319757 | 319807 | 23 | Cover Bolt | Steel | 319768 | 319815 | |
| 5 | Rubber Seat Ring | EPDM | 319791 | 319841 | 24 | Cap Screw (6 req'd) | Bronze | 319760 | 319760 | |
| 6 | Compression Plate | Bronze | 319752 | 319802 | 25 | Rubber Gasket | Rubber | 300030 | 300030 | |
| 7 | Retaining Ring | Bronze | 319792 | 319842 | 26 | Pin | Brass | 300031 | 300031 | |
| 8 | Clapper Latch | Bronze | 300015 | 300214 | 27 | Bronze Washer | Bronze | 300032 | 300032 | |
| 9 | Locking Stud | Bronze | 300016 | 300215 | 28 | Packing Gland Ring | Bronze | 300035 | 300035 | |
| 10 | Body - F-3 | Cast Iron | 319765 | 319813 | 29 | Lock Washer | Bronze | 319761 | 319761 | |
| Body - G-3 | Cast Iron | 319704 | 319812 | 30 | Cap Screw | Bronze | 319762 | 319762 | ||
| 11 | Hinge Pin | Bronze | 300018 | 300217 | 31 | Shield | Elastomer | 319758 | 319808 | |
| 12 | Bushing | Bronze | 300019 | 300218 | 32 | Memory Washer | Brass | 319763 | 319811 | |
| 13 | Pin | Bronze | 319798 | 319845 | 33 | Cotter Pin | Brass | 300211 | 300211 | |
| 14 | Latch Screw | Brass | 300020 | 300020 | 34 | Nut | Brass | 319756 | 319806 | |
| 15 | Plug | Bronze | 300021 | 300021 | 35 | Packing | PTFE | 300036 | 300036 | |
| 16 | Atmospheric Discharge Tube | Brass | 319766 | 300022 | 36 | 1" Close Nipple | Galvanized | 310303-G | 310303-G | |
| 17 | Retaining Ring Screw (6 req'd) | Bronze | 319778 | 319778 | 37 | 1" Elbow | Steel | 311205 | 311205 | |
| 18 | Cover Plate Gasket | Rubber | 300023 | 300219 | N/S | Cover Release Screw | Stainless | 300012 | 300012 | |
| 19 | Clamping Ring | Bronze | 319793 | 319843 |
Refer to Globe's Dry Pipe Valve Installation and Maintenance Guide (Bulletin D.P.V.I.M.) for trim set-up,
installation instructions, and maintenance.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Size
- Factory Trimmed and Leak Tested Hydrostatically or Loose Trim for Customer Installation.
Product Related Documents
Download this page as a pdfValves & Accessories » Wet Alarm System
D-1 Retarding Chamber Model H
Retarding Chamber Model H
Description and Operation
The Globe Model H Retarding Chamber is an accessory which is used with variable pressure wet sprinkler systems where water motor alarms and / or pressure switches are used in conjunction with Globe's Alarm Check Valves. It serves primarily as a hydraulic time delay to prevent most false alarms associated with fluctuating water supply pressures. In situations where excessive water pressure surges occur, the Model H Retarding Chamber is needed to collect excess water from the Alarm Check Valve and feed water back into the main drain, before activating the alarm. An additional retarding chamber could be needed if pressure surges exceed the capacity of one retarding chamber.
Water enters the retarding chamber through the 1/2" NPT Inlet and automatically flows through a restricted orifice and to drain; when the drain capacity is exceeded, as when the alarm check valve clapper remains open or when the system is being tested, the retarding chamber capacity is reached, and water then flows through the Outlet to the water motor alarm and / or electric alarm switch.
The body of the Retarding Chamber has considerable ductility to reduce damage in field handling.
All interior operating parts are machined from highly corrosive-resistant alloys, each having high strength and good wear resistance.
Approvals
- cULus Listed
- FM Approved
- LPCB Approved
Technical Data
- Water Working Pressure Rating - 175 psi (12 bars)
- Factory tested hydrostatically to 350 psi (24 bars)
- Capacity - 1 Gallon (3.785 liters)
- Body - High Tensile Cast Iron
Cross Sections

Click image for a detailed view of this product
| Item | Description | Mat'l | P/N |
|---|---|---|---|
| 1 | Outlet Bushing | Cast Iron | 323354 |
| 2 | Machined Body | Cast Iron | 323352 |
| 3 | Hex Head Machine Screw | Brass | 323357 |
| 4 | Cup | Brass | 323356 |
| 5 | Strainer Screen | Brass | 323355 |
| 6 | Drain Bushing | Brass | 323353 |
Refer to Globe’s Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation instructions, and maintenance.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
Download this page as a pdf
Valves & Accessories » Wet Alarm System
C-2 Alarm Check Valve - Model “H” Series 8”
Alarm Check Valve 8" Model H-1 Flange/Flange, 8" Model H-3 Flange/Groove
Description and Operation
The Globe Model H-1 and H-3 8" Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water through their bodies (non-return) and also provide for the use of a hydraulic fire alarm which is not dependent upon an electrical power supply for its operation. Through the use of a hydraulic retard chamber a time delay is provided to eliminate potential false alarms caused by fluctuating water supply pressures. Where constant pressure water supplies are used the retard chamber (time delay) is not necessary. By incorporating the use of electrical pressure switches, other supplemental alarms, annunciators etc. may also be used.
Globe 8" Model H-1 and H-3 Alarm Check Valves may be installed in the vertical position and trim can be provided for both variable and constant water supply pressures.
The body of the Alarm Check Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling.
All interior operating parts are machined from highly corrosive-resistant alloys, each having high strength and good wear resistance.
Rubber parts are of selective materials which have good abrasive resistance and long life expectancy in terms of resiliency.
Technical Data
- Water Working Pressure Rating - 175 psi (12 bars)
- Factory tested hydrostatically to 350 psi (24 bars)
- Equivalent feet of pipe: 8" Valve = 21 feet
| Physical Data | Model Size | |
|---|---|---|
| H-1 | H-3 | |
| Overall Length | 13 7/8" | 15 1/8" |
| Weight of Valve Complete with Verticle Variable Pressure Trimmings |
150 lbs. | 130 lbs. |
| 200 lbs. | 180 lbs. | |
Approvals
- cULus Listed
- FM Approved
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | P/N |
|---|---|---|---|
| 1 | Body - H-1 | Cast Iron | 323832 |
| Body H-3 | Cast Iron | 323851 | |
| 2 | Cover | Cast Iron | 323835 |
| 3 | Cover Gasket | Rubber | 323833 |
| 4 | Cover Bolt | Steel | 323839 |
| 5 | Seat Ring | Bronze | 323837 |
| 6 | Clapper | Bronze | 323841 |
| 7 | Clapper Disc | EPDM | 323842 |
| 8 | Disc Retainer | Stainless | 323843 |
| 9 | Disc Retainer Bolt | Stainless | 323838 |
| 10 | Hinge Pin | Stainless | 323845 |
| 11 | Hinge Pin Bushing | Bronze | 323846 |
| 12 | Name Plate | Aluminum | 323480 |
| 13 | Drive Screw | Stainless | 323420 |
Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation instructions, and maintenance.
Product Related Documents
Download this page as a pdfValves & Accessories » Wet Alarm System
C-1 Alarm Check Valve - Model “H” Series: 3”, 4”, and 6”
Alarm Check Valve 3", 4" & 6" Model H-1 Flange/Flange, 3" & 4" Model H-2 Groove/Groove, 3", 4" & 6" Model H-3 Flange/Groove
Description and Operation
The Globe Model H-1, H-2 and H-3 Alarm Check Valves are used in wet pipe fire sprinkler systems. They primarily serve a dual purpose in that they prevent a reverse flow of water through their bodies (non-return) and also provide for the use of a hydraulic fire alarm which is not dependent upon an electrical power supply for its operation. Through the use of a hydraulic retard chamber a time delay is provided to eliminate potential false alarms caused by fluctuating water supply pressures. Where constant pressure water supplies are used, the retard chamber (time delay) is not necessary. By incorporating the use of electrical pressure switches, other supplemental alarms, annunciators etc. may also be used.
A unique feature found on the Globe 3", 4" and 6" Alarm Valves is the clapper being hinged to the handhole cover for extreme ease of removal for inspection and service.
Globe Model H-1, H-2 and H-3 Alarm Check Valves may be installed in both vertical and horizontal positions, and trim can be provided for both variable and constant water supply pressures in either of these positions.
The body of the Alarm Check Valve is constructed of high tensile strength cast iron having considerable ductility to reduce damage in field handling.
All interior operating parts are machined from highly corrosive-resistant alloys, each having high strength and good wear resistance.
Rubber parts are of selective materials which have good abrasive resistance and long life expectancy in terms of resiliency.
Technical Data
- Water Working Pressure Rating - 175 psi (12 bars) (See below for more specific rating approvals.)
- 4" Model "H-1" cULus Listed with D.I.N. Class 16 flanges has a pressure rating of 16 bars
- 4" and 6" Model "H-1" LPCB Approved for a 16 bar pressure rating with DIN Class 16 flanges and for a 20 bar pressure rating with DIN Class 25 flanges
- Factory tested hydrostatically at twice the rated working pressure
- Equivalent feet of pipe: 3" Valve = 12.2 feet, 4" Valve = 9.7 feet, 6" Valve = 17 feet
| PHYSICAL DATA | Model / Size | |||||||
|---|---|---|---|---|---|---|---|---|
| H-1 | H-2 | H-3 | ||||||
| 3" | 4" | 6" | 3" | 4" | 3" | 4" | 6" | |
| Overall Length | 9" | 9" | 10" | 10" | 10" | 91/4" | 91/2" | 11" |
| Weight of Vavle Complete with Verticle Variable Pressure Trimmings |
34 lbs. | 42 lbs. | 69 lbs. | 20 lbs. | 22 lbs. | 28 lbs. | 37 lbs. | 59 lbs. |
| 81 lbs. | 89 lbs. | 114 lbs. | 57 lbs. | 69 lbs. | 75 lbs. | 84 lbs. | 100 lbs. | |
Approvals
cULus Listed
FM Approved
LPCB Approved – H1 & H3
NYC – DOB MEA 325-91-M
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | 3" P/N | 4" P/N | 6" P/N |
|---|---|---|---|---|---|
| 1 | Body - H-1 | Cast Iron | 323803 | 323502 | 323562 |
| Body H-2 | Cast Iron | 323827 | 323552 | ------ | |
| Body H-3 | Cast Iron | 323807 | 323542 | 323592 | |
| 2 | Cover Bolt | Steel | 323408 | 323509 | 323569 |
| 3 | Seat Ring | Bronze | 323809 | 323504 | 323564 |
| 4 | Cover | Cast Iron | 323805 | 323507 | 323567 |
| 5 | Clapper | Stainless | 323814 | 323510 | 323570 |
| 6 | Retaining Ring | Stainless | 323527 | 323517 | 323517 |
| 7 | Hinge Pin | Stainless | 323818 | 323516 | 323516 |
| 8 | Cover Gasket | Vellumoid | 323810 | 323508 | 323568 |
| 9 | Clapper Facing Disc | EPDM | 323815 | 323511 | 323571 |
| 10 | Disc Retainer | Stainless | 323816 | 323512 | 323572 |
| 11 | Lock Nut | Stainless | 323514 | 323514 | 323514 |
| 12 | Disc Retainer Bolt | Stainless | 323817 | 323513 | 323573 |
| 13 | Sealing Washer | Hard Fiber | 323515 | 323515 | 323515 |
| 14 | Hinge Pin Bushing | Bronze | 323819 | 323518 | 323518 |
| 15 | Name Plate | Aluminum | 323480 | 323480 | 323480 |
| 16 | Drive Screw | Stainless | 323520 | 323520 | 323520 |
| 17 | Torsion Spring | Stainless | 323528 | 323528 | 323565 |
| 18 | Spring Bushing | Brass | ------ | ------ | 323579 |
Refer to Globe’s Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation instructions, and maintenance.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Size
- Factory Trimmed and Leak Tested Hydrostatically or Loose Trim for Customer Installation.
