Print this page Download this page as a pdf
Dry Sprinklers » Dry Type Horizontal Sidewall

A-58 Dry Type Horizontal Sidewall Sprinkler

Automatic Sprinklers GL Series Dry Type Horizontal Sidewall Recessed Horizontal Sidewall

Description and Operation

Sprinklers

The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples.

The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction.

The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern.

Technical Data

  • Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C)
  • Water Working Pressure Rating - 175 psi (12 Bars)
  • Factory tested hydrostatically to 500 psi (34 Bars)
  • Maximum low temperature glass bulb rating is
    -67°F (-55°C)
  • Frame - bronze
  • Deflector - brass
  • Screw - brass
  • Bulb seat - brass
  • Spring - teflon coated nickel alloy
  • Retainer - brass
  • Pin - stainless steel
  • Torsion spring - stainless steel
  • Bulb - glass with alcohol based solution, 3mm
  • Orifice insert - brass
  • 3/4" NPT or 1" NPT
  • Outer tube - galvanized steel pipe
  • Inner tube - stainless steel

Sprinkler Temperature Rating/Classification and Color Coding

ClassificationAvailable Sprinkler TemperaturesBulb ColorN.F.P.A. Maximum Ceiling Temperature
Ordinary 135°F/155°F 57°C/68°C Orange/Red 100°F 38°C
Intermediate 175°F/200°F 79°C/93°C Yellow/Green 150°F 66°C
High 286°F 141°C Blue 225 °F 107°C

Specifications

Nominal 'K' FactorThread SizeLength2Finishes
5.6 (80 metric) 3/4" or 1" NPT

cULus
Variable to
48"

FM
Variable to
36"


Factory Bronze
1Satin Chrome
Bright Chrome
White Polyester
Black Polyester
2Lead Coated
8.1 (116 metric) 1" NPT
Note:
  • Metric conversions are approximate.
  • cULus listed corrosion resistant: Polyester must be specified on order.
  • 1 Finishes available on special order.
  • 2Lead Coated is UL approved only.

Approvals

StyleSin
Model
K
Factor
Thread
Size
135° F
57° C
155° F
68° C
175° F
79° C
200° F
93° C
286°F
141° C
*FMcULusNYC - DOB
MEA 101-92-E
Horizontial
Sidewall
GL5641 5.6a 1" NPT
GL5642 5.6a 3/4" NPT  
GL8141 8.1b 1" NPT  
Recessed
Horizontial
Sidewall
GL5641 5.6a 1" NPT
GL5642 5.6a 3/4" NPT  
GL8141 8.1b 1" NPT  
Note:
  • aListed for light hazard only with deflector from 4" - 12" below the ceiling.
  • bListed for light and ordinary hazard with deflector from 4" - 12" below the ceiling.
  • * Recessed Horizontal Sidewall - FM Approved 155°F and 200°F only.
  • * Horizontal Sidewall - FM Approved 155°F, 200°F, and 286°F only.

Cross Sections


Important Installation Data

Globe GL Series Dry Horizontal Sidewall sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit.

When installed in a wet system extending into a freezing area, see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs.  Please refer to our Dry Caution Sheet for further important installation data.

Ordering Information

When ordering please specify the following.

  • Quantity
  • Model Number
  • Style
  • Orifice
  • Temperature
  • Finishes desired
  • Quantity - Wrenches - P/N 333010
  • Quantity - Recessed Wrenches - P/N 337014
  • Quantity - Protective Caps - P/N 327109-CAP (Friction Fit
    Recessed)
  • Escutcheons desired
  • "A" Dimension - Distance from face of fitting to the finished ceiling regardless of escutcheon used.

Product Related Documents

Related Products

Globe Product Warranty

Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

Bulletin: GL5641   Last Revised: July 2010   Revision: 14