Product Related Documents
Download this page as a pdfValves & Accessories » Wet Alarm System
N-1 Water Motor Gong - Model WM & WM2
Water Motor Alarm Model WM Model WM-2
Description and Operation
Globe's Model WM and WM-2 Water Motor Alarms are hydraulically operated indoor and outdoor alarms for use with fire protection systems. They are lightweight yet durable, and can be used in conjunction with alarm check, dry pipe, deluge, and preaction valves to sound a local alarm. This water-powered system eliminates the need for an electrical alarm and will operate even if electrical power is lost.
Globe's Model WM Water Motor Alarm features a one- gong system which sounds an alarm outside the building. Globe's Model WM-2 Water Motor Alarm features a unique two-gong system which provides an audible fire alarm both inside and outside the building.
The Water Motor Alarms are suitable for mounting to any type of rigid wall and can accomodate a wall thickness up to 16" (406.4 mm). They are provided with a listed and approved strainer for use in the alarm line. The Gong, Gong Mount, and Water Motor Housing are fabricated from corrosion- resistant cast aluminum. The polymer drive bearings do not require lubrication.
The WM and WM-2 utilize a lightweight, impeller design which can produce a very high decibel sound level. As water passes through the water motor, the impeller turns and the shaft rotates. The rotating shaft drives a striker assembly which rings the gong, sounding a continuous alarm as long as the water flow continues.
Approvals
- cULus Listed
- FM Approved
- NYC-DOB MEA 326-91-M
Technical Data
- Body - cast aluminum
- Finish - red
Cross Sections
Click image above for a detailed view of this product
| Item | Description | Mat'l | WM P/N | WM-2 P/N |
|---|---|---|---|---|
| 1 | Gong Shell | Aluminum | 325506 | 325506 |
| 2 | Hex Head Cap Screw | Zinc | 325521 | 325521 |
| 3 | Gong Mounting Bracket | Aluminum | 325504 | 325504 |
| 4 | Motor Cover | Aluminum | 325509 | ------ |
| Inside Gong Backing Plate | Aluminum | ------ | 325532 | |
| 5 | Impeller Housing | Aluminum | 325502 | 325502 |
| 6 | Impeller | Delrin | 325507 | ------ |
| Impeller - Inside Gong | Delrin | ------ | 325533 | |
| 7 | Striker Shaft | Delrin | 325508 | 325508 |
| 8 | Drive Shaft | Aluminum | 325515 | 325515 |
| 9 | Threaded Pipe | Galvanized Pipe | 325517 | 325517 |
| 10 | Striker Arm |
Mild Steel | 325510 | 325510 |
| 11 | Cap Screw | Zinc Plated | 325520 | 325520 |
| 12 | Knocker | Phenolic | 325513 | 325513 |
| 13 | Knocker Retaining Washer | Stainless Steel | 325516 | 325516 |
| 14 | Knocker Retaining Rivet | Stainless Steel | 325514 | 325514 |
| 15 | Bearing-Thompson | Type 6 Nylon | 325518 | 325518 |
| 16 | 3/8 Helical Spring Lock Washer | Steel | 325522 | 325522 |
| 17 | Backing Plate Gasket | Velumoid | 325511 | 325511 |
| 18 | Wall Plate | Mild Steel | 325528 | 325528 |
Refer to Globe's Water Motor Alarm Installation and Maintenance Guide (Bulletin WMA-I) for trim set-up, installation instructions, and maintenance.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
Product Related Documents
Download this page as a pdfSprinklers » Sprinkler Accessories
B-2 Standard Escutcheons
Globe Standard Escutcheons
Standard Escutcheons 1/2” NPT or 3/4” NPT
Universal for all sprinkler models
1 Pc. (1/4” x 3” Diameter)
- Chrome: 325398
- Chrome-RP: 325398-RP
- Brass: 325399
- White: 325400
1 Pc. (5/8” x 2 7/8” Diameter)
- Chrome: 312086
- Brass: 312088
- White: 312090
- Chrome: 312087
- Brass: 312089
- White: 312091
2 Pc. (max. 2 3/4” x 3 1/2” Diameter)
- Chrome: 312075
- Chrome-P: 312075-P
- Brass: 312076
- White: 312074
- White-P: 312074-P
- Chrome: 312077
- Brass: 312078
- White: 312079
Optional Skirts for 2 Pc. Extended Escutcheon Short Taper Skirt
(reduces deflector to ceiling distance by 3/4”)
- Chrome: 312040
- Brass: 312041
- White: 312042
Flush Skirt
(reduces deflector to ceiling distance by 1 1/4”)
- Chrome: 312044
- Brass: 312045
- White: 312046
*NOTE: Other Escutcheons Available Upon Request. Unless stated “-RP” (rust proof) or “-P” (plastic), all escutcheons are coated/plated for decorative purposes only, thus not recommended for corrosive atmospheres.
Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-10 Escutcheon Tool
Escutcheon Tool For Recessed Automatic Sprinklers
Description and Operation
Globe's escutcheon installation tool for recessed style sprinklers is designed for the installation of Globe's Friction Type Recessed Escutcheon.
By varying the length of the PVC pipe used, the escutcheon may be installed from the floor without the use of scaffolding, ladder, etc., for most ceiling heights.
The Globe Escutcheon Installation Tool incorporates an internal spring to compensate for the amount of the sprinkler exposed below the ceiling.
Technical Data
- PVC Plastic with stainless steel spring
Cross Sections



Download this page as a pdf
Sprinklers » Sprinkler Accessories
B-1 Sprinkler Headguard Without Water Shield
Sprinkler Headguard Model GL Series Automatic Sprinklers
Description and Operation
The Globe Model GL Series sprinkler is designed for use where mechanical injury to the sprinkler might be expected. Typical areas of usage are in storage racks or under open grating.
The Globe headguard can be used with either the 1/2" or 17/32" orifice Model GL Series sprinklers.
Technical Data
- Overall Length
1/2" NPT sprinklers - 2 7/8"
3/4" NPT sprinklers - 3"
1/2" NPT & 3/4" NPT sprinklers - 3 1/4" - Materials
Headguard - steel
- Finishes
Red Enamel painted
Chrome plated
Approvals
FM Approved for use with the Globe GL Series 1/2" and 17/32" orifice upright sprinklers.
Download this page as a pdf
Sprinklers » Sprinkler Accessories » Dry Sprinklers » Dry Type Accessories
B-1 Sprinkler Headguard With Water Shield
Sprinkler Headguard with Water Shield for Model GL Series Automatic Sprinklers
Description and Operation
The Globe Model GL upright sprinkler combined headguard and water shield is designed for use where mechanical injury to the sprinkler might be expected and where a water shield is needed to protect the sprinkler's thermosensitive element from the water spray discharge of higher elevation sprinklers which could operate sooner during a fire.
The Globe combined headguard and water shield can be used with either the 1/2" or 17/32" orifice Model GL upright sprinklers.
Typical areas of usage are in storage racks, under open grating or even outdoors as a protection from weather.
Technical Data
- Overall Length
1/2" NPT sprinklers - 2 7/8"
3/4" NPT sprinklers - 3" - Materials
Headguard - steel
Water shield - steel - Finishes
Red Enamel painted
Chrome plated
Approvals
FM Approved for use with the Globe GL Series 1/2" and 17/32" orifice upright sprinklers.
Download this page as a pdf
Dry Sprinklers » Dry Type Sprinkler Vertical Sidewall
A-94 Dry Type Vertical Sidewall Sprinkler
GL Series Dry Type Vertical Sidewall Upright & Pendent
The Globe GL Series Dry Type Vertical Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe GL Series Dry Type Vertical Sidewall Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with glycerin solution, 5mm size
- Orifice insert - brass
- 3/4" or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length* | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | Variable to 48" |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 Wax Coated1 Wax Over Lead1 |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- *cULus listed for up to a 48" "A" dimension.
- 1Finishes available on special order
- Wax coating cULus listed up to 200°F.
- 2C-U.L. listed corrosion resistant - polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | *cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|
| Vertical Sidewall |
GL5687 | 5.6 | 1" NPT | • | • | • | • | • | • | • |
| GL5688 | 5.6 | 3/4" NPT | • | • | • | • | • | • | • | |
| GL8187 | 8.1 | 1" NPT | • | • | • | • | • | • | • |
Note:
- *3/4" NPT x 5.6K orifice and 1" NPT x 8.1K orifice listed for ordinary hazard.
- Pendent vertical sidewall cULus listed for 6' min. spacing.
- Upright vertical sidewall cULus listed for 9' min. spacing.

Globe GL Series Dry Vertical sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
The GL Series Dry Sprinkler must not be installed in a short radius 90° elbow. When installing in other than an iron tee, the clearances between the end of the sprinkler and fitting should be checked.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used;
"B" Dimension - Distance from face of fitting to the top of the deflector.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Upright
A-95 GL Series Dry Type Upright Sprinkler
GL Series Dry Type Upright
Description and Operation
The Globe GL Series Dry Type Upright Sprinkler is designed for use in special applications such as freezing environments. As an example, they may be efficiently used when connected to a wet type sprinkler system and extended into an unheated attic space.
The Globe GL Series Dry Type Upright Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in the approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C), 155°F (68°C)
175°F (79°C), 200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring assembly - teflon coated nickel alloy and brass
- Bulb - glass with glycerin solution, 5mm size
- Orifice insert -brass
- 3/4 NPT or 1" NPT
- Stabilizer bar - bronze
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | cULus Variable to 48" |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester Black Polyester Lead Coated1 Wax Coated1 Wax over Lead1 |
| 8.1 | (116 metric) | 1" NPT | FM Variable to 36" |
|
Note:
- Metric conversions are approximate.
- cULus listed corrosions resistent; Polyester must be specified on order.
- 1Finishes available on special order.
- - Wax Coating cULus listed up to 200°F.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | *FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Upright | GL5683 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5684 | 5.6 | 3/4" NPT | • | • | • | • | • | • | — | • | |
| GL8183 | 8.1 | 1" NPT | • | • | • | • | • | • | — | • |
Note:
- Listed for all hazards.
- Dry Upright Sprinklers require a minimum operating pressure of 12 psi.
- * Dry Upright - FM Approved 155°F, 200°F, and 286°F.
Cross Section
Click image above for a detailed view of this product
Important Installation Data
Globe GL Series Dry Upright sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the end fitting. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
The GL Series Dry Sprinkler must not be installed in a short radius 90° elbow. When installing in other than an iron tee, the clearances between the end of the sprinkler and fitting should be checked.
For further important installation data, please refer to our Dry Sprinkler Caution Sheet.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- "B" Dimension - Distance from face of fitting to the top of the deflector
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Horizontal Sidewall
A-93 Dry Type Horizontal Sidewall Sprinkler
GL Series Dry Type Horizontal Sidewall Recessed Horizontal Sidewall
Description and Operation
The Globe GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples.
The Globe GL Series Dry Type Horizontal Sidewall Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is -67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with glycerin solution, 5mm
- Orifice insert - brass
3/4" or 1" NPT - Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable FM Variable to |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester Black Polyester Lead Coated1 Wax Coated1 Wax Over Lead1 |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order
- Wax Coating cULus listed up to 200°F - cULus listed corrosion resistant: Polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | *FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Horizontal Sidewall |
GL5685a | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5686a | 5.6 | 3/4" NPT | • | • | • | • | • | • | – | • | |
| GL8185b | 8.1 | 1" NPT | • | • | • | • | • | • | – | • | |
| Recessed Horizontal Sidewall |
GL5685a | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5686a | 5.6 | 3/4" NPT | • | • | • | • | • | • | – | • | |
| GL8185b | 8.1 | 1" NPT | • | • | • | • | • | • | – | • |
Note:
- aListed for light hazard only with deflector from 4" to 12" below the ceiling.
- bListed for light and ordinary harzard with deflector from 4" to 12" below the ceiling.
- * Dry Horizontal Sidewall - FM Approved 155°F, 200°F, and 286°F only.
- * Dry Recessed Horizontal Sidewall - FM Approved 155°F and 200°F only.
Cross Sections

Important Installation Data
Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- Escutcheon desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Concealed Pendent
A-92 Dry Type Adjustable (Dome) Concealed Pendent Sprinkler
GL Series Dry Type Adjustable Concealed Pendent
Description and Operation
The Globe GL Series Dry Type Adjustable Concealed Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. It offers the ultimate in low profile, aesthetically pleasing appearance. The sprinkler is available with 1/2" of adjustment and a deeper profile ceiling plate, 3 5/16" diameter, color finished to match the specifier's exact requirements. Globe's Dry Adjustable Concealed Sprinkler utilizes a frangible 5mm glass bulb type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move; allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern.
A special spring is attached to the pendent deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
The heart of Globe's GL Series sprinkler proven actuation assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass cdischarge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring Assembly - teflon coated nickel alloy and brass
- Bulb - glass with glycerin solution, 5mm size
- Orifice insert - brass
- 3/4" or 1" NPT
- Stabilizer bar - bronze
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length* | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | Variable to 48" |
Bright Chrome White Polyester 1Satin Chrome 1Bright Brass 1Other Painted Finishes |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- *cULus listed for up to a 48" "A" dimension.
- 1Finishes available on special order. Painted plates other than white require customer to furnish paint. Contact Globe for paint specification.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F (57°C) w/plate 135°F (57°C) | 155°F (68°C) w/plate 135°F (68°C) | 155°F (68°C) w/plate 155°F (68°C) | 175°F (79°C) w/plate 155°F (68°C) | 200°F (93°C) w/plate 155°F (68°C) | *cULus |
|---|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL5677 | 5.6 | 1" NPT | • | • | • | • | • | • |
| GL5678 | 5.6 | 3/4" NPT | • | • | • | • | • | • | |
| GL8177 | 8.1 | 1" NPT | • | • | • | • | • | • |
Note: *Listed for all hazards
Cross Section

Click image above for a detailed view of this product
Important Installation Data
Globe GL Series Dry Concealed sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327119
- "A" Dimension - Distance from face of fitting to the
finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Concealed Pendent
A-91 Dry Type Concealed Pendent Sprinkler
GL Series Dry Type Concealed Pendent
Description and Operation
The Globe GL Series Dry Type Concealed Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. It offers the ultimate in low profile, aesthetically pleasing appearance. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Dry Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Dry Concealed Sprinkler utilizes its frangible 5mm glass bulb type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern.
A special spring is attached to the pendent deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
The heart of Globe's GL Series sprinkler proven actuation assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with glycerin solution, 5mm size
- Orifice insert - brass
- 3/4" or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable to FM Variable to |
Bright Chrome White Polyester 1Satin Chrome 1Bright Brass 1Other Painted Finishes |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- Painted plates other than white require customer to furnish paint. Contact Globe for paint specification.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F (57°C) w/plate 135°F (57°C) | 155°F (68°C) w/plate 135°F (68°C) | 155°F (68°C) w/plate 155°F (68°C) | 175°F (79°C) w/plate 155°F (68°C) | 200°F (93°C) w/plate 155°F (68°C) | cULus | * FM |
|---|---|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL5681 | 5.6 | 1" NPT | • | • | • | • | • | • | • |
| GL5682 | 5.6 | 3/4" NPT | • | • | • | • | • | • | ||
| GL8181 | 8.1 | 1" NPT | • | • | • | • | • | • |
Note: Listed for all hazards
* Concealed Pendent style - FM Approvals 135° F Cover & 155° F Sprinkler; 155° F Cover & 200° F Sprinkler
Cross Section
Click image above for a detailed view of this product
Installation Data
Globe GL Series Dry Concealed sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327119
"A" Dimension - Distance from face of fitting to the
finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Pendent
A-90 Dry Type Pendent Sprinkler
Model GL5679, GL8179 Dry Type Pendent Recessed Pendent
Description and Operation
The Globe GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe GL Series Dry Type Pendent Sprinkler utilizes a frangible glass ampule sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm
- Orifice insert - brass
- 3/4" or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester Black Polyester Lead Coated1 Wax Coated1 Wax over Lead1 |
| 8.1 | (116 metric) | 1" NPT | FM Variable to 36" |
|
Note:
- Metric conversions are approximate.
- cULus listed corrosion resistant: Polyester must be specified on order.
- 1Finishes available on special order.
- Wax Coating cULus listed up to 200°F
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | *FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Pendent | GL5679 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5680 | 5.6 | ¾" NPT | • | • | • | • | • | • | – | • | |
| GL8179 | 8.1 | 1" NPT | • | • | • | • | • | • | – | • | |
| Recessed Pendent |
GL5679 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5680 | 5.6 | ¾" NPT | • | • | • | • | • | • | – | • | |
| GL8179 | 8.1 | 1" NPT | • | • | • | • | • | • | – | • |
Note:
- Listed for all hazards
- * Dry Recessed Pendent - FM Approved 155°F and 200°F only.
- * Dry Pendent - FM Approved 155°F, 200°F, and 286° only.
Cross Section

Installation Data
Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- Escutcheons desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Extra Large Orifice
A-82 ELO 231/13 Upright Sprinkler - GL1167
Model GL1167 Extra Large Orifice For Use in NFPA 13, 231, 231C, 231D, & 231F Systems
Description and Operation
The Globe Model GL1167 Extra Large Orifice Upright Sprinkler is intended for use in NFPA 13, 231, 231C, 231D and 231F Systems, when installed in accordance with the Standard Sprinkler Positioning and area / density flow calculation requirements as specified in each respective standard. When acceptable to the Authority having Jurisdiction the Model GL1167 Sprinkler may be used as a "special application" sprinkler when installed to protect single, double and multiple-row and portable rack storage of Class I - IV group A and B plastics, cartoned, expanded or unexpanded, as well as exposed unexpanded with a maximum storage height of 20 feet, maximum ceiling height of 25 feet, 36 inches minimum deflector to top of storage clearance, design density of 0.60 gpm/sq. ft., and a design area of 2,000 sq. ft. for wet systems or 2,600 sq. ft. for dry systems.
The Model GL1167 Sprinkler is a low profile yet durable design which utilizes a 5mm frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it serves to protect various area coverages. This sprinkler series is available in the upright style and several temperature ratings and finishes to meet varying design requirements.
The heart of Globe's Model GL1167 sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)
- Water Working Pressure Rating - 175 psi (12 Bars)
- Minimum Operating Pressure - 10 psi (0.7 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is -67°F (-55°C).
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 11.5 | (166 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Upright | GL1167 | 11.5 | • | • | • | • | • | • |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Extra Large Orifice
A-80 ELO 13 Pendent Sprinkler - GL1160
Model GL1160 Extra Large Orifice Automatic Sprinklers For Use in NFPA 13 Systems
Description and Operation
The Globe Model GL1160 Extra Large Orifice Sprinkler for use in NFPA 13 Systems is a low profile yet durable design which utilizes a 5mm frangible glass ampule as the thermosensitive element. The main use of this sprinkler is when minimal pressure is available and the use of smaller size orifice sprinklers would require the installation of a pump. This sprinkler series is available in various styles, temperature ratings and several finishes to meet many varying design requirements.
The heart of Globe's Model GL1160 sprinkler proven actuating assembly is a hermetically sealed frangible glass am- pule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 11.5 | (166 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Pendent | GL1160 | 11.5 | • | • | • | • | • | • |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Horizontal Sidewall
A-77 Extended Coverage Light Hazard Horizontal Sidewall Sprinkler - GL8128, GL8129 & GL8174
Extended Coverage Light Hazard Model GL8128, GL8129, GL8174 Horizontal Sidewall
Description and Operation

The Globe Models GL8128, GL8129 and GL8174 Extended Coverage Horizontal Sidewall Sprinklers are a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it serves to protect various area coverages and should be installed in accordance with NFPA 13. This sprinkler series is available in various temperature ratings and several finishes to meet many varying design requirements.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C), 155°F (68°C),
200°F (93°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 200°F | 93°C | Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 8.1 | (116 metric) | 3/4" NPT | 3" (7.6 cm) | Factory Bronze 1Satin Chrome Bright Chrome White Polyester2 Black Polyester2 1Lead Coated |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F 57°C | 155°F 68°C | 200°F 93°C | †cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|
| Sidewall | GL8128 | 8.1 | — | • | • | • | • |
| GL8129 | — | • | • | • | • | ||
| GL8174 | • | — | — | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| *SIN Model | Style | TEMP | Ceiling to deflector distance | Width of coverage | Length of coverage | MIN. PRESSURE P.S.I. | FLOW G.P.M. |
|---|---|---|---|---|---|---|---|
| GL8128 GL8129 |
Standard & Recessed |
135°F / 57°C 155°F / 68°C **200°F / 93°C |
4" TO 6" 6" TO 12" |
16' | 16' | QR Models Shown on Page A-46 | |
| 18' | |||||||
| 20' | 16.6 | 33 | |||||
| 22' | 20.8 | 37 | |||||
| ***24' | 26.8 | 42 | |||||
| GL8174 | Standard & Recessed |
135°F / 57°C | 12" TO 18" | 16' | 16' | 12.0 | 28 |
| 18' | 14.6 | 31 | |||||
| 20' | 18.7 | 35 | |||||
| 22' | 20.8 | 37 | |||||
Note:
*Minimum 6' sprinkler spacing.
**200°F Sprinkler not listed for 16' x 22' OR 16' x 24'.
*** 24' Coverages not listed for recessed installations.
Cross Section
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Pendent
A-76 Extended Coverage Light Hazard Pendent Sprinkler - GL8159
Extended Coverage Light Hazard Model GL8159 Pendent
Description and Operation
The Globe Model GL8159 Extended Coverage Pendent Sprinkler for Light Hazard occupancies is a low profile yet durable design which utilizes a 5mm frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it serves to protect various light hazard area coverages and should be installed in accordance with NFPA 13. This sprinkler series is available in four temperature ratings and several finishes to meet many varying design requirements.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (74°C)
200°F (93°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin based solution, 5mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 8.1 | (116 metric) | 3/4" NPT | 3" (7.6 cm) | Factory Bronze 1Satin Chrome Bright Chrome White Polyester2 Black Polyester2 1Lead Coated |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as UL listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | cULus |
|---|---|---|---|---|---|---|---|
| Pendent | GL8159 | 8.1 | • | • | • | • | • |
*1/2 Orifice listed for all hazards
U.L. Listing Design - Use Requirements For Light Hazards
| Style | TEMP | Area of Coverage | MIN. PRESSURE P.S.I. | Flow in G.P.M. |
|---|---|---|---|---|
| Standard Pendent Recessed Pendent |
135°F / 57°C 155°F / 68°C 175°F / 79°C 200°F / 93°C |
16' x 16' | 10.3 | 26 |
| 18' x 18' | 16.6 | 33 | ||
| 20' x 20' | 24.4 | 40 |
Note: Due to the high spray pattern created by the spinkler, there must be a minmum spacing of 8'-0" between sprinklers to eliminate the risk of cold soldering.
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 312366
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Intermediate In-Rack Storage Sprinklers
A-75 Intermediate Level Sprinkler
GL Series Intermediate Level Upright/Pendent
Description and Operation
The Globe GL Series Intermediate Level Sprinklers are primarily designed for use in rack storage sprinkler systems, where their thermosensitive elements must be shielded from the water spray of higher elevation sprinklers which could operate earlier during a fire. The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element.
The Globe Intermediate Level Sprinklers are available in either upright or pendent styles, with 1/2" or 17/32" orifices, in several temperature ratings and with various finishes to meet customer requirements. Each unit is factory fitted with a water shield having a 3 25/32" diameter. Either style may be provided with sprinkler head guards for use where mechanical injury might be expected.
The heart of Globe’s GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C),
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin based solution, 5mm size
- Shield - brass or steel - 3 25/32" diameter
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes1 | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) |
Factory Bronze |
| 7.8 | (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- 1Finishes available on request.
Approvals
| Style | Sin Model | K Factor | 135° 57°C | 155°F 68°C | 175°F 79°C | 200°F 93°C | 286°F 141°C | cULus | FM | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|
| Upright |
GL5663 | 5.6 | • | • | • | • | • | • | • | • |
| GL8163 | 7.8* | • | • | • | • | • | • | - | • | |
| GL8166 | 8.1 | • | • | • | • | • | • | • | • | |
| Pendent | GL5672 | 5.6 | • | • | • | • | • | • | • | • |
| GL8172 | 7.8* | • | • | • | • | • | • | • | • | |
| GL8158 | 8.1 | • | • | • | • | • | • | • | • |
*17/32" X 1/2" NPT.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » High Pressure Sprinklers
A-73 High Pressure Model GL5657 Adjustable Concealed Pendent
High Pressure Model GL Series Adjustable Concealed Pendent
Description and Operation
The Globe High Pressure Model GL Series Concealed Pendent Sprinkler offers the ultimate in low profile, aesthetically pleasing appearance. It is available with 1/2" of adjustment, and may be used in areas where flowing and static pressure do not exceed 300 psi. Globe's Concealed Sprinkler utilizes its frangible glass ampule type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens discharging water onto the floor in its required and approved distribution pattern.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate;
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate;
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate;
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate;
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate. - Water Working Pressure Rating - 300 psi (21 Bars).
- Factory tested hydrostatically to 850 psi (59 Bars).
- Maximum low temperature glass bulb rating is
-67°F (-55°C). - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size.
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes1 | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) |
Bright Chrome White Painted Bright Brass Other Painted Finishes |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white required customer to finish paint.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL5657 | 5.6* | • | • | • | • | • |
*1/2 Orifice listed for all hazards
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 325391
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » High Pressure Sprinklers
A-72 High Pressure Concealed Pendent Sprinkler - GL5655
High Pressure Model GL5655 Concealed Pendent
Description and Operation
The Globe High Pressure Model GL5655 Concealed Pendent Sprinkler offers the ultimate in low profile, aesthetically pleasing appearance. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate color finished to match the specifier's exact requirements. The Model GL5655 Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling, and may be used in areas where flowing and static pressure do not exceed 300 psi. Globe's Concealed Sprinkler utilizes its frangible glass ampule type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens discharging water onto the floor in its required and approved distribution pattern.
A special spring is attached to the pendent sprinkler deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 300 psi (21 Bars)
- Factory tested hydrostatically to 850 psi (59 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes1 | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) |
Bright Chrome White Painted Bright Brass Other Painted Finishes |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white required customer to finish paint.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL5655 | 5.6* | • | • | • | • | • |
*1/2 Orifice listed for all hazards
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 325391
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent
A-71 Adjustable Concealed (Dome) Pendent Sprinkler
GL Series Adjustable Concealed Pendent
Description and Operation
The Globe GL Series Adjustable Concealed Pendent Sprinkler offers the ultimate in low profile, aesthetically pleasing appearance. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate color finished to match the specifier's exact requirements. The Sprinkler is available with 1/2" of adjustment and a deeper profile cover plate assembly. The GL Series Adjustable Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Adjustable Concealed Sprinkler utilizes its frangible glass ampule type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens discharging water onto the floor in its required and approved distribution pattern.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin based solution, 5mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/2" (6.4 cm) |
Bright Chrome White Painted Bright Brass1 Satin Chrome1 Other Painted Finishes1 |
| 4.2 | (59 metric) | 1/2" NPT | ||
| 5.6 | (80 metric) | 1/2" NPT | ||
| 8.1 | (116 metric) | 3/4" NPT | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white required customer to finish paint.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus |
|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL2856 | 2.8 | • | • | • | • | • | • |
| GL4256 | 4.2 | • | • | • | • | • | • | |
| GL5656 | 5.6:* | • | • | • | • | • | • | |
| GL8173 | 8.1* | • | • | • | • | • | • |
:*Listed For All Hazards
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 325391
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent
A-70 Concealed Pendent Sprinkler
GL Series Concealed Pendent
Description and Operation
The Globe GL Series Concealed Pendent Sprinkler offers the ultimate in low profile, aesthetically pleasing appearance. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate color finished to match the specifier's exact requirements. The Sprinkler is available with 1/8" adjustment and a low profile cover plate assembly. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its frangible glass ampule type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens discharging water onto the floor in its required and approved distribution pattern.
A special spring is attached to the pendent sprinkler deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is -67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/2" (6.4 cm) |
Bright Chrome White Painted Bright Brass1 Satin Chrome1 Other Painted Finishes1 |
| 4.2 | (59 metric) | 1/2" NPT | ||
| 5.6 | (80 metric) | 1/2" NPT | ||
Note:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white required customer to finish paint.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus | FM | LPC | CE | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL2854 | 2.8 | • | • | • | • | • | • | — | — | — | • |
| GL4254 | 4.2 | • | • | • | • | • | • | — | — | — | • | |
| GL5654 | 5.6 | • | • | • | • | • | • | • | • | • | • |
Cross Sections
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » "The Inch" - One Inch Adjustable Pendent
A-69 "The Inch" One Inch Adjustable Concealed Pendent - GL5653
"The Inch" Model GL5653 One Inch Adjustable Concealed Pendent
Description and Operation
The Globe GL5653 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 2¾" diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 5mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 5mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire.
Technical Data
- Temperature Ratings - 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating
is -67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 5mm size
- Drop Pin - stainless steel
- Cover Plate - brass
- Upper Escutcheon Assembly - plated steel
Note:Globe's wrench P/N 332765 must be used to install the sprinkler.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 1/2" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted Bright Brass1 Satin Chrome Other Painted Finishes1 |
Note:
- Metric conversions are approximate.
- 1 Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus | FM |
NYC-DOS |
|---|---|---|---|---|---|---|---|---|---|---|
| Adjustable Concealed Pendent |
Cross Sections
Click image above for a detailed view of this product.
| Optional Cover Plate Sizes | WHITE 135°F PART # | WHITE 155°F PART # | CHROME 135°F PART # | CHROME 155°F PART # |
|---|---|---|---|---|
| 2 3/4" | 332726 | 332731 | 332724 | 332729 |
| 3 5/16" | 332706 | 332711 | 332704 | 332709 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Adjustable Concealed Wrenches - P/N 332765
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » High Pressure Sprinklers
A-68 High Pressure Recessed Sprinkler
High Pressure Model GL Series Recessed Pendent
Description and Operation
The Globe High Pressure Model GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it offers greatly increased safety to life and the ability to be used in areas where flowing and static pressure do not exceed 300 psi. This sprinkler series is available in various orifices, temperature ratings and finishes to meet varying design requirements.
The heart of Globe’s Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C),
200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 300 psi (21 Bars)
- Factory tested hydrostatically to 850 psi (59 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Orifice Size | Nominal 'K' Factor | Thread Size | Length | Finishes | ||
|---|---|---|---|---|---|---|
| 1/2" | (15 mm) | 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze Bright Chrome White Polyester1 Black Polyester1 Lead Coated2 |
| 17/32" | (20 mm) | 7.8 | (111 metric) | 1/2" NPT | *2 1/4" (5.7 cm) | |
| 17/32" | (20 mm) | 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- *Excluding pintle.
- 1Available as U.L. and C-U.L. listed corrosion resistant when specified on order.
- 2 Finishes available on special order.
Approvals
| Style | Sin Model | Orifice Size | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | 286°F 141°C | †cULus |
|---|---|---|---|---|---|---|---|---|
| Pendent Recessed |
GL5652 | 5.6 | • | • | • | • | • | • |
| GL8152 | 7.8* | • | • | • | • | • | • | |
| GL8157 | 8.1 | • | • | • | • | • | • |
Note:
- † 1/2" Orifice and 17/32" orifice listed for all hazards.
- *17/32" X 1/2" NPT.
Cross Sections
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325391, Rev. F (1/2"); P/N 325401, Rev. D (L.O.)
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Standard Response - Standard Spray Sprinkler
A-67 Recessed Pendent & Horizontal Sidewall Sprinkler
GL Series Recessed Pendent Recessed Horizontal Sidewall
Description and Operation
The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements.
The heart of Globe’s GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. Assembly is done in the field.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C),
200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length1 | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze Satin Chrome2 Bright Chrome White Polyester3 Black Polyester3 Lead Coated2 |
| 4.2 | (59 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 7.8 | (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- 1 Horizontal Sidewall is 2 9/16".
- 2 Finishes available on special order.
- 3 Available as cULus listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | **286°F 141° C | †cULus | FM | LPC | CE | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Pendent Recessed |
GL2851 | 2.8 | • | • | • | • | • | • | — | — | — | • |
| GL4251 | 4.2 | • | • | • | • | • | • | — | — | — | • | |
| GL5651 | 5.6 | • | • | • | • | • | • | • | • | • | • | |
| GL8151* | 7.8* | • | • | • | • | • | • | • | — | — | • | |
| GL8156 | 8.1 | • | • | • | • | • | •$ | • | • | • | • | |
| § Horizontal Sidewall Recessed |
GL2870 | 2.8 | • | • | • | • | • | • | — | — | — | • |
| GL4270 | 4.2 | • | • | • | • | • | • | — | — | — | • | |
| GL5670 | 5.6 | • | • | • | • | • | • | — | — | — | • | |
| GL8171 | 8.1 | • | • | • | • | • | • | — | — | — | — |
Note:
- § Horizontal sidwall cULus listed for deflector 4" to 12" below the ceiling.
- † 5.6K Orifice, 7.8K Orifice and 8.1K Orifice listed for all hazards.
- *7.8" X 1/2" NPT
- ** 286°F cULus listed only.
$ Brass finish only
Cross Section
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Recessed Wrenches - P/N 325391, Rev. F (1/2"); P/N 325401, Rev. D (L.O.)
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » High Pressure Sprinklers
A-66 High Pressure Model GL Series Upright / Pendent Sprinkler
High Pressure Automatic Sprinklers Model GL Series Upright / Pendent
Description and Operation
The Globe Model GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified, and has been evaluated for use where static or flowing pressures are 300 psi or below. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. Assembly is done in the field.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C), 200°F (93°C),
286°F (141°C), 360°F (182°C) - Water Working Pressure Rating - 300 psi (21 Bars)
- Factory tested hydrostatically to 850 psi (59 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Orifice Size | Nominal 'K' Factor | Thread Size | Length | Finishes | ||
|---|---|---|---|---|---|---|
| 1/2" | (15 mm) | 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
| 17/32" | (20 mm) | 7.8 | (111 metric) | 1/2" NPT | *2 1/4" (5.7 cm) | |
| 17/32" | (20 mm) | 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- *Excluding Pintle
- 1 Finishes available on special order.
- 2 Available as U.L. and C-U.L. listed corrosion resistant- when specified on order.
Approvals
| Style | Sin Model | K Factor | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | 286°F 141° C | cULus |
|---|---|---|---|---|---|---|---|---|
| Upright | GL5662 | 5.6 | • | • | • | • | • | • |
| GL8162 | 7.8* | • | • | • | • | • | • | |
| GL8165 | 8.1 | • | • | • | • | • | • | |
| Pendent | GL5652 | 5.6 | • | • | • | • | • | • |
| GL8152 | 7.8* | • | • | • | • | • | • | |
| GL8157 | 8.1 | • | • | • | • | • | • |
Note:
- *17/32" X 1/2" NPT
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Standard Response - Standard Spray Sprinkler
A-65 Standard Sprinkler (Upright, Pendent, Sidewall, and Conventional)
GL Series Upright • Pendent Vertical Sidewall Horizontal Sidewall Conventional (Old Style)
Description and Operation
The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified. This sprinkler series is available in various styles, orifices, temperature ratings and finishes to meet varying design requirements.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. Assembly is done in the field.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C), 200°F (93°C) ,
286°F (141°C), 360°F (182°C) - 500°F (260°C) Available Upon Request Without Approvals
- Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with glycerin solution, 5mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
| Extra High | 360°F | 182°C | Mauve | 300°F | 149°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length1 | Finishes | |
|---|---|---|---|---|
| 2.8 | (39 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze Satin Chrome2 Bright Chrome4 White Polyester4 Black Polyester4 Wax Coated3,4 Lead Coated2,4 Wax over Lead3,4 |
| 4.2 | (59 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 5.6 | (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 7.8 | (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 | (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) | |
Note:
- Metric conversions are approximate.
- 1 Horizontal Sidewall is 2 9/16".
- 2 Finishes available on special order.
- 3 Wax Coating UL listed up to 200°F only.
- 4 cULus listed corrosion resistant- Polyester must be specified on order.
Approvals
| Style | Sin Model | Orifice Size | 135° 57° | 155° 68° | 175° 79° | 200° 93 | 286° 141° | 360° 182° | cULus | FM | LPC | CE | "NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Upright | GL2861 | 2.8 | • | • | • | • | • | • | • | – | – | – | • |
| GL4261 | 4.2 | • | • | • | • | • | • | • | – | – | – | • | |
| GL5661 | 5.6 | • | • | • | • | • | • | • | • | • | • | • | |
| GL8161 | 7.8* | • | • | • | • | • | • | • | - | – | – | • | |
| GL8164 | 8.1 | • | • | • | • | • | • | • | • | • | • | • | |
| Pendent | GL2851 | 2.8 | • | • | • | • | • | • | • | – | – | – | • |
| GL4251 | 4.2 | • | • | • | • | • | • | • | – | – | – | • | |
| GL5651 | 5.6 | • | • | • | • | • | • | • | • | • | • | • | |
| GL8151 | 7.8* | • | • | • | • | • | • | • | • | – | – | • | |
| GL8156 | 8.1 | • | • | • | • | • | • | • | • | • | • | • | |
| Vertical Sidewall † |
GL5675 | 5.6 | • | • | • | • | • | • | • | • | – | – | • |
| GL8176 | 8.1 | • | • | • | • | • | • | • | – | – | – | • | |
|
Horizontal |
GL2870 | 2.8 | • | • | • | • | • | • | • | – | – | – | • |
| GL4270 | 4.2 | • | • | • | • | • | • | • | – | – | – | • | |
| GL5670 | 5.6 | • | • | • | • | • | • | • | • | – | – | • | |
| GL8171 | 8.1 | • | • | • | • | • | • | • | – | – | – | – | |
| Conventional (Old Style) |
GL5668 | 5.6 | • | • | • | • | • | • | – | – | • | • | – |
| GL8169 | 8.1 | • | • | • | • | • | • | – | – | • | • | – |
Note:
- § Horizontal sidewall UL listed for deflector 4" to 12"below the ceiling, FM approved 4" to 6".
- † Vertical sidewall UL listed for light hazard only.
Pendent vertical sidewall UL listed for 6' min. spacing.
Upright vertical sidewall UL listed for 9' min. spacing. - *1/2" NPT
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Size
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.)
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Sprinkler Vertical Sidewall
A-59 Dry Type Vertical Sidewall Sprinkler
Automatic Sprinklers GL Series Dry Type Vertical Sidewall Upright & Pendent
Description and Operation
The Globe Quick Response GL Series Dry Type Vertical Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe Quick Response GL Series Dry Type Vertical Sidewall Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern. While the Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C), 200°F (93°C),
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length1 | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | Variable to 48" |
Factory Bronze 2Satin Chrome Bright Chrome White Polyester3 Black Polyester3 2Lead Coated |
| 8.1 | (116 metric) | 1" NPT | ||
NOTE:
- Metric conversions are approximate.
- 1 cULus listed for up to A 48" "A" dimension.
- 2 Finishes available on special order.
- 3 cULus listed corrosion resistant- Polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | Thread Size | 155° F 68° C | 175° F 79° C | 200° F 93° C | 286°F 141° C | *cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|
| Vertical Sidewall |
GL5643 | 5.6 | 1" NPT | • | • | • | • | • | • |
| GL5644 | 5.6 | ¾" NPT | • | • | • | • | • | • | |
| GL8143 | 8.1 | 1" NPT | • | • | • | • | • | • |
NOTE:
- * ¾" NPT x 5.6K orifice and 1" NPT x 8.1K orifice cULus listed for ordinary hazard.
- Pendent vertical sidewall cULus listed for 6' min. spacing.
- Upright vertical sidewall cULus listed for 9' min. spacing.
Cross Section

Installation Data
Globe GL Series Dry Vertical sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the end fitting. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
The GL Series Dry Sprinkler must not be installed in a short radius 90° elbow. When installing in other than an iron tee, the clearances between the end of the sprinkler and fitting should be checked.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Escutcheons desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used; "B" Dimension - Distance from face of fitting to the top of the deflector.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Upright
A-60 Dry Type Upright Sprinkler
Automatic Sprinklers GL Series Dry Type Upright
Description and Operation
The Globe Quick Response GL SeriesDry Type Upright Sprinkler is designed for use in special applications such as freezing environments. As an example, they may be efficiently used when connected to a wet type sprinkler system and extended into an unheated attic space.
The Globe Quick Response GL Series Dry Type Upright Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C), 200°F (93°C),
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus Variable FM Variable |
Factory Bronze 1Satin Chrome Bright Chrome White Polyester Black Polyester 2Lead Coated |
| 8.1 | (116 metric) | 1" NPT | ||
NOTE:
- Metric conversions are approximate.
- cULus listed corrosion resistant- Polyester must be specified on order.
- 1 Finishes available on special order.
- 2 Lead coated is UL approved only.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | 286°F 141° C | *FM | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Upright | GL5639 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5640 | 5.6 | 3/4" NPT | • | • | • | • | • | – | • | • | |
| GL8139 | 8.1 | 1" NPT | • | • | • | • | • | – | • | • |
NOTE:
- Listed for all Harzards
- Dry Upright Sprinklers require a minimum operating pressure of 12psi
- * Dry Upright - FM Approved 155°F, 200°F, and 286°F only.
Cross Section
Click image above for a detailed view of this product.
Important Installation Data
Globe GL Series Dry Upright sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
The GL Series Dry Sprinkler must not be installed in a short radius 90° elbow. When installing in other than an iron tee, the clearances between the end of the sprinkler and fitting should be checked.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- "B" Dimension - Distance from face of fitting to the top of the deflector.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Horizontal Sidewall
A-58 Dry Type Horizontal Sidewall Sprinkler
Automatic Sprinklers GL Series Dry Type Horizontal Sidewall Recessed Horizontal Sidewall
Description and Operation
The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples.
The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)
- Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length2 | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT |
cULus FM |
Factory Bronze 1Satin Chrome Bright Chrome White Polyester Black Polyester 2Lead Coated |
| 8.1 | (116 metric) | 1" NPT | ||
Note:
- Metric conversions are approximate.
- cULus listed corrosion resistant: Polyester must be specified on order.
- 1 Finishes available on special order.
- 2Lead Coated is UL approved only.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135° F 57° C | 155° F 68° C | 175° F 79° C | 200° F 93° C | 286°F 141° C | *FM | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Horizontial Sidewall |
GL5641 | 5.6a | 1" NPT | • | • | • | • | • | • | • | • |
| GL5642 | 5.6a | 3/4" NPT | • | • | • | • | • | • | • | ||
| GL8141 | 8.1b | 1" NPT | • | • | • | • | • | • | • | ||
| Recessed Horizontial Sidewall |
GL5641 | 5.6a | 1" NPT | • | • | • | • | • | • | • | • |
| GL5642 | 5.6a | 3/4" NPT | • | • | • | • | • | • | • | ||
| GL8141 | 8.1b | 1" NPT | • | • | • | • | • | • | • |
Note:
- aListed for light hazard only with deflector from 4" - 12" below the ceiling.
- bListed for light and ordinary hazard with deflector from 4" - 12" below the ceiling.
- * Recessed Horizontal Sidewall - FM Approved 155°F and 200°F only.
- * Horizontal Sidewall - FM Approved 155°F, 200°F, and 286°F only.
Cross Sections

Important Installation Data
Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit
Recessed) - Escutcheons desired
- "A" Dimension - Distance from face of fitting to the finished ceiling regardless of escutcheon used.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Concealed Pendent
A-57 Dry Type Adjustable Concealed (Dome) Pendent Sprinkler
Automatic Sprinklers GL Series Dry Type Adjustable Concealed Pendent
Description and Operation
The Globe Quick Response GL Series Dry Type Adjustable Concealed Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. It offers the ultimate in low profile, aesthetically pleasing appearance. The sprinkler is available with 1/2" of adjustment and a deeper profile ceiling plate, 3 5/16" in diameter, color finished to match the specifier's exact requirements. The quick response sprinkler offers the additional feature of greatly increased safety to life, with operation approximately six times faster than ordinary sprinklers and should be used advisedly and under the direction of approving authorities having jurisdiction. Globe's Dry Adjustable Concealed Sprinkler utilizes its frangible 3mm glass bulb type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern.
The heart of Globe's GL Series sprinkler proven actuation assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings
- 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
- 155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
- 175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
- 200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
- Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length2 | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | Variable to 48" | Bright Chrome White Painted 1Satin Chrome 1Bright Brass 1Other Painted Finishes |
| 8.1 | (116 metric) | 1" NPT | ||
NOTE:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white require customer to furnish paint. Contact Globe for paint specification.
- 2cULus listed for up to a 48" "A" dimension.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135° F (57° C) w/plate 135° F (57° C) | 155° F (68° C) w/plate 135° F (68° C) | 175° F (79° C) w/plate 155° F (68° C) | 200° F (93° C) w/plate 155° F (68° C) | *cULus |
|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL5649 | 5.6 | 1"NPT | • | • | • | • | • |
| GL5622 | 5.6 | 3/4 NPT | • | • | • | • | • | |
| GL8149 | 8.1 | 1" NPT | • | • | • | • | • |
NOTE:
- *Listed for ALL hazards
Cross Sections
Click image above for a detailed view of this product.
Important Installation Data
Globe GL Series Dry Concealed sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327119
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Concealed Pendent
A-56 Dry Type Concealed Pendent Sprinkler - GL5637
Automatic Sprinklers GL Series Dry Type Concealed Pendent
Description and Operation
The Globe Quick Response GL Series Dry Type Concealed Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples. It offers the ultimate in low profile, aesthetically pleasing appearance. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate color finished to match the specifier's exact requirements. The Quick Response GL Series Dry Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. The quick response sprinkler offers the additional feature of greatly increased safety to life, with operation approximately six times faster than ordinary sprinklers and should be used advisedly and under the direction of approving authorities having jurisdiction. Globe's Dry Concealed Sprinkler utilizes its frangible 3mm glass bulb type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The plate is soldered to the sprinkler special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern.
A special spring is attached to the pendent deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings
- 135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
- 155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
- 155°F (68°C) Sprinkler, 155°F (57°C) Cover Plate
- 175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
- 200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
- Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm
- Orifice insert - brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes | |
|---|---|---|---|---|
| 5.6 | (80 metric) | 3/4" or 1" NPT | cULus Variable to 48" FM Variable to 36" |
Bright Chrome White Painted 1Satin Chrome 1Bright Brass 1Other Painted Finishes |
| 8.1 | (116 metric) | 1" NPT | ||
NOTE:
- Metric conversions are approximate.
- 1Finishes available on special order. Painted plates other than white require customer to furnish paint. Contact Globe for paint specification.
Approvals
| Style | Sin Model | K Factor | Thread Size |
135° F | 155° F (68° C) w/plate 135° F (57° C) | 155°F (68°C) w/plate 155°F (68°C) | 175° F (79° C) w/plate 155° F (68° C) | 200° F (93° C) w/plate 155° F (68° C) | *FM | cULus |
NYC- |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Con- cealed Pen- dent |
GL5637 | 5.6 | 1"NPT | • | • | • | • | • | • | • | • |
| GL5638 | 5.6 | 3/4 NPT | • | • | • | • | • | - | • | • | |
| GL8137 | 8.1 | 1" NPT | • | • | • | • | • | - | • | • |
Note:
- Listed for ALL hazards
- *Concealed Pendent style - FM Approvals 135° F Cover & 155° F Sprinkler; 155° F Cover & 200° F Sprinkler
- *FM Approved as Standard Response.
Cross Sections
Click image above for a detailed view of this product.
Important Installation Data
Globe GL Series Dry Concealed sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327119
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Extra Large Orifice
A-50 ELO 231/13 Upright Sprinkler - GL1123
Model GL1123 Pendent Extra Large Orifice Automatic Sprinklers For Use in NFPA 13, 231,231C, 231D & 231F Systems
Description and Operation
The Globe Quick Response Model GL1123 Extra Large Orifice Upright Sprinkler is intended for use in NFPA 13, 231, 231C, 231D and 231F Systems when installed in accordance with the Standard Sprinkler Positioning and area / density flow calculation requirements as specified in each respective standard. This sprinkler is intended for use in wet systems only when used for storage applications. When acceptable to the Authority having Jurisdiction the Model GL1123 Sprinkler may be used as a "special application" sprinkler when installed to protect single, double and multiple-row and portable rack storage of Class I - IV group A and B plastics, cartoned, expanded or unexpanded, as well as exposed unexpanded with a maximum storage height of 20 feet, maximum ceiling height of 25 feet, 36 inch minimum deflector to top of storasystems only.
The Model GL1123 is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. While the sprinkler provides an aesthetically pleasing appearance, it serves to protect various area coverages. This sprinkler series is available in the upright style, and several temperature ratings and finishes to meet varying design requirements.
The heart of Globe's Model GL1123 sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 155°F (68°C)
175°F (79°C), 200°F (93°C), 286°F (141°C). - Water Working Pressure Rating - 175 psi (12 Bars)
- Minimum Operating Pressure - 10 psi (.7 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 155°F | 68°C | Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Lenth | Finishes |
|---|---|---|---|
| 11.5 (166 metric) | 3/4" NPT | 2 7/16 (6.19cm) |
Factory Bronze |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as UL listed corrosion resistant - when specified on order.
Approvals
| Style | Sin Model | K Factor | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | 286°F (141°C) | cULus | NYC - DOB MEA - 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Upright | GL1123 | 11.5 | • | • | • | • | • | • |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
Product Related Documents
Download this page as a pdfDry Sprinklers » Dry Type Pendent
A-55 Dry Type Pendent Sprinkler
Automatic Sprinklers GL Series Dry Type
Description and Operation
The Globe Quick Response GL Series Dry Type Pendent Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
The Globe Quick Response GL Series Dry Type Pendent Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings - 135°F (57°C),
155°F (68°C), 175°F (79°C) 200°F (93°C),
286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - brass
- Spring - teflon coated nickel alloy
- Retainer - brass
- Pin - stainless steel
- Torsion spring - stainless steel
- Bulb - glass with alcohol based solution, 3mm size
- Orifice insert -brass
- 3/4" NPT or 1" NPT
- Outer tube - galvanized steel pipe
- Inner tube - stainless steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225 °F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 5.6 (80 metric) | 3/4" NPT or 1"NPT |
cULus Variable FM Variable to |
Factory Bronze Satin Chrome1 Bright Chrome White Polyester Black Polyester Lead Coated2 |
| 8.1 (116 metric) | 1"NPT |
Note:
- Metric conversions are approximate.
- cULus listed corrosion resistant: Polyester must be specified on order.
- 1Finishes available on special order.
- 2Lead Coated is UL approved only.
Approvals
| Style | Sin Model | K Factor | Thread Size | 135°F (57°C) | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | 286°F (141°C) | *FM | cULus | NYC-DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Pendent | GL5635 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5636 | 5.6 | 3/4" NPT | • | • | • | • | • | • | • | ||
| GL8135 | 8.1 | 1" NPT | • | • | • | • | • | • | • | ||
| Recessed Pendent |
GL5635 | 5.6 | 1" NPT | • | • | • | • | • | • | • | • |
| GL5636 | 5.6 | 3/4" NPT | • | • | • | • | • | • | • | ||
| GL8135 | 8.1 | 1" NPT | • | • | • | • | • | • | • |
Note:
- Listed for ALL hazards.
- *Pendent style - FM Approved 155°F, 200°F, and 286°F
- *Recessed Pendent style - FM Approved 155°F and 200°F
Cross Section

Installation Data
Globe GL Series Dry Pendent sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.
When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
- Quantity - Recessed Wrenches - P/N 337014
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
- Escutcheons desired
- "A" Dimension - Distance from face of fitting to the finished ceiling line regardless of escutcheon used.
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Horizontal Sidewall
A-47 Extended Coverage Light Hazard Horizontal Sidewall Concealed Sprinkler
Concealed Extended Coverage Horizontal Sidewall For Light Hazard Occupancies
Description and Operation
The Globe Quick Response GL5613 and GL8113 Extended Coverage Horizontal Sidewall Adjustable Concealed Sprinkler for light hazard occupancies, have the lowest profile available for this type of sprinkler, providing an aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards, and in accordance with NFPA 13. The sprinkler has 1/2” of adjustment for ease of installation. All that is seen on the wall is a 3 1/4” diameter wall plate color finished to match the specifiers exact requirements. In addition to making the sprinkler much less noticeable, the wall plate assembly also provides protection for the sprinkler from flying or hanging objects.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. The 3mm frangible glass ampule provides sprinkler operation approximately six times faster than standard response sprinklers, they can also be installed wherever standard extended coverage horizontal sidewall sprinklers are specified. The wall plate is soldered to the sprinkler’s special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the quick response sprinkler. At the rated temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F |
38°C |
| Intermediate | 175°F | 79°C | Yellow | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Finishes* |
|---|---|---|
| 5.6 (80 metric) | 1/2" NPT |
Bright Chrome |
| 8.1 (116 metric) | 3/4" NPT |
Note:
- Metric conversions are approximate.
- *Finishes available on special order. For painted plates other than white, contact
- Globe for ordering specifications.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) w/plate 135°F (57°C) | 155°F (57°C) w/plate 135°F (57°C) | 175°F (79°C) w/plate 155°F (68°C) | cULus | NYC - DOB MEA - 101-92-E |
|---|---|---|---|---|---|---|---|
| Concealed Sidewall |
GL5613 | 5.6 | • | • | • | • | • |
| GL8113 | 8.1 | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| Model # | K- Factor | Temp. | Ceiling to Deflector Distance | Width of Coverage | Length of Coverage | Min. Pressure P.S.I. | FLOW IN G.P.M. |
|---|---|---|---|---|---|---|---|
| GL5613 | 5.6 | 135°F / 57°C 155°F / 68°C 175°F / 79°C |
4" TO 6" | 16' | 16' | 26.8 | 29 |
| 16' | 18' | 26.8 | 29 | ||||
| 16' | *20' | 32.7 | 32 | ||||
| 6" TO 12" | 16' | 16' | 32.7 | 32 | |||
| 16' | 18' | 32.7 | 32 | ||||
| 16' | *20' | 32.7 | 32 | ||||
| GL8113 | 8.1 | 135°F / 57°C 155°F / 68°C 175°F / 79°C |
4" TO 12" | 16' | 16' | 10.3 | 26 |
| 4" TO 6" | 16' | 18' | 12.8 | 29 | |||
| 6" TO 12" | 16' | 18' | 15.6 | 32 | |||
| 135°F / 57°C 175°F / 79°C |
4" TO 6" | 16' | *20' | 15.6 | 32 | ||
| 6" TO 12" | 16' | *20' | 20.9 | 37 |
NOTE:
- * 155°F not listed in 16' x 20' room size, use either 135°F or 175°F.
- 7' minimum spacing for GL5613 and 6' minimum spacing for GL8113.
Cross Section
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - 5.6K Wrenches - P/N 329678
- Quantity - 8.1K Wrenches - P/N 329679
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Extra Large Orifice
A-48 ELO 13 Pendent Sprinkler - GL1114
Model GL1114 Pendent Extra Large Orifice Automatic Sprinklers For Use in NFPA 13 Systems
Description and Operation
The Globe Quick Response Model GL1114 Extra Large Orifice Pendent Sprinkler for use in NFPA 13 Systems is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. The main use of this sprinkler is when minimal pressure is available and the use of smaller size orifice sprinklers would require the installation of a pump. This sprinkler series is available in upright and pendent styles, various temperature ratings and several finishes to meet many varying design requirements.
The heart of Globe's Model GL1114 sprinkler proven actuating assembly is a hermetically sealed frangible glass am- pule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
Technical Data
- Temperature Ratings - 155°F (68°C)
175°F (79°C), 200°F (93°C), 286°F (141°C) - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Red | 100°F |
38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Lenth | Finishes |
|---|---|---|---|
| 11.5 (166 metric) | 3/4" NPT | 2 7/16 (6.19cm) |
Factory Bronze |
NOTE:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2C-U.L. Listed corrosion resistant - polyester must be specified on order.
Approvals
| Style | Sin Model | K Factor | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | 286°F (141°C) | cULus | NYC - DOB MEA - 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Pendent | GL1114 | 11.5 | • | • | • | • | • | • |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 333010
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Horizontal Sidewall
A-47a Extended Coverage Light Hazard Horizontal Sidewall Sprinkler - GL8114
Concealed Extended Coverage Horizontal Sidewall For Light Hazard Occupancies Model GL8114
Description and Operation
The Globe Quick Response GL8114 Extended Coverage Horizontal Sidewall Adjustable Concealed Sprinklers for light hazard occupancies have the lowest profile available for this type of sprinkler, providing an aesthetically pleasing design. They can be installed wherever standard extended coverage horizontal sidewall sprinklers are specified when allowed by the applicable standards, and in accordance with NFPA 13. The sprinkler has 1/2” of adjustment for ease of installation. All that is seen on the wall is a 3 1/4” diameter wall plate color finished to match the specifiers exact requirements. In addition to making the sprinkler much less noticeable, the wall plate assembly also provides protection for the sprinkler from flying or hanging objects.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. At the rated temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. The wall plate is soldered to the sprinkler’s special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the quick response sprinkler.
Technical Data
- Temperature Ratings - 135°F (57°C) Sprinkler,
135°F (57°C) Cover Plate - Water Working Pressure Rating - 175 psi (12 Bars)
- Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F | 57°C | Orange | 100°F | 38°C |
Specifications
| Nominal 'K' Factor | Thread Size | Finishes* |
|---|---|---|
| 8.1 (116 metric) | 3/4" NPT | Bright Chrome White Painted *Satin Chrome *Bright Brass *Other Painted Surfaces |
Note:
- Metric conversions are approximate.
- *Finishes available on special order. For Painted plates other than white, contact
- Globe for ordering specifications.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) w/plate 135°F (57°C) | cULus | NYC - DOB MEA - 101-92-E |
|---|---|---|---|---|---|
| Concealed Sidewall |
GL8114 | 8.1 | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| Model # | K-Factor | Temp. | Ceiling to Deflector Distance | Width of Coverage | Length of Coverage | MIN. PRESSURE P.S.I. | FLOW IN G.P.M. |
|---|---|---|---|---|---|---|---|
| * GL8114 | 8.1 | 135°F / 57°C |
4" TO 6" | 16' | 22' | 19.8 | 36 |
| 16' | 24' | 23.2 | 39 | ||||
| 6" TO 12" | 16' | 22' | 24.4 | 40 | |||
| 4" TO 12" | 18' | 20' | 19.8 | 36 | |||
| 18' | 22' | 24.4 | 40 |
NOTE:
- * 6' Minimum Spacing
Cross Sections
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - 8.1K Wrenches - P/N 329679
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Horizontal Sidewall
A-46 Extended Coverage Light Hazard Horizontal Sidewall Sprinker - GL8128 & GL8129
Extended Coverage Automatic Sprinklers Model GL8128, GL8129 Horizontal Sidewall
Description and Operation
The Globe Quick Response Models GL8128 and GL8129 Extended Coverage Horizontal Sidewall Sprinklers are a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While this Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard extended coverage horizontal sprinklers are specified; but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction, in accordance with their listings and in accordance with NFPA 13.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C) - Water Working Pressure Rating -
175 psi (1207 kPa) - Factory tested hydrostatically to 500 psi (3448 kPa)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 8.1 (116 metric) | 3/4" NPT | 3" (7.6.cm) | Factory Bronze *Satin Chrome Bright Chrome +White Polyester +Black Polyester *Lead Coated |
NOTE:
- Metric conversions are approximate.
- *Other finishes available on special order.
- +Available as cULus listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Sidewall | GL8128 | 8.1 | • | • | • | • | • | • |
| GL8129 | 8.1 | • | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| Sin Model* | Style | Temp. | Ceiling to Deflector Distance | Width of Coverage | Length of Coverage | Min. Pressure P.S.I. | FLOW IN G.P.M. |
|---|---|---|---|---|---|---|---|
| GL8128 | Standard & Recessed |
135°F / 57°C 155°F / 68°C 175°F / 79°C 200°F / 93°C |
4" TO 6" | 16' | 16' | 10.3 | 26 |
| 18' | 12.8 | 29 | |||||
| GL8129 | Standard & Recessed |
135°F / 57°C 155°F / 68°C 175°F / 79°C |
6" TO 12" | 16' | 10.3 | 26 | |
| 18' | 12.8 | 29 | |||||
| GL8128 | Standard & Recessed |
135°F / 57°C | 4" TO 6" | 20' | 16'.6 | 33 | |
| GL8129 | 6" TO 12" | ||||||
| GL8128 | Standard | 175°F / 79°C | 4" TO 6" | ||||
| GL8129 | 6" TO 12" | ||||||
| GL8128 | Standard & Recessed |
135°F / 57°C | 4" TO 6" | **22' | 20.8 | 37 | |
| GL8129 | 6" TO 12" | **24' | 26.8 | 42 |
*Minimum 6' sprinkler spacing
**Listed with recessed cup with 1/2" adjustment
Cross Sections
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 312366
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Horizontal Sidewall
A-44 Extended Coverage Light Hazard Horizontal Sidewall Sprinkler - GL5628
Extended Coverage Automatic Sprinklers Model GL5628 Horizontal Sidewall
Description and Operation
The Globe Quick Response Model GL5628 Extended Coverage Horizontal Sidewall Sprinkler is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While these Quick Response Sprinklers provide an aesthetically pleasing appearance, they can be installed wherever standard extended coverage horizontal sprinklers are specified; but offer the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction, in accordance with their listings and in accordance with NFPA 13.
The heart of Globe's Model GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C) - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/2" (7.6 cm) | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
NOTE:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as cULus listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | cULus | NYC-DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Sidewall | GL5628 | 5.6 | • | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| Model # | Style | Temp. | Ceiling to Deflector Distance | Width of Coverage | Length of Coverage | Min. Pressure P.S.I. | Flow in G.P.M. |
|---|---|---|---|---|---|---|---|
| GL5628 | Standard & Recessed |
135°F/57°C 155°F/68°C 175°F/79°C |
4" TO 12" | 16' | 16' | 21.6 | 26 |
| 16' | 18' | 26.8 | 29 | ||||
| 18' | 18' | 32.7 | 32 | ||||
| Standard & Recessed |
200°F/93°C | 4" TO 6" | 16' | 16' | 21.6 | 26 | |
| 16' | 18' | 26.8 | 29 | ||||
| 18' | 18' | 32.7 | 32 |
Cross Section
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Standard Wrenches - P/N 325390
- Quantity - Recessed Wrenches - P/N 325391
- Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Extended Coverage Light Hazard Sprinklers » Extended Coverage Light Hazard Pendent
A-41 Extended Coverage Light Hazard Pendent Sprinkler - GL8109
Extended Coverage Light Hazard Automatic Sprinklers Model GL8109 Pendent
Description and Operation
The Globe Quick Response Model GL8109 Extended Coverage Pendent Sprinkler for Light Hazard occupancies is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While this Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard light hazard extended coverage pendent sprinklers are specified; but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction, in accordance with their listings and in accordance with NFPA 13.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.
Technical Data
- Temperature Ratings -
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C) - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C) - Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 8.1 (116 metric) | 3/4" NPT | 3" (7.6 cm) | Factory Bronze Satin Chrome1 Bright Chrome White Polyester2 Black Polyester2 Lead Coated1 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
- 2Available as cULus listed corrosion resistant when specified on order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | cULus |
|---|---|---|---|---|---|---|---|
| Pendent | GL8109 | 8.1 | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards Only
| Sin Model | Style | Temp | Area of Coverage | MIN. PRESSURE P.S.I. | Flow in G.P.M. |
|---|---|---|---|---|---|
| GL8109 | Standard & Recessed |
135°F / 57°C 155°F / 68°C 175°F / 79°C 200°F / 93°C |
16' x 16' | 10.3 | 26 |
| 18' x 18' | 16.6 | 33 | |||
| 135°F / 57°C | 20' x 20' | 24.4 | 40 |
Note: Due to height spray pattern created by this sprinkler, there must be a minimum spacing of 8'-0" between sprinklers to eliminate the risk of cold soldering.
Cross Section
Click image above for a detailed view of this product
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 312366
- Quantity - Recessed Wrenches - P/N 325401, Rev. D
- Quantity - Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Intermediate In-Rack Storage Sprinklers
A-39 Intermediate Level Upright & Pendent Sprinkler
Automatic Sprinklers GL Series Intermediate Level Upright • Pendent
Description and Operation
The Globe Quick Response GL Series Intermediate Level Sprinklers are primarily designed for use in rack storage sprinkler systems, where their thermosensitive elements must be shielded from the water spray of higher elevation sprinklers which could operate earlier during a fire. The Globe GL Series Sprinkler is a low profile yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. The Quick Response Sprinkler can be installed wherever standard intermediate level sprinklers are specified. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction and in accordance with their listings.
The Globe Intermediate Level Sprinklers are available in either upright or pendent styles, with 1/2" or 17/32" orifices, in various temperature ratings and with various finishes to meet customer requirements. Each unit is factory fitted with a water shield having a 3 25/32" diameter. Either style may be provided with sprinkler head guards for use where mechanical injury might be expected.
The heart of Globe’s GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern depending upon the deflector style used.
Technical Data
- Temperature Ratings
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C) - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Shield - brass or steel - 3 25/32" diameter.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
| High | 286°F | 141°C | Blue | 225°F | 107°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes* |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | Factory Bronze |
| 7.8 (111 metric) | 1/2" NPT | 2 1/4" (5.7 cm) | |
| 8.1 (116 metric) | 3/4" NPT | 2 7/16" (6.2 cm) |
Note:
- Metric conversions are approximate.
- *Other finishes available on request.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) | 155°F (68°C) | 175°F (79°C) | 200°F (93°C) | 286°F (141°C) | cULus | FM |
|---|---|---|---|---|---|---|---|---|---|
| Upright | GL5617 | 5.6 | • | • | • | • | • | • | • |
| GL8117 | 7.8* | • | • | • | • | • | • | • | |
| GL8120 | 8.1 | • | • | • | • | • | • | • | |
| Pendent | GL5612 | 5.6 | • | • | • | • | • | • | • |
| GL8112 | 7.8* | • | • | • | • | • | • | • | |
| GL8108 | 8.1 | • | • | • | • | • | • | • |
* 17/32" X 1/2" NPT.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Temperature
- Finishes desired
- Quantity - Wrenches - P/N 325390 (1/2"); P/N 312366 (L.O.)
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » "The Inch" - One Inch Adjustable Pendent
A-38 “The Inch” One Inch Adjustable Concealed Pendent - GL5606
Quick Response
"The Inch" Automatic Sprinklers Model GL5606, One Inch Adjustable Concealed Pendent
Description and Operation
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile, aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 2¾" diameter ceiling plate color finished to match the specifier's exact requirements. The GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be installed. The "push on - screw off" designed cover plate is easily installed and with a nominal 1" inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the 3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved pattern to extinguish or control the fire.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating
- 175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Deflector - brass
- Screw - brass
- Frame - bronze
- Bulb seat - brass
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Drop Pin - stainless steel
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
- Globe's wrench P/N 332765 must be used to install this sprinkler.
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature | ||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 5.6 (80 metric) | 1/2" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted1 Satin Chrome1 Other Painted Finishes1 |
Note:
- Metric conversions are approximate.
- 1Finishes available on special order.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 155°F (68°C) with plate 155°F (68°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus | *FM |
NYC-DOS |
|---|---|---|---|---|---|---|---|---|---|---|
| Adjustable Concealed Pendent |
GL5606 | 5.6 | • | • | • | • | • | • | • | • |
Note:
- *FM Approved as Standard Response
Cross Section
Click image above for a detailed view of this product.
| Optional Cover Plate Sizes | White 135°F Part # | White 155°F Part # | Chrome 135°F Part # | Chrome 155°F Part # |
|---|---|---|---|---|
| 2 3/4" | 332726 | 332731 | 332724 | 332729 |
| 3 5/16" | 332706 | 332711 | 332704 | 332709 |
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Adjustable Concealed Wrenches - P/N 332765
Product Related Documents
Download this page as a pdfSprinklers » Standard Spray Sprinklers » Concealed Pendent » Extended Coverage Light Hazard Sprinklers
A-37 Extended Coverage Light Hazard Concealed (Dome) Pendent Sprinkler - GL8104
Automatic Sprinklers Model GL8104 Concealed Pendent
Description and Operation
The Globe Quick Response Model GL8104 Extended Coverage Concealed Pendent Sprinkler is a low profile, aesthetically pleasing design. It provides sprinkler operation approximately six times faster than ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified when allowed by the applicable standards, and in accordance with NFPA 13. It offers the additional feature of greatly increased safety to life and should be used advisedly and under the direction of approving authorities having jurisdiction. All that is seen at the ceiling is a 3 9/32" diameter ceiling plate color finished to match the specifier's exact requirements. The Model GL8104 Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule type sprinkler which is located above the ceiling and concealed from view by the ceiling plate. The ceiling plate is soldered to the sprinkler's special upper support assembly in three places. Upon the application of sufficient heat, the plate falls to the floor exposing the quick response pendent spray sprinkler. At the ampule's rated temperature, the sprinkler opens discharging water onto the floor in its required and approved distribution pattern.
A special spring is attached to the pendent sprinkler deflector that serves to provide a constant tension against the ceiling plate. This feature virtually ensures freedom from environmental vibration problems.
Technical Data
- Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate - Water Working Pressure Rating -
175 psi (12 Bars) - Factory tested hydrostatically to 500 psi (34 Bars)
- Maximum low temperature glass bulb rating is
-67°F (-55°C)
- Frame - bronze
- Deflector - brass
- Screw - brass
- Bulb seat - copper
- Spring - nickel alloy
- Seal - teflon
- Bulb - glass with alcohol based solution, 3mm size
- Cover Plate - brass
- Upper Escutcheon Assembly - steel
Sprinkler Temperature Rating/Classification and Color Coding
| Classification | Available Sprinkler Temperatures | Bulb Color | N.F.P.A. Maximum Ceiling Temperature |
||
|---|---|---|---|---|---|
| Ordinary | 135°F/155°F | 57°C/68°C | Orange/Red | 100°F | 38°C |
| Intermediate | 175°F/200°F | 79°C/93°C | Yellow/Green | 150°F | 66°C |
Specifications
| Nominal 'K' Factor | Thread Size | Length | Finishes |
|---|---|---|---|
| 8.1 (116 metric) | 3/4" NPT | 2 1/2" (6.4 cm) | Bright Chrome White Painted *Satin Chrome *Bright Brass *Other Painted Finishes |
Note:
- Metric conversions are approximate.
- *Finishes available on special order. For painted plates other than white, contact Globe
- for ordering specifications.
Approvals
| Style | Sin Model | K Factor | 135°F (57°C) with plate 135°F (57°C) | 155°F (68°C) with plate 135°F (57°C) | 175°F (79°C) with plate 155°F (68°C) | 200°F (93°C) with plate 155°F (68°C) | cULus | NYC - DOB MEA 101-92-E |
|---|---|---|---|---|---|---|---|---|
| Concealed Pendent |
GL8104 | 8.1 | • | • | • | • | • | • |
U.L. Listing Design - Use Requirements For Light Hazards
| Style | Sin Model | Tempr | Room Size | MIN. PRESSURE P.S.I. | FLOW G.P.M. |
|---|---|---|---|---|---|
| Concealed Pendent |
GL8104 | 135°F / 57°C 155°F / 68°C 175°F / 79°C 200°F / 93°C |
16' x 16' | 10.3 | 26 |
| 18' x 18' | 15.6 | 32 | |||
| 135°F / 57°C | 20' x 20' | 24.4 | 40 |
Minimum 8' Sprinkler Spacing
Cross Section
Click image above for a detailed view of this product.
Ordering Information
When ordering please specify the following.
- Quantity
- Model Number
- Style
- Orifice
- Thread Sizes
- Temperature
- Finishes desired
- Quantity - Concealed Wrenches - P/N 325401
- Quantity - Protective Caps - P/N 327119
Product Related Documents
Related Products
Globe Product Warranty
Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).
Bulletin: GL4906 Last Revised: September 2011 Revision: 1
Bulletin: CLEAN ROOM Last Revised: May 2009
Bulletin: EQ ESCUTCHEON Last Revised: May 2009
Bulletin: EQ ESCUTCHEON Last Revised: May 2009
Bulletin: GL5679-EQ Last Revised: August 2010 Revision: 1
Bulletin: GL8159-EQ Last Revised: May 2009
Bulletin: GL5635-EQ Last Revised: July 2010 Revision: 1
Bulletin: GL8109-EQ Last Revised: May 2009
Bulletin: GL5651-EQ Last Revised: April 2009
Bulletin: BULLETIN GL2801-EQ Last Revised: April 2009
Bulletin: BULLETIN GL 3010 Last Revised: September 2011 Revision: 1
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: GL4202 Last Revised: December 2009
Bulletin: GL4252 Last Revised: December 2009 Revision: 1
Last Revised: July 2009
Bulletin: GL5653-EQ Last Revised: April 2010 Revision: 1
Bulletin: GL5653/5606 Last Revised: May 2009 Revision: 7
Bulletin: GL5606-EQ Last Revised: April 2009 Revision: 2
Bulletin: BULLETIN ONE INCH ADJ CONC Last Revised: March 2008 Revision: 3
Bulletin: 3 Last Revised: March 2008 Revision: BULLETIN MILL CAUTION
Bulletin: 10 Last Revised: July 2010 Revision: BULLETIN DRY CAUTION
Bulletin: 4 Last Revised: March 2008 Revision: BULLETIN CAUTION
Bulletin: STDR Last Revised: June 2002 Revision: 2
Bulletin: SPRCAB Last Revised: August 2002 Revision: 2
Bulletin: GL5610 Last Revised: September 2011 Revision: 1
Bulletin: SPRWR Last Revised: July 2009 Revision: 3
Bulletin: ESCUTCH Last Revised: October 2007 Revision: 2
Bulletin: A05-176-06 Last Revised: July 1999 Revision: 491
Bulletin: A05-972-02 Last Revised: November 1999 Revision: 578
Bulletin: A05-177-05 Last Revised: November 1999 Revision: 566
Last Revised: March 2002
Last Revised: March 2009
Last Revised: March 2009
Last Revised: March 2002
Bulletin: A05-180-06 Last Revised: June 2000 Revision: 45
Bulletin: TESTDRAIN Last Revised: December 2009 Revision: 1
Bulletin: BUTTERFLY Last Revised: February 2010 Revision: 4
Bulletin: BUTTERFLY Last Revised: February 2010 Revision: 4
Bulletin: BUTTERFLY Last Revised: February 2010 Revision: 4
Bulletin: BUTTERFLY Last Revised: February 2010 Revision: 4
Bulletin: RCV Last Revised: January 2010 Revision: 3
Bulletin: JFN Last Revised: February 2008 Revision: 4
Bulletin: WS Last Revised: June 2002 Revision: 3
Bulletin: H2,3 REV #1 Last Revised: July 2010
Bulletin: H1 REV #1 Last Revised: July 2010
Bulletin: AAFD Last Revised: June 2002 Revision: 3
Bulletin: DPV-D Last Revised: February 2007 Revision: 3
Bulletin: DPV-F-3 Last Revised: June 2002 Revision: 5
Bulletin: RET.CHM. Last Revised: June 2002 Revision: 2
Bulletin: BULLETIN ACV-8H Last Revised: May 2003 Revision: 2
Bulletin: ACV Last Revised: August 2010 Revision: 7
Bulletin: WM Last Revised: August 2002
Bulletin: ESCUTCH Last Revised: October 2007 Revision: 2
Bulletin: ASB-ESCTL Last Revised: August 2002 Revision: 2
Bulletin: ASB-HG Last Revised: May 2006
Bulletin: ASB-HGWS Last Revised: May 2006
Bulletin: GL5687 Last Revised: August 2010 Revision: 9
Bulletin: GL5683 Last Revised: April 2007 Revision: 8
Bulletin: GL5685 Last Revised: August 2010 Revision: 14
Bulletin: GL5677 Last Revised: August 2010 Revision: 9
Bulletin: GL5681 Last Revised: August 2010 Revision: 12
Bulletin: GL5679 Last Revised: August 2010 Revision: 11
Bulletin: GL1167 Last Revised: August 2002 Revision: 1
Bulletin: GL1160 Last Revised: March 2003 Revision: 2
Bulletin: GL8128-STD Last Revised: October 2003 Revision: 5
Bulletin: GL8159 Last Revised: October 2003 Revision: 3
Bulletin: GL5653 Last Revised: January 2004 Revision: 3
Bulletin: GL300PSIAC Last Revised: April 2004 Revision: 2
Bulletin: GL5655 Last Revised: October 2003 Revision: 2
Bulletin: GL2856 Last Revised: October 2003 Revision: 3
Bulletin: GL2854 Last Revised: December 2006 Revision: 7
Bulletin: GL5653 Last Revised: July 2009 Revision: 6
Bulletin: GL300PSIR Last Revised: September 2004 Revision: 2
Bulletin: GL5651 Last Revised: April 2009 Revision: 8
Bulletin: GL300PSI Last Revised: September 2004 Revision: 1
Bulletin: GL5661 Last Revised: December 2006 Revision: 3
Bulletin: GL5643 Last Revised: August 2010 Revision: 8
Bulletin: GL5639 Last Revised: August 2010 Revision: 9
Bulletin: GL5641 Last Revised: July 2010 Revision: 14
Bulletin: GL5649 Last Revised: July 2010 Revision: 10
Bulletin: GL5637 Last Revised: July 2010 Revision: 13
Bulletin: GL1123 Last Revised: October 2002 Revision: 3
Bulletin: GL5635 Last Revised: July 2010 Revision: 13
Bulletin: GL5613 Last Revised: February 2005 Revision: 7
Bulletin: GL1114 Last Revised: August 2002 Revision: 2
Bulletin: GL8114 Last Revised: February 2005 Revision: 1
Bulletin: GL8128 Last Revised: October 2003 Revision: 5
Bulletin: GL5628 Last Revised: July 2009 Revision: 5
Bulletin: GL8109 Last Revised: July 2005 Revision: 5
Bulletin: GL5603 Last Revised: June 2003 Revision: 3
Bulletin: GL5606 Last Revised: July 2009 Revision: 5
Bulletin: GL8104 Last Revised: July 2005 Revision: 6